Section 5 – Installation
5.1
Order of operation
1. Locate the Evap air humidifier in the air supply duct as close as possible to the HRV unit. The minimum
distance after a bend is 150mm.
2. It is important during installation that sufficient clearance is available so that the Evap humidifier can be
rotated at all times without the need for dismantling when replacing the Evap cassette.
N.B.! The Evap humidifier must be installed perfectly level!
3. Keep at least 100 millimetres clear space at the bottom.
4. Install the Evap humidifier horizontally between the ducts or air hoses.
The Evap humidifier must hang level to guarantee good water drainage.
5. Use brackets with M8 thread connection to hang the unit.
6. Connect the black 4mm hose with the ¾” adapter to the mains water supply, for this use a ¾” washing
machine tap with check valve.
7. Make sure that the water pressure is between 1.5 bar and max. 3.5 bar.
8. The Evap humidifier is supplied with a 15 millimetre drain hose with a length of 50 centimetres.
Push this hose carefully into the white coupling on the black drain Secure the connection by tightening
the ring on the compression fitting by hand!
N.B.!
The drain hose must be connected to the sewer depressurized and
with sufficient fall! NO water may remain in the hose!
9. Fit the temperature sensor (T3) in the air supply duct of the outside air duct.
10. Fit the humidity and temperature sensor (SHC80) as close as possible after the Evap in the air duct to
the dwelling, maximum distance 100 centimetres.
N.B.!
The sensor(s) may not be damaged or get wet!
11. Insert the plug into the socket. Check the voltage, green power LED comes on.
12. Open the water supply tap and check for leaks in the water supply and the drain.
13. The Evap humidifier automatically activates a pre-programmed test program. During the test
cycle, the service light will flash at intervals of 5 seconds.
14. After the test cycle, check the entire system for leaks (water supply and drainage).
15. After 1 hour, check the entire system again for leaks (water supply and drainage).
16. The Evap is now ready for operation.
17.
Optional
Open the controller packaging and follow the instructions in the manual.