InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013
InteliNano-NT-MRS-1.4-Fast User Guide.pdf
Setpoints
Use
▲
and
▼
buttons to move or change value.
Start
button to select setpoint or confirm changes and
Stop
button to go back.
Basic settings
Setpoint
code
Setpoint name
B01
Nominal Voltage Ph-N
80 – 480 V
B02
Nominal Voltage Ph-Ph
80 – 600 V
B03
Nominal Frequency
50 Hz (1), 60 Hz (2)
B04
Connection Type
Mono Phase (1), SplitPhase (2),
3Ph3Wire (3), 3Ph4Wire (4)
B05
Units Format
Metric unit format (1), US unit
format (2)
B07
Zero Power Mode Delay
0-360 min
B08
Light Tower Mode
Disable (1), Enable (2)
B09
Nominal RPM
100-4000
Engine parameters and protections
Setpoint
code
Setpoint name
E01
Prestart Time
0-600 s
E02
Maximum Cranking Time
0-60 s
E03
Cooling Time
0-3600 s
E04
Oil Pressure Shutdown
0-10 Bar
E05
Coolant Temperature Shutdown
0 -150 °C
E06
Battery Undervoltage
8 – 40 V
E07
Warning Maintenance
0 – 10000 h
E08
Oil Pressure Starter Disengagement
Disable (1), Enable (2)
E09
Choke Time
0 – 3600 s
E10
Minimal Stabilization Time
1 – 300 s
Generator protections
Setpoint
code
Setpoint name
G01
Generator Overvoltage Shutdown
G02
– 200 %
G02
Generator Undervoltage Shutdown
0 -
G01
%
G03
Generator Overfrequency Shutdown G04
– 130 %
G04
Generator Underfrequency Shutdown
0 –
G03
%
To apply all changes return to the main setup menu and restart the controller by pressing the
Stop
button.
Alarms and Events
Events
Manual Start
Remote Start
Manual Stop
Remote Stop
Auto On
Auto Off
Power On
Island Operation
Warnings
Warning Maintenance
Low Battery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communication Error
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.
Technical data
Power supply range
6-36 VDC
Power supply drop-out immunity 100 ms
Power consumption
35 – 295 mA
Zero Power Mode consumption
52 - 344 µA
Operating temperature
-20... 70 °C
Operating humidity
95% non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel)
IP65 with GASKET 4x405 only
IP50 without gasket
Storage temperature
-30... 80 °C
Binary outputs (up to 4)
Low current outputs (2)
500 mA
High current output (2)
6 A (long term) / 10 A (short term)
Total output current
10 A (long term) / 16 A (short term)
Binary inputs (up to 6)
Input resistance
1,5 kΏ
Closed contact voltage
<2 V
Open contact voltage
>3,5 V
Analog inputs (up to 3)
Galvanic insulation
Not insulated
Electrical range
0 - 2500 kΏ
Resolution
0,1 Ώ
Precision
2 % ± 3 Ώ
Charging alternator preexcitation circuit
Excitation current
100 mA
Charging fail threshold
80 %
Generator/Mains measurements
Measurement input
3ph generator voltage
Measurement type
True RMS
Voltage range
480 V Ph-Ph (277 V Ph-N)
Max. measured voltage
340 V Ph-N
Voltage accuracy
1%
Frequency range
40 – 70 Hz
Frequency accuracy
1 %
4