12
BRIGGSandSTRATTON.COM
Troubleshooting
Problem
Cause
Correction
Automatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Automatic transfer switch does not
transfer to utility
1. Utility disconnect breaker open
(Models 071020 & 071021 only).
2. Service disconnect breaker open.
3. Utility voltage not acceptable.
1. Reset utility disconnect breaker
(Models 071020 & 071021 only).
2. Reset service disconnect breaker.
3. Wait for utility voltage to return to
normal.
Generator is still running after switch
transfers to utility power
Engine cool down period.
Engine should stop after 1 minute.
Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power
1. A-A or B-B contacts not operating
correctly.
2. Too much load on generator.
3. Current transformer not connected.
4. Broken current transformer.
1. Check A-A or B-B contacts for
proper operation and/or check
control wiring to external load.
2. Decrease load to generator.
3. Plug CT connectors into control
board.
4. Contact local Briggs & Stratton
Power Products service center.
Generator is still running after utility
power is restored
1. Minimum engine run time has not
elapsed.
2. Fuse(s) in transfer switch is
defective.
1. Wait five minutes for transfer
switch to retransfer to utility power.
2. Check fuse(s) and replace if
necessary.
Содержание 71018
Страница 13: ...13 Schematic and Wiring Diagram Models 071018 and 071019 ...
Страница 14: ...14 BRIGGSandSTRATTON COM Schematic and Wiring Diagram Models 071020 and 071021 ...
Страница 17: ...Home Generator Systems Manual de Instalación y del Operario 100 200 Amp Automatic Transfer Switch ...
Страница 31: ...Home Generator Systems Guide d Installation et d Utilisation 100 200 Amp Automatic Transfer Switch ...