13 

4  INSTALLATION AND COMMISSIONING 

 

This chapter provides  the  installation and commissioning guidelines. The installation and the 

commissioning of Brooks FT1-SB shall be carried out in accordance of AS3000. The block wiring 

diagram of FT1-SB is shown in Figure 6 below.

 

 

 

I

+

47

K

+

-

DET.

C

680

DET.

POWER SUPPLY

24V / 1A

A
N

V+

V-

PO

WER

MCP

EOL

3K9

24

V

0V

24V

24V

0V

0V

TX

TX

RX

RX

DI

SP

LAY

DE

TE

CT

OR

SUB930

SUB931/931S/932

FT1 - SB

DISPLAY MODULE

FT1 - SB

CONTROL MODULE

240V AC 

NO

NC

COM

NO

NC

COM

NO

COM

NC

NO

COM

NC

NO

COM

NC

DISABLE

CONTACT RATING

0.5A @ 24V DC

24VDC / 0.5 Amp

SUPERVISED

CONTACT RATING

0.5A @ 24V DC

CONTACT RATING

0.5A @ 24V DC

CONTACT RATING

0.5A @ 24V DC

CONTACT RATING

5A @ 24VDC / 240VAC 

ALARM

OUTPUTS

FAULT

OUTPUTS

N

 

                                                               

Figure 6 FT1-SB Block Wiring Diagram

 

 

4.1  Installation 

4.1.1  FT1-SB Installation 

1.  The control / termination module and the power supply are designed to be DIN rail mounted. 

It can be installed at a convenient location within the switchboard cabinet and connected to 

the display module via 4 core cable as sown in Figure 

7

 

2.  The display module is to be mounted via a standard 90x90mm square cut out on the 

front door of a switch board. Please refer to the mechanical drawing of the system 

cabinet as shown in Figure 8. 

3.  Before the installation is completed, check and secure all the electrical connections. 

 
 
 
 
 

Содержание Firetracker FT1-SB

Страница 1: ...SYSTEM MANUAL FT1 SB Single Zone FireAlarm System...

Страница 2: ...Issue Date Description Written By Checked By Draft 0 2 9 2008 Original Document A Shenouda C Orr Issue 1 4 11 11 Update drawing in figure 7 A Shenouda A Shenouda Issue 2 18 11 19 Change Brooks address...

Страница 3: ...OLS AND INDICATIONS 9 3 1 LED FLASH FUNCTIONS 9 3 2 BUZZER INDICATING PATTERN 9 3 3 CONTROL FUNCTIONS 10 3 4 CONTROL OUTPUTS 10 3 4 1 Non supervised outputs 10 3 4 2 Supervised Output 11 3 5 ZONE INPU...

Страница 4: ...e Input Circuit 12 Figure 6 FT1 SB Block Wiring Diagram 13 Figure 7 Control Termination Module Power Supply mounting 14 Figure 8 FT1 SB Front Display typical mounting 14 TABLE LIST Table 1 FT1 SB Spec...

Страница 5: ...ors and auxiliary outputs are available on the termination module The termination module is interfaced to the display module via RS232 Only 4 wires are required to connect the front display module to...

Страница 6: ...tact 30V 0 5 Amp Disable Relay Output Changeover zone disable relay contact 30V 0 5 Amp Dimensions Display Module 96mm x 96mm x 72mm H W D Termination Module 90mm x 106mm x 58mm H W D Power Supply 90m...

Страница 7: ...lity is segregated and includes a separate controls and LED indicators for each function i e alarm test fault test and disable isolate A Power ON and Common Fault indicators are provided to indicate t...

Страница 8: ...odule The termination and control module to be mounted on a DIN rail at a convenient location within the switchboard cabinet The module as shown in Figure 2 above provides the termination point for al...

Страница 9: ...ow Figure 3 Din rail Power supply Features Universal AC input Short circuit Overload Over voltage Protections Can be installed on a 35mm DIN rail LED indicator for power on No load power consumption C...

Страница 10: ...nction Power On Steady On Power On Zone Alarm Flashing Steady on Alarm Test True Alarm Zone Fault Flashing Steady Fault Test Open or short circuit fault Zone Disable Steady Zone outputs disabled Commo...

Страница 11: ...tected and verified before the alarm relays and buzzer become active Fault Test Fault LED flashes once every second Fault relay activate Perform zone fault test It takes approximately 3 seconds for th...

Страница 12: ...terminals on the control termination module The EOL resistor type is 47K 1 2W or 1W 1 metal film 3 5 Zone Input The zone input specifications and compatible devices are listed in Table 5 and Table 6...

Страница 13: ...296 Panasonic Conventional enclosed heat detector 80 degrees 6297 Panasonic Conventional enclosed heat detector 100 degrees 6298 Panasonic Conventional enclosed heat detector 120 degrees MRCSRR Menvie...

Страница 14: ...5A 24VDC 24VDC 0 5Amp SUPERVISED CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 5A 24VDC 240VAC ALARM OUTPUTS FAULT OUTPUTS N Figure 6 FT1 SB Block Wiring Dia...

Страница 15: ...FT1 SB System Manual MA370 Iss 2 14 Figure 7 Control Termination Module Power Supply mounting Rear Front Figure 8 FT1 SB Front Display typical mounting...

Страница 16: ...er ON LED on the power supply module is illuminated 2 On the front Display check that only the green Power ON LED is illuminated all other LED indicators should be extinguished 3 Measure the DC voltag...

Страница 17: ...ted zone open circuit and check the following Zone fault LED and common fault LED Illuminate steady Buzzer is pulsing once every 3 seconds Fault relay on the Control Termination Module is de energized...

Страница 18: ...cident neglect misuse unauthorized dismantling or contamination howsoever caused incorrect installation careless handling or where repairs have been made or attempted by others Onsite warranty repairs...

Страница 19: ...ent Abbotsford VIC 3067 Ph 03 9879 5294 SA P O Box 101 Woodville SA 5011 729A Port Road Woodville SA 5011 Ph 08 8347 0000 QLD P O Box 511 Archerfield QLD 4108 2 49 Boyland Ave Coopers Plains QLD 4108...

Отзывы: