InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 

InteliNano-NT-MRS-1.4-Fast User Guide.pdf 

Setpoints 

Use

 

 

and

 

 

buttons to move or change value. 

Start

 

button to select setpoint or confirm changes and

 

Stop

 

button to go back.

Basic settings

 

Setpoint 

code 

Setpoint name

 

B01 

Nominal Voltage Ph-N 

80 – 480 V

 

B02 

Nominal Voltage Ph-Ph 

80 – 600 V

 

B03 

Nominal Frequency 

50 Hz (1), 60 Hz (2) 

B04 

Connection Type 

Mono Phase (1), SplitPhase (2), 

3Ph3Wire (3), 3Ph4Wire (4) 

B05 

Units Format 

Metric unit format (1), US unit 

format (2) 

B07 

Zero Power Mode Delay 

0-360 min 

B08 

Light Tower Mode 

Disable (1), Enable (2) 

B09 

Nominal RPM 

100-4000 

Engine parameters and protections

 

Setpoint 

code 

Setpoint name

 

E01 

Prestart Time 

0-600 s

 

E02 

Maximum Cranking Time 

0-60 s

 

E03 

Cooling Time 

0-3600 s

 

E04 

Oil Pressure Shutdown 

0-10 Bar

 

E05 

Coolant Temperature Shutdown 

0 -150 °C 

E06 

Battery Undervoltage 

8 – 40 V

 

E07 

Warning Maintenance 

0 – 10000 h

 

E08 

Oil Pressure Starter Disengagement 

Disable (1), Enable (2)

E09 

Choke Time 

0 – 3600 s 

E10 

Minimal Stabilization Time 

1 – 300 s 

Generator protections

 

Setpoint 

code 

Setpoint name

 

G01 

Generator Overvoltage Shutdown 

G02

 – 200 % 

G02 

Generator Undervoltage Shutdown 

0 - 

G01

 % 

G03 

Generator Overfrequency Shutdown  G04

 – 130 % 

G04 

Generator Underfrequency Shutdown 

0 – 

G03

 % 

To apply all changes return to the main setup menu and restart the controller by pressing the

 

Stop

 

button. 

Alarms and Events  

Events

 

Manual Start

 

Remote Start

 

Manual Stop 
Remote Stop

 

Auto On 

Auto Off 
Power On 
Island Operation 

Warnings

 

Warning Maintenance

 

Low Battery

 

Low Fuel Level

 

External Warning 1

 

External Warning 2 
External Warning 3 
ECU Communication Error 

Shutdowns

 

Emergency Stop

 

Overspeed

 

Underspeed 
Low Oil Pressure

 

High Coolant temperature

 

External Shutdown 1

 

External Shutdown 2

 

External Shutdown 3

 

GCB Fail

 

Generator Overvoltage

 

Generator Undervoltage

 

Generator Overfrequency

 

Generator Underfrequency

 

Generator CCW Rotation

 

Start Fail

 

Stop Fail

 

Battery Flat

 

ECU 

For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.

Technical data 

Power supply range 

6-36 VDC 

Power supply drop-out immunity  100 ms  
Power consumption 

35 – 295 mA 

Zero Power Mode consumption 

52 - 344 µA 

Operating temperature 

-20... 70 °C 

Operating humidity 

95% non-condensing (IEC/EN 60068-2-30) 

Protection degree (front panel) 

IP65 with GASKET 4x405 only 
IP50 without gasket 

Storage temperature 

-30... 80 °C 

Binary outputs (up to 4) 
Low current outputs (2) 

500 mA 

High current output (2) 

6 A (long term) / 10 A (short term) 

Total output current 

10 A (long term) / 16 A (short term) 

 

Binary inputs (up to 6) 
Input resistance 

1,5 kΏ 

Closed contact voltage 

<2 V 

Open contact voltage 

>3,5 V 

 

Analog inputs (up to 3) 
Galvanic insulation 

Not insulated 

Electrical range 

0 - 2500 kΏ 

Resolution 

0,1 Ώ 

Precision 

2 % ± 3 Ώ 

Charging alternator preexcitation circuit 
Excitation current 

100 mA 

Charging fail threshold 

80 % 

Generator/Mains measurements 
Measurement input 

3ph generator voltage 

Measurement type 

True RMS 

Voltage range 

480 V Ph-Ph (277 V Ph-N) 

Max. measured voltage 

340 V Ph-N 

Voltage accuracy 

1% 

Frequency range 

40 – 70 Hz 

Frequency accuracy 

1 % 

4

Not for 

Reproduction

Содержание ComAp InteliNano NT

Страница 1: ...ComAp InteliNano NT System Controller Manual Standby Generator System 80021813USN Revision C Briggs Stratton All rights reserved N o t f o r R e p r o d u c t i o n ...

