TABLE 19
Fan assembly status LED patterns during normal operation
LED color
Description
Action required
No light
Fan assembly is not receiving power.
Verify that the fan FRU is seated correctly.
Steady green
Fan assembly is operating normally.
No action required.
Steady amber (for
more than 5
seconds)
Fan fault for one of the following reasons:
•
A fan assembly with mismatched airflow is present.
•
One or more of the fans in the fan assembly has failed.
Try one of the following:
•
Replace the mismatched fan assembly with
one that has the correct airflow direction.
•
Replace the faulty fan assembly.
NOTE
The Brocade G630 device requires minimum of two fan assemblies to be functional. Up to one fan assembly failure is
supported.
Fan assembly unit fault indicators
Use one of the following methods to determine the status of the fan assemblies:
•
Check the fan assembly status LED.
•
In Web Tools, click the Fan Status icon.
•
Enter the
fanShow
command at the prompt to display fan assembly status, as shown in the following example:
Device:admin> fanshow
Fan #1 is OK
Fan #2 is OK
Fan #3 is FAILED
Fan assembly task guide
You can perform an easy set of steps to install or replace a fan assembly or to replace two or all the three fan assemblies. By default, all
the three fan assemblies are installed in the device.
Installing an additional fan assembly (hot-install)
If your device is up and running with two fan assemblies and you want to install an additional fan assembly, complete the following steps.
1. Remove the existing filler panel.
2. Insert the new fan assembly.
3. Verify the fan assembly status LED.
Replacing a fan assembly (hot-swap)
If your device is up and running with three fan assemblies, but one of them has failed, complete the following steps.
1. Remove the old or failed fan assembly.
2. Insert the new fan assembly.
3. Verify the fan assembly status LED.
Fan assembly unit fault indicators
Brocade G630 Hardware Installation Guide
84
53-1005235-02
Содержание Brocade G630
Страница 1: ...HARDWARE INSTALLATION GUIDE Brocade G630 Hardware Installation Guide 53 1005235 02 29 December 2017 ...
Страница 10: ...Brocade G630 Hardware Installation Guide 10 53 1005235 02 ...
Страница 22: ...Brocade G630 Hardware Installation Guide 22 53 1005235 02 ...
Страница 48: ...Brocade G630 Hardware Installation Guide 48 53 1005235 02 ...
Страница 72: ...Brocade G630 Hardware Installation Guide 72 53 1005235 02 ...
Страница 88: ...Brocade G630 Hardware Installation Guide 88 53 1005235 02 ...
Страница 96: ...Brocade G630 Hardware Installation Guide 96 53 1005235 02 ...
Страница 100: ...Brocade G630 Hardware Installation Guide 100 53 1005235 02 ...