Full-Coverage Drum Heater
(FGDH & FGPDH Series)
INSTALLATION / OPERATION INSTRUCTIONS
STEP 1
Remove heater from box. Make visual inspection of heater. Do not use if torn or damaged.
STEP 2
Drum heater should be placed on a clean, dry surface. Open hook and loop closure on heater
and position around drum with adjustable thermo-switch in the upper third of the heater. Heater
should be positioned on drum such that it is covering the drum from the floor to the top of the
drum. Fasten hook and loop closure so heater is tight against the drum with no sagging or
bundling. Cover top of drum with optional insulation cover (sold separately, PN: FGDC55). For
larger diameter drums, up to 24.2” (615mm), optional Insulated expansion strips are available
(sold separately, PN: FGDHSTRIP).
STEP 3 (see page 3 for electrical compliance)
For 120VAC model, plug standard 3-prong plug to appropriate electrical power supply. For
230VAC model, terminate power cord to appropriate electrical power supply. The power cable
consists of three color-coded conductors, black, white, and green. The black wire should be
connected to Line 1. The white wire should be connected to Line 2. The green wire should be
connected to earth ground. The power connections must be adequately rated to electrically
support the voltage and amperage of the heater. The identification label located on the power
cord displays voltage and amperage requirements. Follow all local electrical codes for proper
electrical connections.
STEP 4
Adjust controller to desired setting (See page 6 for programming instructions). Drum
heaters designed for metal drums (FGDH series) can be adjusted 50-450ºF (10-232ºC). Drum
heaters designed for plastic drums (FGPDH series) can be adjusted 50-160ºF (10-71ºC).
VOLTAGE:
120VAC; 230VAC;
Read and understand this entire manual
before operating this electric heater.
WARNING
© BriskHeat
®
Corporation. All rights reserved.
6
Full-Coverage Drum Heater
(FGDH & FGPDH Series)
PROGRAMMING DIGITAL TEMPERATURE CONTROLLER
Parameter Programming
Set Point (SP) is the only parameter the user can access without code protection.
Press SET. SP text will appear on the display.
Press SET again. The real value is shown on the display.
The value can be modified with the UP and DOWN arrows.
Press SET to enter any new values.
Press SET and DOWN at the same time to quit programming or wait one minute and the
display will automatically exit programming mode.
Buzzer
In the event of alarm or error condition, the internal buzzer is activated. To silence the buzzer,
press and hold the SET and Down keys for 2 seconds.
LED Indications
OUT This indicates that the heater is on.
Display Messages
In normal operation, the sensor temperature will be shown on the display. In case of alarm or
error, the following messages will be shown:
Er = Memory Error
-- = Short-Circuit Probe Error (Disconnects output).
oo = Open Probe Error (Disconnects output).
Controller Operation
Once the controller reaches set point, the heater will turn off and will not turn on again until the
temperature falls 5°F below the set point.
The
controller
will alarm if the temperature at the sensor exceeds 15°F of the setpoint.