background image

4

1. Unpack the fixtures. The louver frames and lamps may be packed with the fixtures or separately. 

       To prevent damage, install the fixtures before installing lamps and louver frames.

2. Prepare the line-voltage wiring to the fixtures. Depending on building conditions, it may be necessary

       to install the power and control wiring before the fixture is placed in the ceiling. Ensure that the supply 

       voltage matches that required by the ballasts. To install the power feed, remove the knockouts as needed

       and install the correct type of power cabling and strain relief (not provided). Connect the wires from the 

       feed using wire nuts, observing the wire color-coding, and re-install the knockout plate. 

Brightline

       fixtures intended for the North American market use Black/White/Green wires respectively for 

       Line/Neutral/Earth Ground; fixtures shipped to other locations use Brown/Blue/Green-Yellow for 

       Line/Neutral/Earth Ground. You may want to install sufficient slack in the power cable so that, if

       necessary, the fixture can be moved to an adjacent ceiling opening.

 
3. These fixtures are not Insulated Ceiling (IC) rated. Maintain the proper distance from insulation 

       (3 in [76 mm] in the US and Canada).

4. If the fixture requires low-voltage control, the proper wiring must be run to each fixture.  Connect the 

      control wires inside the fixture, observing the proper color-coding. Install the control wiring 

      above the ceiling. (See the 

Control Wiring

 section below.)

5. Fixtures can be mounted in two ways: either flush-mount in a “hard” ceiling, such as plaster or drywall;

      or mounted in a T-Grid acoustical-tile ceiling.

Installation

Figure 3

 

Figure 1

 

Figure 2

  

•  

Hard Ceilings:

 Verify that the locations in which you 

   intend to mount the fixtures are free of above-ceiling

   obstructions such as ceiling joists, air conditioning

   ducts, etc. For ease of installation, a minimum of 

   8 in [203 mm] of clear height above the ceiling is

   recommended. In accordance with drawings provided 

   by 

Brightline

 or the local architect or engineer, prepare 

   the ceiling by cutting openings that are 24.56- x 24.56-in 

   [624- x 624-mm] in size. Depending on ceiling construction,

   it may be necessary to install a frame in the opening to 

   accommodate the weight of the fixture. Install the power and 

   control wiring as described above. With the mounting clips 

   in their recessed position (folded back next to the fixture, 

   see figure 1), lift the fixture into its opening. 

   Using a screwdriver, turn the screws on the bottom of the mounting clips until the clips turn approximately 

   90° and rest on the frame or ceiling structure. (Figure 2) Adjust the clips so the bottom of the fixture is 

   flush with the exposed side of the ceiling. (Figure 3)

    

Содержание Stealth-T

Страница 1: ...peration and Installation Guide Evolutionary Lighting Systems 580 Mayer Street Building 7 Bridgeville PA 15017 phone 412 206 0106 fax 412 206 0146 www brightlines com 2011 Brightline L P All rights reserved Patent pending TM REV 11 17 2011 1 ...

Страница 2: ...ure that is energized or to work with your hands near an exposed socket that is energized A qualified technician should perform service on fixtures Do not remove the ballast cover until the unit has been de energized In case of lamp failure 1 Turn the fixture power off 2 Wait 30 seconds for the ballast to reset 3 Install the new lamp s 4 Turn the fixture back on Stealth T Fixtures Two lamp glare f...

Страница 3: ... BI option Louvers are also available for downward throw operation DN option Reflector Die cut code gauge cold rolled steel with 4 pull down spring latches Door frame may be removed from fixture without tools Luminaire Ballast High frequency electronic ballast with a power factor 97 THD 10 Class A sound rating Luminaire operates at 230VAC 50 Hz 51A Dimensions The overall dimension of the fixture b...

Страница 4: ...l the proper wiring must be run to each fixture Connect the control wires inside the fixture observing the proper color coding Install the control wiring above the ceiling See the Control Wiring section below 5 Fixtures can be mounted in two ways either flush mount in a hard ceiling such as plaster or drywall or mounted in a T Grid acoustical tile ceiling Installation Figure 3 Figure 1 Figure 2 Ha...

Страница 5: ...ucture in compliance with local codes Figures 4 and 5 Brightline recommends not relying on the t track alone to hold the weight of the fixtures 5 continued T Grid Ceilings Prepare the T Grid to receive the fixtures Fixtures are available for either 2 x 2 ft or 600 x 600 mm grid spacings Depending on the ceiling layout it may be necessary to add additional track sections and or prepare different si...

Страница 6: ...6 Non Dim Switched Riser Diagram L L L L L L L Line Voltage The fixture is wired to a source of AC power Line Neutral Ground only ...

Страница 7: ...nterior face and a power inlet for cord up to 15mm To wire the fixture 1 Untighten self tapping screw 2 Remove bracket from fixture enough to access terminal block 3 Feed leads through the grommetted hole 4 Wire according to label adjacent to terminal block Tighten contact screws 5 Re insert bracket into fixture and close with self tapping screw ...

Страница 8: ...Y CONDUCTORS DO NOT INSTALL INSULATION WITHIN 76MM 3 IN OF ANY PART OF THE LUMINAIRE DRY LOCATIONS ONLY IP RATING IP20 TURN OFF FIXTURE BEFORE RELAMPING CAUTION RISK OF FIRE USE WITH MAXIMUM 55 WATT LAMP BIAX 2G11 SOCKET AMBIENT TEMPERATURE Ta 25 C INPUT VOLTAGE GROUND EARTHLING INTERIOR FACE OF BRACKET ...

Страница 9: ...9 Page left blank intentionally ...

Страница 10: ...t of your order Two receptacles are provided to allow the control wiring to be daisy chained As each fixture is assigned an individual address fixtures on a DALI control line may be dimmed to differing intensities DALI control wiring is topology and polarity independant DALI control cables may be daisy chainned Keep the total wire run as short as possible See the literature that is provided with your...

Страница 11: ...low the control wiring to be daisy chained As each fixture is assigned an individual address fixtures on a DALI control line may be dimmed to differing intensities DALI control wiring is topology and polarity independent DALI control cables may be daisy chained Keep the total wire run as short as possible See the literature that is provided with your DALI controller or contact Brightline for details ...

Страница 12: ... to keep the lamps and lenses clean Use a dry non abrasive cloth to remove dust Avoid the use of materials that might scratch the lenses n o i t u l o S e s u a C e l b i s s o P m e l b o r P Fixture does not light 1 Missing or improper incoming power 2 Defective lamp s 1 Verify that the fixture is recieving proper voltage 2 Troubleshoot by replacing with known good lamps If necessary replace wit...

Страница 13: ...okups or by unauthorized repairs Failure to notify Brightline of unsatisfactory operation or any improper or unauthorized installation maintenance use repairs or adjustments shall terminate the warranty and Brightline shall have no further responsibility under the warranty Brightline shall not be liable for special or consequential damages in any claim action suit or proceeding arising under this ...

Страница 14: ...14 Notes ...

Отзывы: