7 181 465 347 (01.07)
Rectifying faults
27
5.
B
Power OFF the appliance.
B
Remove fuse SI 3 from appliance
PCB control board and test for
continuity.
R =
∞
?
yes:
B
Change the fuse.
B
Turn ON the appliance.
B
Press
, does appliance restart???
E9?
↓
6.
no:
B
Remount the fuse.
B
Turn ON the appliance.
6.
The PCB control board is damaged.
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change PCB control board.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.
E 9
and
flashing.
Safety temperature limiter has tripped.
Check
Action