BRONKHORST HIGH-TECH B.V.
9.17.017
page 9
1.3 Modul
configuration
Module X
Sensor
Out
IO
Output
IO
Input
## - # # #
Module
See table Modules, System configuration
*Sensor output signal
Code
0 - 5 Vdc
A
0 - 10 Vdc
B
0 - 20 mA dc (Sinking)
C
4 - 20 mA dc (Sinking)
D
15 - 20 mA dc
E
0 - 20 mA (Sourcing)
F
4 - 20 mA (Sourcing)
G
FLOW-BUS R
Other/Specify Z
*Not applicable for CEM modules.
I/O output signal
Code
0 - 5 Vdc
A
0 - 10 Vdc
B
0 - 20 mA (Sourcing)
C
4 - 20 mA (Sourcing)
D
Other/Specify Z
I/O input signal
Code
0 - 5 Vdc
A
0 - 10 Vdc
B
0 - 20 mA (Sourcing)
C
4 - 20 mA (Sourcing)
D
Other/Specify Z
The temperature control unit offers the ability to set the desired temperature for the heater system of the
CEM. The temperature inside the CEM is monitored with a PT-100 temperature sensor, the signal of which is
being used by the temperature controller to control the adjusted temperature.
Power for the CEM heater is provided for by the R/C module.
For safety reasons the CEM heater W-300 42 Vac is powered with 42 Vac. Because of the high currents
involved, the high power CEM (1000 Watt) has a separate power supply, which is being controlled by the
temperature R/C module, intended for use with this system.
The power for the CEM heater W-300 direct 120 Vac / 230 Vac power supply operation is provided by the
R/C module and does not require a separate power supply.
For detailed information consult manual 9.17.042.
1.4 In/Output
signals
If applicable, connection of cables, carrying in- or/and output signals is further explained in the customer
system description.
Содержание E-7000 Series
Страница 2: ...BRONKHORST HIGH TECH B V ...
Страница 4: ...BRONKHORST HIGH TECH B V ...
Страница 6: ...BRONKHORST HIGH TECH B V ...
Страница 14: ...BRONKHORST HIGH TECH B V page 14 9 17 017 ...
Страница 16: ...BRONKHORST HIGH TECH B V page 16 9 17 017 2 3 Startup and menu selection ...
Страница 18: ...BRONKHORST HIGH TECH B V page 18 9 17 017 2 4 Measure menu ...
Страница 20: ...BRONKHORST HIGH TECH B V page 20 9 17 017 2 5 Operation menu ...
Страница 22: ...BRONKHORST HIGH TECH B V page 22 9 17 017 2 6 Reset menu ...
Страница 24: ...BRONKHORST HIGH TECH B V page 24 9 17 017 2 7 Alarm menu ...
Страница 26: ...BRONKHORST HIGH TECH B V page 26 9 17 017 2 8 Instrument menu ...
Страница 28: ...BRONKHORST HIGH TECH B V page 28 9 17 017 2 9 Local menu ...
Страница 30: ...BRONKHORST HIGH TECH B V page 30 9 17 017 2 10 FLOW BUS menu ...