FT2GAS
Gaseous Extinguishing System
Rev No. 1.3
33
4.1.3
Warning Signs PCB Layout
Figure 11 Brooks Warning Signs PCB Layout
Table 16 Warning Signs DIP Switch Setting
Purpose
Switch
Number
Status
1 = ON
0 = OFF
Description
Mode
SW1
1
Single
mode, the whole sign illuminates
0
Dual
mode,
level 1 alarm illuminates the top half “FIRE ALARM” while
level 2 alarm illuminates the bottom half “DO NOT
ENTER” or “EVACUATE”
Buzzer
SW2
1
Enable warning sign buzzer
0
Disable warning sign buzzer (default setting)
Sign Flashing
SW3
1
Enable sign flashing
0
Disable sign flashing (default setting)