A

 -  

Two Pin Terminal Block —

 Used to connect utility 

240 VAC from fuse block in ATS to the control board. 

Connect only one wire per terminal.

B

 - 

 Fault Contacts —

 Use NO, COM and NC to hook up a 

siren, light, etc. to alert you in case of a fault. Contacts 

reverse state (NO goes to NC and vice versa) upon a 

fault condition.

C

 - 

 Transfer Switch Communication (TxRx and TxRx 

GND) —

 Connect to transfer switch control board for 

communication interface using 18 AWG twisted pair 

wire.

D -  +LED and GND Connection —

 Not required for optional 

wireless monitor #6229. Available for optional 

hardwired remote system status panel accessory, 

#6154.

E

 -

  Eight Pin Terminal Block —

 Used to connect signal 

wires to the control board. Connect only one wire per 

terminal.

F

 -

  Power Connection (Line 1 and Line 2) —

 Power 

connection to transfer switch.

G

 -

  Neutral and Ground Connection —

 Connect to transfer 

switch neutral and ground

System Connectors

Compare this illustration with your generator to familiarize yourself with the location of these connections. 

LINE 1

LINE 2

GROUND

NEUTRAL

]

]

E

F

G

B

C

D

A

 

•  For power output connection (Line 1, Line 2, Neutral, and Ground), refer to the following table:

Power output connections 

minimum 300V, 75°C

25 kW

1/0 Copper
3/0 Aluminum

 

•  Reference NEC 2011 table 310.15 (B) (16)

 

•  Use National Electric Code for correction factors and wire size calculations.

 

•  For utility circuit connection (Utility A and Utility B) use #14 AWG minimum 300 volt wire.

 

•  For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt wire.

 

•  When connecting to the terminal block, fasten only one wire to each connector screw.

 

•  Torque terminal block screws to 4.4 in-lb (0.49 Newton meter).

 

•  Torque circuit breaker connections to 45 in-lb (5 Newton meter).

Содержание Standby Generator Systems

Страница 1: ...ual Liquid Cooled Generator System This generator is rated in accordance with UL Underwriters Laboratories 2200 stationary engine generator assemblies and CSA Canadian Standards Association standard C...

Страница 2: ...ce This generator system requires professional installation before use The installer should follow the instructions completely Where to Find Us You never have to look far to find support and service f...

Страница 3: ...andby Generator to REDUCE THE RISK OF FIRE 14 Other General Location Guidelines 16 Concrete Slab 16 Access Ports 18 The Gaseous Fuel System 20 Fuel Consumption 21 Fuel Pressure 21 Power Loss 21 Fuel P...

Страница 4: ...ing Parts Electrical Shock Explosion WARNING The engine exhaust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING C...

Страница 5: ...ce the fuel system lines must be properly purged and leak tested After the generator is installed you should inspect the fuel system periodically NO leakage is permitted DO NOT operate engine if smell...

Страница 6: ...running at governed speed DO NOT modify generator in any way NOTICE Improper treatment of generator could damage it and shorten its life Use generator only for intended uses If you have questions abo...

Страница 7: ...ons must strictly comply with all applicable codes industry standards and regulations Owner Responsibilities Read and follow the instructions given in the operator s manual Follow a regular schedule i...

Страница 8: ...ge If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claim procedures Missing or damaged parts are not warranted Shipment Contents The standby genera...

Страница 9: ...control panel to the transfer switch is installed in a separate conduit from high voltage wires unless the insulation rating on all wiring is rated for 600V See Transfer Switch Communication Dipswitch...

Страница 10: ...N o t f o r R e p r o d u c t i o n 10 BRIGGSandSTRATTON COM Page Intentionally Left Blank...

Страница 11: ...ld result in death serious injury headache fatigue dizziness vomiting confusion seizures nausea or fainting Operate this product ONLY outdoors in an area that will not accumulate deadly exhaust gas Ke...

Страница 12: ...to a potentially occupied building or structure By law it is required in many states to have a Carbon Monoxide CO detector in operating condition in homes and other structures occupied by people Carbo...

Страница 13: ...oors ventilation intakes soffit vents crawl spaces open garage doors or other openings where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building or structure...

Страница 14: ...ad clearance from any structure overhang or trees DO NOT place weatherproof enclosure under a deck or other type of structure that may confine airflow USE ONLY flexible fuel line provided Connect prov...

Страница 15: ...tallations with Structure Without a Fire Rating NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend Standby weatherproof enclosure must ha...

Страница 16: ...enings If prevailing winds will cause blowing or drifting you may need to construct a windbreak to protect the unit Concrete Slab At the appropriate location construct a concrete slab 28 day compressi...

Страница 17: ...Use a spreader bar to ensure that the chains straps or cables DO NOT touch the generator s roof Hooks may be used in the lifting holes in place of the pipe in accordance with OSHA or local lifting re...

Страница 18: ...fuel selector and engine starter E Control Panel Cover field wiring and control wires Each generator is shipped with a set of identical keys These keys fit in the lock on the front and rear removable...

Страница 19: ...2 Secure the panel with two bolts To remove front panel 1 Remove the two bolts H that secure the panel to the unit 2 Lift panel to remove from unit To secure front panel 1 Place panel in unit 2 Secur...

Страница 20: ...s known to occur piping should be protected against freezing The termination of hard piping should include a sediment trap E where condensate is not likely to freeze A minimum of one accessible approv...

Страница 21: ...ing Maximum pressure with engine OFF at No Load is 13 85 in W C Power Loss Air density is less at high altitudes resulting in less available engine power Specifically engine power will decrease 3 for...

Страница 22: ...the open position 3 Press the control board OFF button 4 Remove 15 Amp fuse from control panel 5 Remove the rear panel 6 Locate the fuel selector collar on bottom of fuel regulator A 7 Carefully push...

Страница 23: ...and Line 2 Power connection to transfer switch G Neutral and Ground Connection Connect to transfer switch neutral and ground System Connectors Compare this illustration with your generator to familia...

Страница 24: ...wn schematically and as wiring diagram A complete schematic and wiring diagram can be found later in this manual Neutral is not bonded to ground at generator NOTICE Prior to making connections verify...

Страница 25: ...d terminals installed per terminal supplier s instructions and comply with national electrical codes and local requirements Utility Circuit Connection 240V Utility leads must be routed in conduit The...

Страница 26: ...ity outage OFF Turns off running generator prevents unit from starting and resets any detected faults OFF must be pressed and held for more than 5 seconds in order to reset service codes MANUAL Used t...

Страница 27: ...THE GENERATOR OFF TURNS OFF RUNNING GENERATOR PREVENTS UNIT FROM STARTING AND RESETS ANY DETECTED FAULTS AUTOMATIC MODE NORMAL OPERATING POSITION PRESS AND HOLD BUTTON TO PLACE UNIT INTO AUTOMATIC MO...

Страница 28: ...ate or change these settings follow the steps below IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS THE CONTROL PANEL WILL AUTOMATICALLY EXIT THE PROGRAM MODE SET DATE SET DATE If set to O...

Страница 29: ...button The following will scroll across the digital display and then move to the next item Run time Date Time Exercise Cycle date and start time The user can press the LEFT ARROW or RIGHT ARROW at an...

Страница 30: ...d region where the generator is being operated Confirm all settings before operating the generator for the first time For advanced menu items press and hold the left arrow right arrow and escape key f...

Страница 31: ...e specifications shown in this chart Battery Specifications BCI Model 26R Volts 12 Volt DC Amps MIN 525 CCA cold cranking amps Type VRLA Valve Regulated Lead Acid Terminal Hardware Post Dimensions MAX...

Страница 32: ...rged This may cause the engine to run roughly for a few minutes 6 Listen for unusual noises vibration or other indications of abnormal operation Check for oil leaks while engine runs 7 Let engine warm...

Страница 33: ...generator will only enter the exercise cycle if the unit is in the AUTO mode and this exact procedure is followed To set the exercise timer NOTICE The generator is set with a default exercise cycle se...

Страница 34: ...N o t f o r R e p r o d u c t i o n 34 BRIGGSandSTRATTON COM Schematic Diagram...

Страница 35: ...N o t f o r R e p r o d u c t i o n 35...

Страница 36: ...N o t f o r R e p r o d u c t i o n 36 BRIGGSandSTRATTON COM Wiring Diagram...

Страница 37: ...N o t f o r R e p r o d u c t i o n 37...

Страница 38: ...N o t f o r R e p r o d u c t i o n 38 BRIGGSandSTRATTON COM NOTES...

Страница 39: ...N o t f o r R e p r o d u c t i o n 39 NOTES...

Страница 40: ...N o t f o r R e p r o d u c t i o n Page Intentionally left Blank...

Отзывы: