Default settings
Network configuration is done ex factory as indicated on the serial number label or in the technical specifications. The table
below shows the supported configurations for the available interface protocols (default settings are printed in boldface):
Protocol
(RS-232)
FLOW-BUS
(RS-485)
Modbus
(RTU/ASCII)
PROFIBUS DP
DeviceNet™
Address
3
3
…125
1
…247
0…
126
0…
63
Baud Rate
9600
19200
38400
57600
115200
230400
460800
187500
400000
9600
19200
38400
56000
57600
115200
128000
256000
(autodetect)
9600
19200
45450
93750
187500
500000
1500000
3000000
6000000
12000000
125000
250000
500000
Parity
0
0
0, 1,
2
2
0
Communication via fieldbus connection (top connector, RS-485)
Using the RS-232 interface, set the following parameters to configure the instrument for communication via the fieldbus
connection:
Fieldbus 1 Address
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…255
199
125/10
0x0FAA/4011
Fieldbus 1 Baud Rate
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned long
RW
B
0…1.0E10
201
125/9
0xFD48…0xFD49/64841…64842
Fieldbus 1 Parity
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…2
335
125/12
0x0FAC/4013
The following values are supported:
Value
Description
0
No parity
1
Odd parity
2
Even parity
Communication via standard connection (RS-232/RS-485)
Use the following parameters to configure the instrument for FLOW-BUS or Modbus communication via the side connector:
·
If the 8-pin DIN connector is set for RS-485 communication, the instrument will not respond when connected to an RS-
232 configuration. In that case, use the power-up functionality of the
mode and enable RS-232 communication.
·
After configuring the required parameters, use the same procedure to leave configuration mode and restore the original
communication settings (otherwise, configuration mode remains enabled after power down).
Fieldbus 2 Address
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…255
309
124/10
0x0F8A/3979