Section 2 – Operation 

 

The purpose of the Evap is to humidify air passing through wetted media in an energy-efficient, silent and safe 
way. The adiabatic humidification process is carried out in the humidifier unit and increases the humidity in the 
air supply to the room.  

The Evap humidifier must be installed in the air duct to the building. 

 

2.1 

Principle of operation

  

The Evap is installed in the air duct to the building. The humidifier operates completely independently and 
switches on when the (absolute) outside air humidity becomes too low. 

The switching is linked to the prevailing outside temperature, using an average meteorological year as the 
reference year. This value is controlled by the T3 temperature sensor, which must be installed in the outdoor air 
duct. The default temperature setting for triggering the Evap humidification unit is 12°C. 

The Evap then humidifies the supplied air until that air reaches a maximum relative humidity of 78%.  

The integrated PTC preheater is only operational when the air temperature is lower than 17°C after 
humidification. This limits the energy usage of the PTC preheater. 

The maximum moisture supply capacity is 4 kg/h (approx. 4 liters per hour) and is highly dependent on the air 
temperature and air flow across the Evap humidifier. The maximum air flow capacity of the Evap is 600 m

3

/h 

 

2.2 

Safety

  

The water is legionella-safe because of the built-in, patented, legionella-free LegioSafe water distributor. The 
supply water first passes through the LegioSafe before it moistens the matrix. As a result there is no risk for the 
inhabitants of houses or buildings. Only fresh water is used. There is no recycling of water. The matrix is 
completely dry if there is no demand for humidification. 

The SHC80 duct sensor also supplied measures the relative humidity and temperature in the duct after the 
Evap. This position guarantees the maximum operation and condensate-free ducts under the normal conditions 
of use of our design. 

The Evap air humidifier has several safety features: 

1.  A mechanical Klixon temperature switch that switches off the PTC preheater if the set temperature is 

exceeded.  
 

2.  An additional temperature sensor in the humidifier unit that also switches off the PTC preheater if the 

set temperature is exceeded.  
 

3.  Legionella shutdown protection. If the air humidifier unit is switched off for 72 hours, the water valve will 

automatically open and flush the pipes and the Evap cassette for 30 seconds to prevent legionella from 
forming.  

 

 

Содержание evap WTW

Страница 1: ...INSTALLATION INSTRUCTIONS English WWW BRINKAIRFORLIFE NL 614796 B ...

Страница 2: ... 12 years and over persons with reduced mental capacity physical limitations or lack or experience and knowledge if they are supervised or have been instructed in the use the product safely and are aware of the possible hazards Children should not play with the product Cleaning and maintenance by the user may not be carried out by children without supervision ...

Страница 3: ...y 2 3 Use 3 3 1 Description of the components 3 3 2 Description of the components 3 4 Technical specifications 4 4 1 Specifications 4 4 2 Illustrations 4 5 Setup 5 5 1 Order of operation 5 6 Faults 6 7 Maintenance 7 7 1 Procedure for replacing Evap cassette 7 8 Wiring diagram 8 9 Service 9 9 1 Service products 9 10 Declaration of Conformity 10 ...

Страница 4: ...x cassette with LegioSafe water filter One 1 PTC electric heating element One 1 cord with connection adapter for SHC80 sensor L 1m One 1 water supply hose L 1m Ø 4mm adapter outside One 1 cord with coupling for cord with mains plug L 1m One 1 cord fitted with a temperature sensor T3 L 2m Supplied separately are One 1 combined humidity temperature sensor SHC80 One 1 cord with coupling for cord with...

Страница 5: ...upply capacity is 4 kg h approx 4 liters per hour and is highly dependent on the air temperature and air flow across the Evap humidifier The maximum air flow capacity of the Evap is 600 m 3 h 2 2 Safety The water is legionella safe because of the built in patented legionella free LegioSafe water distributor The supply water first passes through the LegioSafe before it moistens the matrix As a resu...

Страница 6: ...PTC preheater is only operational when the air infeed temperature falls below the set minimum temperature Humidity and temperature sensor SHC80 The SHC80 duct sensor also supplied measures the relative humidity and temperature in the duct after the Evap This position guarantees the maximum operation and condensate free ducts under the normal conditions of use of our design Temperature sensor T3 Th...

Страница 7: ...capacities 230V 50HZ Maximum power consumption 800 W h Average annual consumption 160 kWh Maximum water consumption 5 litre per hour Water supply connection internal thread with connection to 4mm Water drainage connection 15 mm hose connector Maximum air volume 600 m3 u Duct connection Standard d 200 mm 4 2 Illustrations Top Front Side Back Bottom ...

Страница 8: ... length of 50 centimetres Push this hose carefully into the white coupling on the black drain Secure the connection by tightening the ring on the compression fitting by hand N B The drain hose must be connected to the sewer depressurized and with sufficient fall NO water may remain in the hose 9 Fit the temperature sensor T3 in the air supply duct of the outside air duct 10 Fit the humidity and te...

Страница 9: ...nd replace valve If valve is working and matrix material does not get wet after switching then the LegioSafe filter is blocked and must be replaced Order product code 351025 from your dealer Alarm LED continuously on Heating faulty Check air temperature after the humidifier this must be 17ºC if not air heater is faulty Call installer for replacement Alarm LED continuously on T3 sensor outside air ...

Страница 10: ... is accessible Take into account any leakage water from the side of the unit 7 Disconnect the Evap cassette from the water supply by pushing in the ring of the knee joint on side of the housing and sliding the whole knee off of the black hose In this way the cassette is disconnected and can be removed 8 Pull slide the cassette from the Evap humidifier using the supplied tool large plug 9 Clean the...

Страница 11: ...Evap 8 Section 8 Wiring diagram ...

Страница 12: ... 9 Service 9 1 Service products Product description Product code Evap cassette LegioSafe 351025 Evap cassette 351026 Evap air heater 351027 Evap water valve 351028 Evap drain 351029 Evap knee 351030 Evap PCB 1 351031 ...

Страница 13: ...ts of the Evap are EN 60334 2 98 2003 A1 2005 A2 20089 A11 2013 EN 60335 1 2012 EN62233 2008 EN 61000 3 2 2014 EN 61000 3 3 2013 EN 55014 2 1997 A1 2009 A2 2011 EN 55014 2 1997 A1 2001 A2 2008 Fire safety of Matrix material used Fire test of evaporative media EN ISO1182 EN13823 declared Euro Class A2 S2 d0 Hygiene assessment The Evap is fitted with a registered LegioSafe water filter this filter r...

Страница 14: ... 11 NL 7950 AA Staphorst Wethouder Wassebaliestraat 8 7951SN Staphorst T 31 0 522 46 99 44 F 31 0 522 46 94 00 info brinkclimatesystems nl www brinkclimatesystems nl BRINK CLIMATE SYSTEMS B V 614796 B 09 2017 ...

Отзывы: