Briggs & Stratton Standby Generator Systems Скачать руководство пользователя страница 31

Not for 

Reproduction

 31

Final Installation Considerations

Engine Oil

NOTICE

 Any attempt to crank or start the engine before it 

has been properly serviced with the recommended oil will 

result in equipment failure.
•  Refer to Maintenance in the operator’s manual for oil  

fill information.

•  Damage to equipment resulting from failure to follow this 

instruction will void engine and generator warranty.

The engine is shipped from the factory pre-run and filled 

with synthetic oil (API SJ/CF 5W-30). This allows for system 

operation in a wide range of temperature and climate 

conditions. Before starting the engine, check oil level and 

ensure that engine is serviced as described in Maintenance 

of the Operator’s Manual.
The use of synthetic oil 

does not

 alter the required oil 

change intervals described in the Operator’s Manual.

Coolant System

This engine is shipped from the factory filled with a 50/50 

mix of automotive (Ethylene glycol) anti-freeze and water. 

This will provide optimum year round protection against 

freezing, boiling and corrosion.

Battery

The installer must supply and install a valve-regulated 

rechargeable starting battery. The starting battery MUST 

conform to the specifications shown in this chart.

Battery Specifications

BCI Model 26R

Volts

12 Volt DC

Amps (MIN)

525 CCA (cold cranking amps)

Type

VRLA (Valve Regulated Lead Acid)

Terminal Hardware

Post

Dimensions (MAX):
     Width

7.5 inches (191 mm)

     Length

11.25 inches (286 mm)

     Height

10.0 inches (254 mm)

Install the battery

 as described in 

Servicing the Battery

 in 

the 

Maintenance

 section of the operator’s manual. Always 

make sure the 

NEGATIVE

 cable is connected last.

 

WARNING

 Battery posts, terminals and related 

accessories contain lead and lead compounds,  chemicals 

known to the State of California to cause cancer and 

reproductive harm. Wash hands after handling.

 

WARNING

 Storage batteries give off explosive 

hydrogen gas during recharging. 

Slightest spark will ignite hydrogen 

and cause explosion, resulting 

in death, serious injury and/or 

property damage. 

Battery electrolyte fluid contains acid and is 

extremely caustic. 

Contact with battery contents could cause severe 

chemical burns. 

A battery presents a risk of electrical shock and high short 

circuit current.

•  DO NOT dispose of battery in a fire. Recycle battery.
•  DO NOT allow any open flame, spark, heat, or lit cigarette 

during and for several minutes after charging a battery.

•  DO NOT open or mutilate the battery.
•  Wear protective goggles, rubber apron, rubber boots and 

rubber gloves.

•  Remove watches, rings, or other metal objects.
•  Use tools having insulated handles.

Содержание Standby Generator Systems

Страница 1: ...ual Liquid Cooled Generator System This generator is rated in accordance with UL Underwriters Laboratories 2200 stationary engine generator assemblies and CSA Canadian Standards Association standard C...

Страница 2: ...ce This generator system requires professional installation before use The installer should follow the instructions completely Where to Find Us You never have to look far to find support and service f...

Страница 3: ...andby Generator to REDUCE THE RISK OF FIRE 14 Other General Location Guidelines 16 Concrete Slab 16 Access Ports 18 The Gaseous Fuel System 20 Fuel Consumption 21 Fuel Pressure 21 Power Loss 21 Fuel P...

Страница 4: ...ing Parts Electrical Shock Explosion WARNING The engine exhaust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING C...

Страница 5: ...ce the fuel system lines must be properly purged and leak tested After the generator is installed you should inspect the fuel system periodically NO leakage is permitted DO NOT operate engine if smell...

Страница 6: ...running at governed speed DO NOT modify generator in any way NOTICE Improper treatment of generator could damage it and shorten its life Use generator only for intended uses If you have questions abo...

Страница 7: ...ons must strictly comply with all applicable codes industry standards and regulations Owner Responsibilities Read and follow the instructions given in the operator s manual Follow a regular schedule i...

Страница 8: ...ge If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claim procedures Missing or damaged parts are not warranted Shipment Contents The standby genera...

Страница 9: ...control panel to the transfer switch is installed in a separate conduit from high voltage wires unless the insulation rating on all wiring is rated for 600V See Transfer Switch Communication Dipswitch...

Страница 10: ...N o t f o r R e p r o d u c t i o n 10 BRIGGSandSTRATTON COM Page Intentionally Left Blank...

Страница 11: ...ld result in death serious injury headache fatigue dizziness vomiting confusion seizures nausea or fainting Operate this product ONLY outdoors in an area that will not accumulate deadly exhaust gas Ke...

Страница 12: ...to a potentially occupied building or structure By law it is required in many states to have a Carbon Monoxide CO detector in operating condition in homes and other structures occupied by people Carbo...

