FT2GAS
Gaseous Extinguishing System
Rev No. 1.3
41
Typical
I
A
calculations:
Items
Qiescent
Current
(mA)
Alarm
Current
(mA)
Qty
Total Alarm
Current (mA)
FT2GAS
75
250
1
250
Local Control Station (LCS)
0
60
3
180
“Fire Alarm / Do Not Enter” Sign
0
95
3
285
“Fire Alarm / Evacuate” Sign
0
95
3
285
“System Inoperative” Sign
0
95
3
285
3A Gas Discharge for 1 min
0
50
Optional Tone / Voice Sounders
0
135
6
810
Total Load current (mA)
75
1995
C20, Required Battery Capacity =
=
11.15
Ah
Battery Charger Calculations
Battery charger Ah required for 96 hours=
(5xI
Q
)
+ F
c
(0.5xI
A
)
=
(5x0.075) + 2(0.5x1.145)
=
1.52
Ah
Battery charging current required =
=
1.52/(96x0.75)
=
21.11
mA
1.2[(0.2(1.995x0.5+0.05)]
,where
η
is efficiency of
battery manufacturer typically
75%-85% (BB Battery)
η
×
Q
T
Required
Ah
Charger
Battery
Therefore, a battery capacity close to 11Ah battery or next higher with a battery charging current of
21.11 mA would be sufficient for this example.
Standard FT2GAS is equipped with 5.5 Amp switch mode power supply and space for 12 AH SLA
batteries.
Содержание FireTracker FT2GAS
Страница 1: ...Operation Technical Manual FT2GAS Rev 1 3 Gaseous Extinguishing System FT2GAS M320 Dec 2019...
Страница 2: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 2...
Страница 55: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 55 5 BLOCK WIRING DIAGRAM Figure 19 FT2GAS Block Wiring Diagram...
Страница 56: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 56 Figure 20 FT2GAS Warning Signs Connection Diagram...
Страница 57: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 57 Figure 21 Warning Sign with Voice and Timer connection...