Ethernet indicators
RJ-45 connection sockets on instruments with a EtherCAT® or PROFINET interface have two integrated LED indicators, with
standard Ethernet functionality:
Amber: Ethernet speed
Green: Ethernet link/activity
The tables below list the different LED indications:
•
Green
Pattern
Time
Indication
off
continuous
Power-off or program not running
on
continuous
Normal operation mode
short flash
0.1 sec on,
2 sec off
Valve Safe State mode; there is no bus communication (PROFIBUS DP, DeviceNet™,
EtherCAT® and PROFINET). Valves are in safe state. This LED indication is also active
when the instrument is in ‘Initialization Mode' (parameter
Init Reset
= 73)
blink
0.2 sec on,
0.2 sec off
Special function mode; the instrument is busy performing a special function (e.g.
auto-zero or self-test)
long flash
2 sec on,
0.1 sec off
Configuration mode; the 9-pin D-sub (power) connector is set for RS232
communication (ProPar) at baud rate 38400
•
Red
Pattern
Time
Indication
off
continuous
No error
on
continuous
Critical error; the instrument needs servicing before it can be used
short flash
0.1 sec on,
2 sec off
FLOW-BUS
Node occupied: re-install instrument
PROFIBUS DP
No data exchange between master and slave (automatic recovery)
Modbus
Data is being received or transmitted
DeviceNet™
Minor communication error
EtherCAT®
Instrument is not in OP mode
PROFINET
No application relation established
blink
0.2 sec on,
0.2 sec off
FLOW-BUS
Waiting for communication
PROFIBUS DP
Not used
Modbus
Not used
DeviceNet™
No bus power
EtherCAT®
Not used
PROFINET
Not used
long flash
2 sec on,
0.1 sec off
FLOW-BUS
Not used
PROFIBUS DP
Requested parameter not available
Modbus
Not used
DeviceNet™
Serious communication error; manual intervention needed
EtherCAT®
Configuration error
PROFINET
Configuration error (e.g. a requested parameter is not available)