Страница 13: ...oors ventilation intakes soffit vents crawl spaces open garage doors or other openings where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building or structure...

Страница 14: ...ad clearance from any structure overhang or trees DO NOT place weatherproof enclosure under a deck or other type of structure that may confine airflow USE ONLY flexible fuel line provided Connect prov...

Страница 15: ...tallations with Structure Without a Fire Rating NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend Standby weatherproof enclosure must ha...

Страница 16: ...enings If prevailing winds will cause blowing or drifting you may need to construct a windbreak to protect the unit Concrete Slab At the appropriate location construct a concrete slab 28 day compressi...

Страница 17: ...Use a spreader bar to ensure that the chains straps or cables DO NOT touch the generator s roof Hooks may be used in the lifting holes in place of the pipe in accordance with OSHA or local lifting re...

Страница 18: ...fuel selector and engine starter E Control Panel Cover field wiring and control wires Each generator is shipped with a set of identical keys These keys fit in the lock on the front and rear removable...

Страница 19: ...2 Secure the panel with two bolts To remove front panel 1 Remove the two bolts H that secure the panel to the unit 2 Lift panel to remove from unit To secure front panel 1 Place panel in unit 2 Secur...

Страница 20: ...s known to occur piping should be protected against freezing The termination of hard piping should include a sediment trap E where condensate is not likely to freeze A minimum of one accessible approv...

Страница 21: ...ing Maximum pressure with engine OFF at No Load is 13 85 in W C Power Loss Air density is less at high altitudes resulting in less available engine power Specifically engine power will decrease 3 for...

Страница 22: ...the open position 3 Press the control board OFF button 4 Remove 15 Amp fuse from control panel 5 Remove the rear panel 6 Locate the fuel selector collar on bottom of fuel regulator A 7 Carefully push...

Страница 23: ...and Line 2 Power connection to transfer switch G Neutral and Ground Connection Connect to transfer switch neutral and ground System Connectors Compare this illustration with your generator to familia...

Страница 24: ...wn schematically and as wiring diagram A complete schematic and wiring diagram can be found later in this manual Neutral is not bonded to ground at generator NOTICE Prior to making connections verify...

Страница 25: ...d terminals installed per terminal supplier s instructions and comply with national electrical codes and local requirements Utility Circuit Connection 240V Utility leads must be routed in conduit The...

Страница 26: ...ity outage OFF Turns off running generator prevents unit from starting and resets any detected faults OFF must be pressed and held for more than 5 seconds in order to reset service codes MANUAL Used t...

Страница 27: ...THE GENERATOR OFF TURNS OFF RUNNING GENERATOR PREVENTS UNIT FROM STARTING AND RESETS ANY DETECTED FAULTS AUTOMATIC MODE NORMAL OPERATING POSITION PRESS AND HOLD BUTTON TO PLACE UNIT INTO AUTOMATIC MO...

Страница 28: ...ate or change these settings follow the steps below IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS THE CONTROL PANEL WILL AUTOMATICALLY EXIT THE PROGRAM MODE SET DATE SET DATE If set to O...

Страница 29: ...button The following will scroll across the digital display and then move to the next item Run time Date Time Exercise Cycle date and start time The user can press the LEFT ARROW or RIGHT ARROW at an...

Страница 30: ...d region where the generator is being operated Confirm all settings before operating the generator for the first time For advanced menu items press and hold the left arrow right arrow and escape key f...

Страница 31: ...e specifications shown in this chart Battery Specifications BCI Model 26R Volts 12 Volt DC Amps MIN 525 CCA cold cranking amps Type VRLA Valve Regulated Lead Acid Terminal Hardware Post Dimensions MAX...

Страница 32: ...rged This may cause the engine to run roughly for a few minutes 6 Listen for unusual noises vibration or other indications of abnormal operation Check for oil leaks while engine runs 7 Let engine warm...

Страница 33: ...generator will only enter the exercise cycle if the unit is in the AUTO mode and this exact procedure is followed To set the exercise timer NOTICE The generator is set with a default exercise cycle se...

Страница 34: ...N o t f o r R e p r o d u c t i o n 34 BRIGGSandSTRATTON COM Schematic Diagram...

Страница 35: ...N o t f o r R e p r o d u c t i o n 35...

Страница 36: ...N o t f o r R e p r o d u c t i o n 36 BRIGGSandSTRATTON COM Wiring Diagram...

Страница 37: ...N o t f o r R e p r o d u c t i o n 37...

Страница 38: ...N o t f o r R e p r o d u c t i o n 38 BRIGGSandSTRATTON COM NOTES...

Страница 39: ...N o t f o r R e p r o d u c t i o n 39 NOTES...

Страница 40: ...N o t f o r R e p r o d u c t i o n Page Intentionally left Blank...

Отзывы: