Содержание 6344

Страница 1: ...ctions Neutral Tap Kits For Direct Power Model 6344 Model 6345 Model 6346 Copyright Briggs Stratton Milwaukee WI USA 80015784 Revision A Questions Help is just a moment away Call Technical Services 800 743 4115 Monday Friday 8 00 AM to 5 00 PM Central Time ...

Страница 2: ...tral Tap Kit Contents Parallel Tap GTA 250 0 1 ea Cover GTC 250 350 1 ea Oxide Inhibitor 1 ea Installation instruction 1 ea 6345 Neutral Tap Kit Contents Parallel Tap GTA 0 0 1 ea Cover GTC 0 1 ea Oxide Inhibitor 1 ea Installation instruction 1 ea 6346 GTA 250 0 6345 GTA 0 0 6344 GTA 2 2 Main Tap Main Tap Main Tap Wire Range AWG 250 0 14 1 0 0 2 0 14 2 12 2 14 NOTE The Neutral Tap Kit is suitable ...

Страница 3: ...zard Symbols and Meanings Electrical Shock Rotating Parts Auto Start Safety WARNING Generator produces hazardous voltage Failure to properly ground generator could result in electrocution Failure to isolate generator from utility power could result in death or serious injury to electric utility workers due to back feed of electrical energy DO NOT touch bare wires or bare receptacles DO NOT use gen...

Страница 4: ... cable from negative battery terminal indicated by NEGATIVE NEG or NOTE Use of Oxide Inhibitor included with this Kit is recommended on all connections Install Neutral Tap Kit 1 Check to make sure that all power sources to the meter enclosure are OFF 2 Determine where the neutral tap should be located inside the meter enclosure Then see where the main neutral tap lines up with the White Neutral wi...

Страница 5: ...16 275 3 8 375 1 2 500 9 16 600 Table 2 Tightening Torque Values for ILSCO Mechanical Screw Connectors Wire Size Tightening Torque in Inch Pounds Screw Driver External Drive Wrench 14 AWG 35 75 12 AWG 35 75 10 AWG 35 75 8 AWG 40 75 6 AWG 45 110 4 AWG 45 110 2 AWG 50 150 1 AWG 50 150 1 0 AWG 50 180 2 0 AWG 50 180 3 0 AWG 250 4 0 AWG 250 250 kcmil 325 350 kcmil 325 500 kcmil 375 600 kcmil 375 700 kc...

Страница 6: ...6 BRIGGSandSTRATTON COM 9 When installing the meter adapter to the meter socket check to make sure that jaws align properly with the protective cover as shown in Figure 5 Figure 5 10 This concludes the installation of the Neutral Tap kit ...

Страница 7: ...N o t f o r R e p r o d u c t i o n 7 This page intentionally left blank ...

Страница 8: ...N o t f o r R e p r o d u c t i o n 8 BRIGGSandSTRATTON COM This page intentionally left blank ...