Страница 2: ...t User Guide 3 System Controller 5 Display Screen Structure 6 Alarms Events and History 7 Events 7 Warnings 7 Shut Downs 7 ECU Messages 8 Start and Stop Engine 8 Manual Mode 8 Auto Mode 8 N o t f o r R e p r o d u c t i o n ...

Страница 3: ...utput settings Outputs and inputs Output code Output source Type Terminal assignment O00 Not Used binary T04 T05 T06 T07 O01 Starter binary T04 O02 Fuel Solenoid binary T04 T05 T06 T07 O03 Stop Solenoid binary T04 T05 T06 T07 O04 Alarm binary T04 T05 T06 T07 O07 Ready To Load binary T04 T05 T06 T07 O08 Prestart binary T04 T05 T06 T07 O09 ECU Power Relay binary T04 T05 T06 T07 O10 Choke binary T04 ...

Страница 4: ...e Stop Auto On Auto Off Power On Island Operation Warnings Warning Maintenance Low Battery Low Fuel Level External Warning 1 External Warning 2 External Warning 3 ECU Communication Error Shutdowns Emergency Stop Overspeed Underspeed Low Oil Pressure High Coolant temperature External Shutdown 1 External Shutdown 2 External Shutdown 3 GCB Fail Generator Overvoltage Generator Undervoltage Generator O...

Страница 5: ...solid the controller is in AUTO mode When LED is off the controller is in MANUAL mode G Stop Button Works in MANUAL MODE only Press this button to initiate the stop sequence of the generator when engine is running This button is also used to cancel changes in setup mode to go back or to exit and for alarm confirmation H Alarm LED RED LED will blink when there is one or more active warning or activ...

Страница 6: ... will be displayed on the upper right corner of the display The second screen contains detailed voltage and frequency information The third screen shows engine information oil pressure coolant temperature fuel level and battery voltage The fourth screen shows the most recent alarms or events Display Screen Structure The displayed information is structured into screens Use the up and down arrows to...

Страница 7: ...ve O04 Alarm output will open the red LED will stop blinking and the warning symbol on the screen will go out Shutdowns Shutdown procedure The InteliNano controller opens outputs O05 GCB Close Open O01 Starter O08 Prestart and O02 Fuel Solenoid and then closes O03 Stop Solenoid to stop the engine immediately O04 Alarm output is closed Active or not confirmed protection disables starting Active unc...

Страница 8: ...e green LED above the Auto button is off the controller is in MANUAL mode If there is no active shut down alarm you can start the engine by pressing the Start button The green LED will blink during the starting cooling or stopping procedure While the engine is running the green LED will light steadily The generator is ready to load Press the Stop button to stop the engine The first press will open...

Страница 9: ...ComAp InteliNano NT Manual del sistema de control Generador de reserva Briggs Stratton Todos los derechos reservados 80021813USCN Revisión C N o t f o r R e p r o d u c t i o n ...

Страница 10: ...a de usuario 11 Controlador del sistema 13 Estructura de la pantalla 14 Alarmas eventos e historial 15 Eventos 15 Advertencias 15 Cierres 15 Mensajes ECU 16 Arrancar y parar el motor 16 Modo manual 16 Modo automático 16 N o t f o r R e p r o d u c t i o n ...

Страница 11: ...iones de motor ECU setting Ajustes ECU Generator protections Protecciones de generador Info Información Output settings Ajuste de salidas Entradas y salidas Salidas código Fuente de la salida Tipo Asignación del terminal O00 No Usado binario T04 T05 T06 T0 O01 Arranque binario T04 O02 Solenoide combustible binario T05 O03 Solenoide parada binario T05 O04 Alarma binario T04 T05 T06 T07 O07 Preparad...

Страница 12: ...nings Aviso Mantenimiento Batería Baja Bajo Nivel Combustible Aviso Externo 1 Aviso Externo 2 Aviso Externo 3 ECU Error Comunicación Shutdowns Parada Emergencia Sobrevelocidad Baja velocidad Baja presión de Aceite Alta Temperatura motor Parada Externa 1 Parada Externa 2 Parada Externa 3 Fallo GCB Sobretensión Generador Baja Tensión Generador Alta frecuencia Generador Baja frecuencia Generador Sent...

Страница 13: ...i el LED VERDE permanece encendido el controlador está en modo AUTO Cuando el LED está apagado el controlador está en modo MANUAL G Botón Stop Paro Funciona únicamente en MODO MANUAL Pulse este botón para iniciar la secuencia de paro del generador cuando el motor está en funcionamiento Este botón también se usa para cancelar los cambios en el modo de ajuste regresar o salir y para la confirmación ...

Страница 14: ... mostrada estado del GCB únicamente cuando está configurada y el contador de horas de funcionamiento Cuando alguna alarma se activa se muestra el símbolo general de advertencia en la esquina superior derecha de la LCD La segunda pantalla contiene la tensión y la información de frecuencia La tercera pantalla muestra la información del motor presión del aceite temperatura del refrigerante nivel de c...

Страница 15: ...a O04 se abre el LED rojo que está arriba del botón Stop deja de parpadear y el símbolo de advertencia en la pantalla principal se apaga Cierres Procedimiento de cierre El controlador InteliNano abre las salidas O05 cerrar abrir GCB O01 motor de arranque O08 arranque previo y O02 solenoide de combustible y cierra la O03 solenoide de paro para detener el motor de inmediato La salida O04 alarma está...

Страница 16: ...D verde que está arriba del botón Auto está apagado el controlador está en modo MANUAL Cuando no hay alarmas de cierre activa puede arrancar el motor pulsando el botón Start El LED verde que está arriba del botón parpadea El LED parpadea durante el procedimiento de arranque enfriamiento y paro Cuando el motor ya arrancó el LED verde deja de parpadear y se ilumina de manera permanente El generador ...

Страница 17: ...ComAp InteliNano NT Manuel du Contrôleur Système Système de génératrice auxiliaire Briggs Stratton Tous droits réservés 80021813USCN Révision C N o t f o r R e p r o d u c t i o n ...

Страница 18: ...pide 19 Contrôleur de système 21 Structure de l écran d affichage 22 Alarmes Événements et Historiques 23 Événements 23 Avertissements 23 Arrêts 23 Messages ECU 24 Démarrage et arrêt du moteur 24 Mode manuel 24 Mode automatique 24 N o t f o r R e p r o d u c t i o n ...

Страница 19: ...19 Guide de démarrage rapide n est pas disponible en Français N o t f o r R e p r o d u c t i o n ...

Страница 20: ...20 BRIGGSandSTRATTON COM Guide de démarrage rapide n est pas disponible en Français N o t f o r R e p r o d u c t i o n ...

Страница 21: ...rte est allumée en continu cela signifie que le contrôleur est au mode automatique La DEL verte est éteinte cela signifie que le contrôleur est au mode manuel G Bouton d arrêt Stop Fonctionne uniquement au mode manuel Appuyer sur ce bouton pour initier la séquence d arrêt de la génératrice lorsque le moteur est en marche Ce bouton sert aussi à annuler les changements au mode de réglage à faire un ...

Страница 22: ...énéral s affiche dans le coin supérieur droit de l écran Un deuxième écran présente les renseignements détaillés sur la tension et la fréquence Les renseignements suivants sur le moteur sont affichés au troisième écran pression d huile niveau de carburant et tension de la batterie Un quatrième écran affiche les plus récents événements et alarmes Structure de l écran d affichage Les renseignements ...

Страница 23: ...if Lorsqu un avertissement devient inactif la sortie O04 Alarm s ouvre et la DEL rouge au dessus du bouton d arrêt cesse de clignoter et le symbole d avertissement de l écran principal disparait Arrêts Procédure d arrêt Le contrôleur InteliNano ouvre les sorties O05 GCB Close Open O01 Starter O08 Prestart et O02 Fuel Solenoid et ferme O03 Stop Solenoid pour arrêter immédiatement le moteur La sorti...

Страница 24: ...vez pas démarrer le moteur ou connecter une charge en appuyant sur le bouton de démarrage Start Le contrôleur se met automatiquement en marche lorsque toutes les conditions de démarrage et de connexion de charges sont atteintes AVIS Le moteur en mode automatique NE peut PAS être arrêté à l aide du bouton d arrêt Stop Arrêt non confirmé inactif La sortie O04 Alarm est fermée la DEL rouge au dessus ...

Отзывы: