background image

 

 

 

 

 

brookfield NB-2000-HD2 

                                            Table 1 
       Minimum

 

Closing Time (seconds) to Latch Check* 

                                                Door Weight (lbs.) 

 
Door 
Width(in.) 

 
   
20000 

 
 
25000 

 
 
30000 

 
 
35000 

 
 
40000 

 
 
45000 

 
 
50000 

 
 
55000 

 
 
60000 

     

48 

  37 

 41 

 44 

  48 

   51 

   55 

  57 

  60 

  63 

     

54 

  41 

 46 

 50 

  54 

   58 

   61 

  65 

  68 

  71 

     

60 

  46 

 51 

 55 

  60 

   64 

   68 

  72 

  75 

  79 

     

66 

  50 

 56 

 61 

  66 

   71 

   75 

  79 

  83 

  86 

     

72 

  55 

 61 

 66 

  72 

   77 

   82 

  86 

  90 

  94 

     

84 

  64 

 71 

 77 

  84 

   90 

   95 

  100 

  105 

  110 

     

96 

  73 

 81 

 89 

  96 

   103     109    115 

  120 

  125 

*PER ANSI 156.10.  For weights and widths not listed, TIME=(DOOR WIDTH) X (DOOR WEIGHT)^1/2 / 188

 

 

Minimum Opening Time (seconds) to Backcheck** 

**shall be set to the same criteria as closing times. 

 

 (Latchcheck or Backcheck): A door shall not close or 
open in the last 10 degrees in less than 1.5 seconds 

IMPORTANT: 

Operating door at speeds faster than those established in ANSI 156.10 will void warranty and may 
damage operator.                                                                                                     

 

 

Содержание NB-2000-HD2

Страница 1: ...brookfield industries inc Commercial Industrial Door Operator Installation Instructions C 99 W Hillside Ave Thomaston CT 06786 P 860 283 6211 F 860 283 6123 www bfimfg com info bfimfg com NB 2000 HD2...

Страница 2: ...1of this manual Assure all electrical wiring and grounding is installed as specified in this manual and as required by any local codes Proper installation can also reduce the risk of electrical shock...

Страница 3: ...that all personnel are clear of the path of this operator and the door that it is attached to 2 Assure that all fingers hands feet limbs and articles of clothing are clear of all moving parts and pinc...

Страница 4: ...eset by brookfield industries inc however we recommend these values be double checked with the Parameter sheet supplied 7 Install activation switches or push button stations a within sight of the door...

Страница 5: ...ead Door or Follow Door on the next screen Fig 5 then skip to step 5 Fig 2 Fig 3 Fig 4 Fig 5 4 Selecting Standard will give you the screen shown in Fig 6 Choose the appropriate serial number series of...

Страница 6: ...t Inputs to display the Input Diagnostic Screen Fig 10 Fig 10 The buttons down the left side represent an actual input to the PLC All standard Operator functions can be tested using these buttons The...

Страница 7: ...select Lead or Follow Door on the next screen then skip to step 6 4 For Standard operator choose the appropriate ship date of the operator on the next screen 5 You ll be given a display of the first t...

Страница 8: ...ose Enable preset to the Door Position value plus 30 units i e if the Door Position is 310 set the Auto Close Enable to 340 Note Some installations may require slightly higher lower values for best re...

Страница 9: ...2 77 82 86 90 94 84 64 71 77 84 90 95 100 105 110 96 73 81 89 96 103 109 115 120 125 PER ANSI 156 10 For weights and widths not listed TIME DOOR WIDTH X DOOR WEIGHT 1 2 188 Minimum Opening Time second...

Страница 10: ...10VAC THRU LEFT SIDE OF COVER 4 1 2 DIA THRU HOLES FOR 3 8 DIA GRADE 5 BOLTS TYP 6 PLACES TYP 2 PLACES FRONT ELEVATION SIDE ELEVATION L 110 VAC INPUT SPA CER REFERENCE LEGEND INSIDE COVER SPEED BOARD...

Страница 11: ...1 F E D 2 3 C B A 1 2 3 4 Date Material 6 7 Scale 8 F D E Checked by Drawn by Decimal Fractional Angular Tolerances 5 Revision note 6 Rev 7 B C Notes A Date Sign 8 Check...

Страница 12: ...NE FRONT ELEVATION SIDE ELEVATION SPEED BOARD LEGEND BRACKET DETAIL 1 F E D 2 3 C B A 1 2 3 4 Date Material 6 7 Scale 8 F D E Checked by Drawn by Decimal Fractional Angular Tolerances 5 Revision note...

Страница 13: ...6 4 294 4 1 1 5 6 1 4 4170 25 24 5 6 24 5 6 25 24 5 6 25 25 8 02765 8 176276 6 4 0 564 2 11 72 1 1 0 0 176 8 0 9 4 9 55 8 10 4 52 4 4 1 0 24 5 6 0 0276 CVG RRTQXGF D FCVG CVGTKCN brookfield industrie...

Страница 14: ......

Страница 15: ...ging Door Operator Information contained herein is exclusive property of brookfield industries inc and may not be duplicated in part or in whole without written consent Line Note 10 Review Page 2 for...

Страница 16: ...ators reverse M1 M2 at motor 11 When using receptacle style chargers ue GFC I type 12 Provides auto open during power loss 13 Additional N terminal block for battery backup only For 220 VAC Power See...

Страница 17: ...ic opening during power loss The battery backup system is an optional addition Relay 110 220 VAC Input IPDT 6A Output Note 9 NEMA Enclosure A2 14 Note 16 12 11 A1 Spacer 1 1 1 1 3 3 9 9 10 10 11 11 12...

Отзывы: