Broadcast Tools WVRC-4 Plus Скачать руководство пользователя страница 14

e-mail: 

[email protected]   

voice: 

360.854.9559   

fax: 

866.783.1742

14

WVRC-4 Plus Installation and Operation Manual

SET UP

Opening the LOGIN Web Page

1.

Connect the supplied GRAY colored XOVER cable between the PC’s

Ethernet port and the products “NET” network RJ45 jack.

2.

Connect the supplied 12 volt DC only, 2.5 amp power supply to the product’s

power jack labeled 12V DC Power.  Verify that the front panel green POWER LED
is ON and the left “LINK” LED above the “NET” Network RJ-45 connector is illu-
minated 

Ethernet (NETWORK) port LED indicator functions

Open the product’s login page by typing the following URL into the browser:
http://192.168.1.55   a username and password is required to change any parameter
and are case sensitive.

Factory “login” defaults:

username:

admin (lower case) 

password: 1234

3.

Once you are logged in, follow this manual for setup and/or operational

information. 

Содержание WVRC-4 Plus

Страница 1: ...registered trademarks of Broadcast Tools Inc Copyright 1989 2013 by Broadcast Tools Inc All rights reserved No part of this document may be reproduced or distributed without permission Visit www broa...

Страница 2: ...r Control Web Page 16 User Setup Web Page 17 I O Setup Web Page 18 Metering Setup page 19 Temperature Setup page 20 Virtual Channels Setup page 21 Status Setup page 22 Relays Setup page 23 Silence Sen...

Страница 3: ...and should never be attempted The removable euroblock screw terminals are not designed to shield humans from potentially dangerous voltages Contact with high voltages can cause serious injury or death...

Страница 4: ...es Benefits NTP time base and or battery backed real time clock calendar with accurately better than 2 0 minutes per year Four Virtual metering channels Single 1 8 T R S temperature probe port allowin...

Страница 5: ...ntrol con nections with all shields tied to the station site ground terminal The station site ground should be connected to the rear panel chassis ground Chs Gnd 6 32 chas sis screw using an 18 or 20...

Страница 6: ...t ACS LED Illuminated when a valid access code is entered HK LED Illuminated when the unit is off hook DV LED Illuminated when a valid DTMF tone is detected ALM LED Illuminated when unit is in an alar...

Страница 7: ...minal is ground When configured for WET floating this terminal is the anode via a 2 2K ohm current limiting resistor BOTTOM ST1B 4B Connector Status opto isolators This terminal is always the cathode...

Страница 8: ...plied CAT5 straight or x over cable to the desired ETH ERNET WAN LAN port Silence Sensor Inputs Connect your unbalanced monaural or stereo audio source to the terminals labeled SS LT SS GD and SS RT T...

Страница 9: ...for the desired value reading using the web interface NOTE Valid sample voltages MUST be applied to the selected metering input in order to perform calibration Status Logic Inputs Each status logic in...

Страница 10: ...SPST mechanical latching relay TEMPerature Probe Input Insert the temperature probe 25 foot cable mini 3 5mm plug in to the rear panel jack labeled TEMP 67 F to 257 F 55 C TO 125 C NOTE The tempera tu...

Страница 11: ...AUTION If you are not familiar with Ethernet enabled equipment it may be use ful to contact your IT department network administrator or network consultant for assistance Assigning an IP address alread...

Страница 12: ...1 Open the control panel by clicking on the start menu click on settings then click on Control Panel Note that the control panel shown is in Classic View If con trol panel is in Category View select t...

Страница 13: ...etwork settings write down the current settings or screen capture the page and print so that they can be restored once the unit is configured Next select the radio button labeled Use the following IP...

Страница 14: ...product s power jack labeled 12V DC Power Verify that the front panel green POWER LED is ON and the left LINK LED above the NET Network RJ 45 connector is illu minated Ethernet NETWORK port LED indica...

Страница 15: ...in Web Page The Login screen displays the Username and Password entry points as well as the date time and site ID You may view the password by checking the Show Password box After you have successfull...

Страница 16: ...n of each item on this page Queued Logs Displays the number of queued log entries scheduled to be emailed Meters Four metering analog input channels Virtual Channels Four virtual metering channels Rel...

Страница 17: ...Monitor Control allows the following access About Monitor Control Show log Help and Logout 3 Monitor Only allows the following access About Monitor only Help and Logout Only users with admin access ca...

Страница 18: ...configured to send an email to up to 8 email recip ients When the device enters or exits an alarm condition Some devices have multiple alarm conditions such as a High and a Low alarm state If the devi...

Страница 19: ...ress the Save Settings button to save the calibration only the other settings Alarms High This option enables the High Trip Point alarm Alarms Low This option enables the Low Trip Point alarm Alarms E...

Страница 20: ...GH alarm temperature set point Temp Type This option specifies what temperature scale will be used Fahrenheit or Centigrade Hysteresis Hysteresis deadband this option specifies the hysteresis used whe...

Страница 21: ...nd the Multiplier Constant together Alarms High This option enables the High Trip Point alarm Alarms Low This option enables the Low Trip Point alarm Alarms Exit This option enables the generation of...

Страница 22: ...This drop down configures the input signal to be normal ly High or normally Low This is used to determine if an input is ON or OFF NOTE When the Normal signal level is set to HIGH NO voltage is applie...

Страница 23: ...conds the relay will be activated when it is turned on This value applies to the Raise Lower con figuration as well as the Pulse function in the Toggle Pulse con figuration Raise Lower Configuration W...

Страница 24: ...he event action sequencer Action When meter status silence sensor power failure or tem perature input number is in condition delay xx seconds then engage for xx seconds EXAMPLE When meter 1 is in High...

Страница 25: ...assign up to 8 email addresses to receive silence alarm emails Log Device This enables the email snapshot logging of this input Delay Time Specifies the delay time between detected silence and alarm a...

Страница 26: ...the PF input Email Addresses This allows you to assign up to 8 email addresses to receive power failure emails Log Device This enables the email snapshot logging of this input Delay Time This option s...

Страница 27: ...m emails to whenever the input generates an alarm Log Device This enables the email snapshot logging of this input Delay Timer Specifies the delay time from when the input value is above the set alarm...

Страница 28: ...he ping address is lost Alarms Exit This option enables an alarm after exiting an Internet Down condition Email Addresses This allows you to configure up to 8 emails to be sent whenever the device exi...

Страница 29: ...ing strings to place a one second pause and a semi colon for a five second pause Pager Data This is used to identify the station or location of the device To assign the pager dial out number to an ala...

Страница 30: ...numbers in the dial list when calling out an alarm if it does not receive an acknowledgement NOTE Alarms are acknowledged by pushing the star key when an alarm is called out Ring Specifies the number...

Страница 31: ...rk left to right when configuring a schedule event To select a cell just click in the cell box and it will transform the background will be yellow and you should have either drop down boxes or checkbo...

Страница 32: ...e Relays can be pulsed or toggled from the scheduler as well Select Pulse or Toggle from the Event drop down box on the Scheduler Setup Page to configure this item Then from the Device drop down box s...

Страница 33: ...for the clause to be executed If the clause is empty then no action is taken Configuring Event Time Frequency Scheduled events can be initiated either on a repeat or one time basis One time events wil...

Страница 34: ...the checkboxes under Date for the days of the week and months of the year that you want this event to happen Time Selecting the time of day an event occurs is accomplished using the Time column Hours...

Страница 35: ...ected cell at a time To select a cell just click in the cell box and it will transform the background should be yellow To unselect a cell click in the yellow portion of the cell or onto another cell C...

Страница 36: ...tus inputs S01x to S04x are allowed Status Conditionals Meters The meter conditional takes 2 parameters the meter number and whether it is in high alarm or low alarm The following are valid meter cond...

Страница 37: ...TRUE if the reset switch is low and will return FALSE if the reset switch is high Clauses Clauses perform actions such as setting a Boolean value setting the state of a relay or executing the event of...

Страница 38: ...ration Manual SET UP Restoring to Factory Defaults NOTE The WVRC 4 Plus factory defaults may be restored by holding the front panel PGM button IN repowering the unit wait for the SS and PF LED s to fl...

Страница 39: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 39 WVRC 4 Plus Installation and Operation Manual SET UP Email Network Setup Web Page...

Страница 40: ...fault 25 SMTP Return Address Enter your return email here If an email cannot be deliv ered a message stating why will be sent to this address NOTE The user must enter the following items before an ema...

Страница 41: ...rm is queued and emailed as a digest every 24 hours The number of queued alarms is displayed on the Monitor Control page Daily Alarm Email Time The time that queued alarms are sent Queued alarms are s...

Страница 42: ...ult is 1400 bytes Time Zone Offset from UTC Sets the timezone Default 8 Set Time The hour minute second month day and year boxes can be used to set the time of the RTC The time is only updated if you...

Страница 43: ...pop up indicating the status of the email and an error condition if the email was not sent correctly If an email was not sent correctly please review your SMTP set tings and correct as necessary NOTE...

Страница 44: ...ys if the alarm is entering or exiting an alarm condition Date Displays what date the alarm was logged Time Displays what time the alarm was logged NOTE With the admin access level the user may contro...

Страница 45: ...6 783 1742 45 WVRC 4 Plus Installation and Operation Manual SET UP About Web Page The About Web Page displays the product name firmware version numbers and Broadcast Tools Web site link WEBSITE Visit...

Страница 46: ...d Lower Relays are controlled by entering the single digit channel number 1 4 of the relay you wish to control followed by for Lower or for Raise To query the new analog metering value press the chann...

Страница 47: ...disable or 9 for poll Power fail silence sensor and temperature are controlled with 99 followed by 1 for power fail 2 for silence sensor and 3 for temperature 1 to enable 0 to disable or 9 to poll So...

Страница 48: ...this should illuminate the front panel PGM LED 3 Enter the two digit address of the message you wish to program into connected the telephone A list of available messages and their addresses is provid...

Страница 49: ...t 1 21 5 Analog Input 2 22 5 Analog Input 3 23 5 Analog Input 4 24 5 Engineering Unit 1 31 2 6 Engineering Unit 2 32 2 6 Engineering Unit 3 33 2 6 Engineering Unit 4 34 2 6 Number 0 40 2 6 Number 1 41...

Страница 50: ...n Fahrenheit ON Celsius DIP 3 If OFF description messages will be played when controlled via dial up If ON raise and lower description messages will not be played DIP 4 OFF Xport control ON Control vi...

Страница 51: ...tor contact closures to ground or external logic source Power Failure input Optically isolated 6 to 12 VDC 10 ma center positive 2 1mm x 5 5mm coax type Connectors Metering analog status relays telco...

Страница 52: ...OTHER WARRANTIES OR REMEDIES TO THE MAXIMUM EXTENT PERMITTED BYAPPLICABLE LAW BROADCAST TOOLSAND ITS SUPPLIERS DISCLAIMALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPL...

Страница 53: ...EN55022 1998 IEC CSPIR22 1993 Radiated RF emissions 30MHz 1000MHz Conducted RF Emissions Telecom Lines 150KHz 30MHz FCC Part 15 Subpart B Class B IEC 1000 3 2 A14 2000 IEC 1000 3 3 1994 Electromagnet...

Страница 54: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 54 APPENDIX...

Страница 55: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 55 APPENDIX...

Страница 56: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 56 APPENDIX...

Страница 57: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 57 APPENDIX...

Отзывы: