FT1-SB System Manual
MA370 Iss. 2
16
4.2.3 Actual Test
Alarm Test
1. Using an aerosol smoke can, spray each smoke detector in turn and check the following:
•
Alarm LED illuminates steady
•
Buzzer is steady On
•
Alarm relays on the Control / Termination Module are energised
•
Supervised alarm output is active (24V on the terminals)
2. Press “Silence Buzzer” control, buzzer will silence.
3. Press “Reset” control, alarm relays de-energise and the alarm LED turns off
Fault Test
1. Remove the last detector in the circuit (EOL) to simulated zone open circuit and check
the following:
•
Zone fault LED and common fault LED Illuminate steady
•
Buzzer is pulsing once every 3 seconds
•
Fault relay on the Control / Termination Module is de-energized
2. Press “Silence Buzzer” control, buzzer will silence.
3. Re-mount the detector, check that the fault LED remains illuminated.
4. Press “Reset” control, fault LED turns off
Disable Test
1. Press disable control, ensure disable LED illuminates
2. Carry out an ALARM TEST as shown above, ensure the alarm LED illuminates but the
alarm outputs do not function.
3. Carry out a FAULT TEST as shown above, ensure the fault LED illuminates but the
fault outputs do not function.
4. Re press the disable control to re-enable the system.