FT2GAS
Gaseous Extinguishing System
Rev No. 1.3
17
2.5
CIE Inputs and Outputs
2.5.1
Fire Detection Zone Inputs
The zone specifications and the compatible devices are listed Table 8 below.
2.5.1.1
ZONE INPUT CIRCUIT SPECIFICATIONS
Table 8 Zone Input
Item
Description
Number of zones in one CIE
2 zones
Number of detectors per zone
0 – 40, including Manual Call Points (MCPs) if any
Maximum number of detectors in alarm per
zone
Up to 2 detectors per zone, including MCPs, heat and/or
smoke detectors.
Zone current per zone
0 – 51mA
Typical Zone quiescent current per zone
5mA
Typical zone input resistance in alarm
conditions per zone
560 Ohm
The typical zone input circuit is shown in Figure 3 below
Figure 3 Zone Input Circuit
Each zone input circuit is fully supervised for open circuit and short circuit faults. The EOL resistor type
is 3K9, 1W, 1%, metal film.
2.5.1.2
ZONE INPUTS COMPATIBLE ACTUATING DEVICES
Table 9 Compatible devices
Part No.
Description
4452
Conventional multi detector (recommended)
Note:
Only smoke detectors can be used in gaseous extinguishing systems.
Содержание FireTracker FT2GAS
Страница 1: ...Operation Technical Manual FT2GAS Rev 1 3 Gaseous Extinguishing System FT2GAS M320 Dec 2019...
Страница 2: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 2...
Страница 55: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 55 5 BLOCK WIRING DIAGRAM Figure 19 FT2GAS Block Wiring Diagram...
Страница 56: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 56 Figure 20 FT2GAS Warning Signs Connection Diagram...
Страница 57: ...FT2GAS Gaseous Extinguishing System Rev No 1 3 57 Figure 21 Warning Sign with Voice and Timer connection...