InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 

InteliNano-NT-MRS-1.4-Fast User Guide.pdf 

CAN INTERFACE

GENERATOR VOLTAGE 

MEASUREMENT

T16 = Neutral
T17 = Phase 1
T18 = Phase 2
T19 = Phase 3

USB interface

L

COM

H

INTPUT TERMINALS

T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog input – Low Fuel Level
T14 = binary/analog input – Coolan Temperature
T15 = binary/analog input – Oil Pressure

OUTPUT TERMINALS

T04 = binary output – Starter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)

POWER SUPPLY, D+

T01 = BATT -
T02 = D+
T03 = BATT +

G

ECU

DIESEL / GASOLINE ENGINE

GENERATOR

LOAD

Fuel Solenoid

Batter

y

Sarter

Fuel Level Analog

Coolant Tem

perature Analog

Oil Pr

essure Analog

D+

-

+

Alarm

Ready To Load

Fuel Solenoid

Starter

COM

Remote Start And Load

Em
er

gency Stop

CAN

L COM H

USB

Batter

y +

Batter

y -

D +

PC

L1

L2

L3

N

InteliNano NT

 

MRS

 Fast User Guide 

Typical wiring diagram 

Accessing the setup mode 

Ensure the engine is stopped and the controller is in Manual mode (green LED above button

Auto

 

is turned off).

 

If you have not configured the custom initialization (init) screen then press and hold 

Stop

button, then briefly press 

button

 

and then 

Auto

.

If you have already created your own init screen then press and hold 

Stop

 

button and then briefly press  

, the custom init screen will appear, keep holding the 

Stop

button. Then press

 

to switch LCD to default init screen, and then press

Auto

.

To move up and down in the setup menu use

 

and

 

 

buttons. Press

Start

button to select or

Stop

button for exit.

Basic settings

 

Input settings

 

Engine parameters and protections

 

ECU setting

 

Generator protections

Info

Output settings 

Outputs and inputs 

Output 

code 

Output source 

Type  Terminal assignment 

O00  Not Used

 

binary  T04, T05, T06, T07 

O01  Starter

 

binary  T04 

O02  Fuel Solenoid

 

binary  T04, T05, T06, T07 

O03  Stop Solenoid

 

binary  T04, T05, T06, T07 

O04  Alarm

 

binary  T04, T05, T06, T07 

O07  Ready To Load

 

binary  T04, T05, T06, T07 

O08  Prestart

 

binary  T04, T05, T06, T07 

O09  ECU Power Relay

 

binary  T04, T05, T06, T07 

O10  Choke 

binary  T04, T05, T06, T07 

O11  Glow Plugs 

binary  T04, T05, T06, T07 

Normally Open Contact – output 

Normally Open Contact - input 

button 

Normally Closed Contact – output 

Normally Closed Contact – input 

button 

User curves

 

I21

I23

I25

VDO Level % 

VDO 5 Bar

VDO 40-120 °C 

Datcon Level % 

VDO 10 Bar

VDO 50-150 °C 

Datcon 5 Bar 

Datcon High °C 

Datcon 7 Bar 

Datcon Low °C

Datcon 10 Bar 

Not selected 

Not selected 

Not selected 

Input 

code 

Input source 

Type 

Terminal assignment 

I00  Not Used

 

binary  T07, T11, T12, T13, T14, T15

I01  Emergency Stop

 

binary  T07, T11, T12, T13, T14, T15

I02  Remote Start/Stop

 

binary  T11 

I03  Remote Start And Load

 

binary  T11 

I04  Access Lock

 

binary  T07, T11, T12, T13, T14, T15 

I07  GCB Feedback

 

binary  T07, T11, T12, T13, T14, T15

I10  External Warning 1

 

binary  T07, T11, T12, T13, T14, T15

I11  External Warning 2

 

binary  T07, T11, T12, T13, T14, T15

I12  External Warning 3

 

binary  T07, T11, T12, T13, T14, T15

I13  External Shutdown 1

 

binary  T07, T11, T12, T13,T14, T15

I14  External Shutdown 2

 

binary  T07, T11, T12, T13, T14, T15

I15  External Shutdown 3

 

binary  T07, T11, T12, T13, T14, T15

I20  Low Fuel Level

 

binary  T07, T11, T12, T13, T14, T15

I21  Fuel Level Analog

 

analog  T13, T14, T15 

I22  Low Oil Pressure

 

binary  T07, T11, T12, T13, T14, T15

I23  Oil Pressure Analog

 

analog  T13, T14, T15 

I24  High Coolant Temperature

 

binary  T07, T11, T12, T13, T14, T15

I25  Coolant Temperature Analog

 

analog  T13, T14, T15 

Dimensions

Case dimensions:

 

118mm x108mm x 40mm

Panel Cutout: 96mm x 96mm 

W

ARNING

!

 

 

If D+ is not used, connect this terminal to battery positive!

3

Not for 

Reproduction

Содержание ComAp InteliNano NT

Страница 1: ...ComAp InteliNano NT System Controller Manual Standby Generator System 80021813USN Revision C Briggs Stratton All rights reserved N o t f o r R e p r o d u c t i o n ...

Страница 2: ...t User Guide 3 System Controller 5 Display Screen Structure 6 Alarms Events and History 7 Events 7 Warnings 7 Shut Downs 7 ECU Messages 8 Start and Stop Engine 8 Manual Mode 8 Auto Mode 8 N o t f o r R e p r o d u c t i o n ...

Страница 3: ...utput settings Outputs and inputs Output code Output source Type Terminal assignment O00 Not Used binary T04 T05 T06 T07 O01 Starter binary T04 O02 Fuel Solenoid binary T04 T05 T06 T07 O03 Stop Solenoid binary T04 T05 T06 T07 O04 Alarm binary T04 T05 T06 T07 O07 Ready To Load binary T04 T05 T06 T07 O08 Prestart binary T04 T05 T06 T07 O09 ECU Power Relay binary T04 T05 T06 T07 O10 Choke binary T04 ...

Страница 4: ...e Stop Auto On Auto Off Power On Island Operation Warnings Warning Maintenance Low Battery Low Fuel Level External Warning 1 External Warning 2 External Warning 3 ECU Communication Error Shutdowns Emergency Stop Overspeed Underspeed Low Oil Pressure High Coolant temperature External Shutdown 1 External Shutdown 2 External Shutdown 3 GCB Fail Generator Overvoltage Generator Undervoltage Generator O...

Страница 5: ...solid the controller is in AUTO mode When LED is off the controller is in MANUAL mode G Stop Button Works in MANUAL MODE only Press this button to initiate the stop sequence of the generator when engine is running This button is also used to cancel changes in setup mode to go back or to exit and for alarm confirmation H Alarm LED RED LED will blink when there is one or more active warning or activ...

Страница 6: ... will be displayed on the upper right corner of the display The second screen contains detailed voltage and frequency information The third screen shows engine information oil pressure coolant temperature fuel level and battery voltage The fourth screen shows the most recent alarms or events Display Screen Structure The displayed information is structured into screens Use the up and down arrows to...

Страница 7: ...ve O04 Alarm output will open the red LED will stop blinking and the warning symbol on the screen will go out Shutdowns Shutdown procedure The InteliNano controller opens outputs O05 GCB Close Open O01 Starter O08 Prestart and O02 Fuel Solenoid and then closes O03 Stop Solenoid to stop the engine immediately O04 Alarm output is closed Active or not confirmed protection disables starting Active unc...

Страница 8: ...e green LED above the Auto button is off the controller is in MANUAL mode If there is no active shut down alarm you can start the engine by pressing the Start button The green LED will blink during the starting cooling or stopping procedure While the engine is running the green LED will light steadily The generator is ready to load Press the Stop button to stop the engine The first press will open...

Страница 9: ...ComAp InteliNano NT Manual del sistema de control Generador de reserva Briggs Stratton Todos los derechos reservados 80021813USCN Revisión C N o t f o r R e p r o d u c t i o n ...

Страница 10: ...a de usuario 11 Controlador del sistema 13 Estructura de la pantalla 14 Alarmas eventos e historial 15 Eventos 15 Advertencias 15 Cierres 15 Mensajes ECU 16 Arrancar y parar el motor 16 Modo manual 16 Modo automático 16 N o t f o r R e p r o d u c t i o n ...

Страница 11: ...iones de motor ECU setting Ajustes ECU Generator protections Protecciones de generador Info Información Output settings Ajuste de salidas Entradas y salidas Salidas código Fuente de la salida Tipo Asignación del terminal O00 No Usado binario T04 T05 T06 T0 O01 Arranque binario T04 O02 Solenoide combustible binario T05 O03 Solenoide parada binario T05 O04 Alarma binario T04 T05 T06 T07 O07 Preparad...

Страница 12: ...nings Aviso Mantenimiento Batería Baja Bajo Nivel Combustible Aviso Externo 1 Aviso Externo 2 Aviso Externo 3 ECU Error Comunicación Shutdowns Parada Emergencia Sobrevelocidad Baja velocidad Baja presión de Aceite Alta Temperatura motor Parada Externa 1 Parada Externa 2 Parada Externa 3 Fallo GCB Sobretensión Generador Baja Tensión Generador Alta frecuencia Generador Baja frecuencia Generador Sent...

Страница 13: ...i el LED VERDE permanece encendido el controlador está en modo AUTO Cuando el LED está apagado el controlador está en modo MANUAL G Botón Stop Paro Funciona únicamente en MODO MANUAL Pulse este botón para iniciar la secuencia de paro del generador cuando el motor está en funcionamiento Este botón también se usa para cancelar los cambios en el modo de ajuste regresar o salir y para la confirmación ...

Страница 14: ... mostrada estado del GCB únicamente cuando está configurada y el contador de horas de funcionamiento Cuando alguna alarma se activa se muestra el símbolo general de advertencia en la esquina superior derecha de la LCD La segunda pantalla contiene la tensión y la información de frecuencia La tercera pantalla muestra la información del motor presión del aceite temperatura del refrigerante nivel de c...

Страница 15: ...a O04 se abre el LED rojo que está arriba del botón Stop deja de parpadear y el símbolo de advertencia en la pantalla principal se apaga Cierres Procedimiento de cierre El controlador InteliNano abre las salidas O05 cerrar abrir GCB O01 motor de arranque O08 arranque previo y O02 solenoide de combustible y cierra la O03 solenoide de paro para detener el motor de inmediato La salida O04 alarma está...

Страница 16: ...D verde que está arriba del botón Auto está apagado el controlador está en modo MANUAL Cuando no hay alarmas de cierre activa puede arrancar el motor pulsando el botón Start El LED verde que está arriba del botón parpadea El LED parpadea durante el procedimiento de arranque enfriamiento y paro Cuando el motor ya arrancó el LED verde deja de parpadear y se ilumina de manera permanente El generador ...

Страница 17: ...ComAp InteliNano NT Manuel du Contrôleur Système Système de génératrice auxiliaire Briggs Stratton Tous droits réservés 80021813USCN Révision C N o t f o r R e p r o d u c t i o n ...

Страница 18: ...pide 19 Contrôleur de système 21 Structure de l écran d affichage 22 Alarmes Événements et Historiques 23 Événements 23 Avertissements 23 Arrêts 23 Messages ECU 24 Démarrage et arrêt du moteur 24 Mode manuel 24 Mode automatique 24 N o t f o r R e p r o d u c t i o n ...

Страница 19: ...19 Guide de démarrage rapide n est pas disponible en Français N o t f o r R e p r o d u c t i o n ...

Страница 20: ...20 BRIGGSandSTRATTON COM Guide de démarrage rapide n est pas disponible en Français N o t f o r R e p r o d u c t i o n ...

Страница 21: ...rte est allumée en continu cela signifie que le contrôleur est au mode automatique La DEL verte est éteinte cela signifie que le contrôleur est au mode manuel G Bouton d arrêt Stop Fonctionne uniquement au mode manuel Appuyer sur ce bouton pour initier la séquence d arrêt de la génératrice lorsque le moteur est en marche Ce bouton sert aussi à annuler les changements au mode de réglage à faire un ...

Страница 22: ...énéral s affiche dans le coin supérieur droit de l écran Un deuxième écran présente les renseignements détaillés sur la tension et la fréquence Les renseignements suivants sur le moteur sont affichés au troisième écran pression d huile niveau de carburant et tension de la batterie Un quatrième écran affiche les plus récents événements et alarmes Structure de l écran d affichage Les renseignements ...

Страница 23: ...if Lorsqu un avertissement devient inactif la sortie O04 Alarm s ouvre et la DEL rouge au dessus du bouton d arrêt cesse de clignoter et le symbole d avertissement de l écran principal disparait Arrêts Procédure d arrêt Le contrôleur InteliNano ouvre les sorties O05 GCB Close Open O01 Starter O08 Prestart et O02 Fuel Solenoid et ferme O03 Stop Solenoid pour arrêter immédiatement le moteur La sorti...

Страница 24: ...vez pas démarrer le moteur ou connecter une charge en appuyant sur le bouton de démarrage Start Le contrôleur se met automatiquement en marche lorsque toutes les conditions de démarrage et de connexion de charges sont atteintes AVIS Le moteur en mode automatique NE peut PAS être arrêté à l aide du bouton d arrêt Stop Arrêt non confirmé inactif La sortie O04 Alarm est fermée la DEL rouge au dessus ...

Отзывы: