SRC-32 Installation and Operation Manual

INSTALLATION

Output Control Commands:

*uORrrL-

Latch Output rr, (output number 01-32).  01–08 are relays,
09–32 open collectors

*uORrrF-

Unlatch Output rr, (output number 01-32).  01–08 are relays,
09–32 open collectors

*uORrrPtt-

Pulse Output rr, (output number 01-32).  Pulse Length tt: 00-
99 corresponds to 00 - 9.9 Seconds.  01–08 are relays, 09–32
open collectors

ASCII Information Retrieval Commands:

*POLL -

Respond with unit (ID) address in appropriate time slot.  If
there are multiple units on the line, each will respond with a
different delay after receipt of this command.

*uSPii -

Send status of input ii. Response is SuP,ii,x where x is 1 if the 
corresponding input is high, 0 otherwise.

*uSPA -

Send status of all inputs. Response is
SuP,A,x,x,x,x,x,x,x,x,x,x,x,x,x,x,x,x 
--> 31<CR><LF > where input 1 is first and input 32 is last.
x is 1 if the corresponding input is high, 0 otherwise.

*uSR -

Send status of all OUTPUTS.  Response is: 
SuA,x,x,x,x,x,x,x,x--->32<CR><LF>

*uU -

Send Unit Information :<name(SRC-32)><version><cr><lf>

*SA -

Send current AT command string for modem.

*ST -

Send current telephone number for modem to dial.

SRC-32 Binary Serial Burst Commands:

Dip switch 5 must be on for binary commands to be processed.  All commands start
with a 2Ah (ASCII *).  The first byte contains the board ID and the byte count
iiibbbbb Byte count is number of bytes after the byte containing the byte count
including checksum. The second byte contains an 8-bit command.  Some commands
are followed by data bytes.  Checksum is the LSByte of the sum of all bytes pre-
ceding checksum including start.  Binary commands must be received as a packet.
If 50 ms or more passes after a character is received with no new character follow-
ing, the SRC-32 will begin looking for a new string if no valid data packet has been
received.

WEBSITE:

Visit our web site for
product updates and
additional information

Содержание SRC-32

Страница 1: ...nt Revisions of this information or new editions may be issued to incorporate such changes Broadcast Tools is a registered trademarkof Broadcast Tools Inc Copyright 1989 2005 by Broadcast Tools Inc Al...

Страница 2: ...ax x 866 783 1742 SRC 32 Installation and Operation Manual Table of Contents Section Title Page Introduction 3 Safety Information 3 Who to Contact for Help 3 Product Description 4 Front Panel Descrip...

Страница 3: ...dous condition WHO TO CONTACT FOR HELP If you have any questions regarding your product or you need assistance please con tact your distributor from whom you purchased this equipment If you would like...

Страница 4: ...baud rate can be set to 2400 9600 19200 or 38400 other baud rates may be supplied This can be done using either the ASCII or binary command formats listed below Inputs can be simple contact closures...

Страница 5: ...switch or recycle the power DIP 1 2 The board address is set using Dipswitch numbers 1 and 2 in normal hex format 1 2 0 0 0 master No polling is required for status 0 1 1 1 0 2 1 1 3 DIP 3 4 Set baud...

Страница 6: ...ase S followed by the unit address and then the specific response If acknowledgments are enabled successful com mands are responded to with RRR while errors get an EEE response The syntax of each comm...

Страница 7: ...31 CR LF where input 1 is first and input 32 is last x is 1 if the corresponding input is high 0 otherwise uSR Send status of all OUTPUTS Response is SuA x x x x x x x x 32 CR LF uU Send Unit Informa...

Страница 8: ...receive an update from its corresponding paired unit for a period of 20 seconds its LCD display will begin to flash COM FAILURE As soon as communications is restored the COM FAILURE message will clea...

Страница 9: ...or output n 00h 1Fh if input n is low n 20h 3Fh if input n is high n 40h 5Fh if output n is low and n 60 7F if output n is high n cccnnnnn where ccc 000 input low 001 input hi 010 output lo 011 outpu...

Страница 10: ...BAR 4 is also suggested for the power transformer The purchase of an inexpensive uninterruptible power supply UPS will provide back up in case of power outages Check out our web site for lightning pro...

Страница 11: ...16B In 17A In 17B In 18A In 18B Top 4 In 19A In 19B In 20A In 20B In 21A In 21B Bottom 4 In 22A In 22B In 23A In 23B In 24A In 24B Top 5 In 25A In 25B In 26A In 26B In 27A In 27B Bottom 5 In 28A In 2...

Страница 12: ...Other baud rates may be requested RS 422 485 Serial Port 2400 9600 19200 38400 baud 8 data bits no parity 1 stop bit Other baud rates may be requested Ethernet Option Optional External Ethernet Devic...

Страница 13: ...I IE ES S O OR R R RE EM ME ED DI IE ES S TO THE MAXIMUM EXTENT PERMITTED BYAPPLICABLE LAW BROADCAST TOOLSAND ITS SUPPLIERS DISCLAIMALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIM...

Отзывы: