Engine Maintenance

Oil
Oil Recommendations

We recommend the use of Briggs & Stratton Warranty Certified oils for best
performance. Other high-quality detergent oils are acceptable if classified for 

service SF, SG, SH, SJ or higher. DO NOT use special additives.
Outdoor temperatures determine the proper oil viscosity for the engine. 

Use the chart to select the best viscosity for the outdoor temperature range 

expected.

*  Below 4°C (40°F) the use of SAE 30 will result in hard starting.

**  Above 27°C (80°F) the use of 10W30 may cause increased oil consumption. 

Check oil level more frequently.

Checking Oil Level

  

 Figure 

4

 

7

Oil level should be checked prior to each use or at least every 8 hours of 

operation. Keep oil level maintained.

  1.  Make sure generator is on a level surface.
  2.  Clean area around oil fill (

4, H

), remove oil cap/dipstick and wipe 

dipstick with clean cloth. Replace dipstick. Remove and and check oil 

level.

NOTICE

   DO NOT screw in dipstick when checking oil level.

  3.  Verify oil is at full mark (

7, A

) on dipstick. Replace and tighten oil cap/

dipstick.

Adding Engine Oil

  1.  Make sure generator is on a level surface.
  2.  Check oil level as described in 

Checking Oil Level

.

  3.  If needed, slowly pour oil into oil fill opening to the full mark on dipstick. 

DO NOT overfill.

NOTICE

   Overfilling with oil could cause the engine to not start, or hard 

starting.

•  DO NOT overfill.

•  If over the full mark on dipstick, drain oil to reduce oil level to full mark on 

dipstick.

  4.  Replace and tighten oil cap/dipstick.

Changing Engine Oil

   

Figure

 

4

If you are using your generator under extremely dirty or dusty conditions, or in 

extremely hot weather, change the oil more often.

  KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE. 

CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION 

CENTERS.

Change the oil while the engine is still warm from running, as follows:

  1.  Make sure unit is on a level surface.
  2.  Disconnect the spark plug wire from the spark plug and place the wire 

where it cannot contact spark plug.

  3.  Clean area around oil drain plug (

4, J

). The oil drain plug is located at 

base of engine, opposite carburetor.

  4.  Remove oil drain plug and drain oil completely into a suitable container.
  5.  Reinstall oil drain plug and tighten securely. Remove oil fill cap/dipstick.
  6.  Repeat steps 3 and 4 to add engine oil as described in 

Adding Engine 

Oil

.

  7.  Wipe up any spilled oil.

Service Air Cleaner

  

 Figure

 

8

Your engine will not run properly and may be damaged if you run it with a dirty 

air cleaner. Service more often if operating under dirty or dusty conditions.

To service the air cleaner, follow these steps:

  1.  Loosen screws (

A

) and remove air cleaner cover (

B

).

  2.  Carefully remove cartridge (

C

) from base (

D

).

  3.  Install clean (or new) air cleaner assembly inside cover. Dispose of old 

filter properly.

  4.  Assemble air cleaner cover onto base and tighten screws.

Service Spark Plug   

Figure

 

9

Changing the spark plug will help your engine to start easier and run better.
  1.  Clean area around spark plug.
  2.  Remove and inspect spark plug.
  3.  Check electrode gap with wire feeler gauge and reset spark plug gap to 

recommended gap if necessary (see 

Specifications

).

  4.  Replace spark plug if electrodes are pitted, burned or porcelain 

is cracked. Use the recommended replacement spark plug. See 

Specifications.

  5.  Install spark plug and tighten firmly.

16 BRIGGSandSTRATTON.COM

 

WARNING

   Unintentional sparking could cause fire or electric shock 

resulting in death or serious injury.

WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR

•  Disconnect the spark plug wire from the spark plug and place the wire 

where it cannot contact spark plug.

WHEN TESTING FOR ENGINE SPARK

•  Use approved spark plug tester.

•  DO NOT check for spark with spark plug removed.

 

CAUTION   

Avoid prolonged or repeated skin contact with used motor 

oil.

•  Used motor oil has been shown to cause skin cancer in certain laboratory 

animals.

•  Thoroughly wash exposed areas with soap and water.

Содержание 030618

Страница 1: ...RATTON POWER PRODUCTS GROUP LLC MILWAUKEE WISCONSIN U S A Manual No 80007328 Revision Portable Generator Operator s Manual This generator is rated in accordance with CSA Canadian Standards Association standard C22 2 No 100 04 motors and generators ...

Страница 2: ...N o t f o r R e p r o d u c t i o n 2 BRIGGSandSTRATTON COM H B P S E C 4 M L A B C 3 D A F G 2 A D A B C G E F 1 J K R T N D ...

Страница 3: ...N o t f o r R e p r o d u c t i o n 3 3 9 A B 6 C 7 A D B A C 8 11 A 5 10 B A C ...

Страница 4: ...e thousands of Briggs Stratton authorized service dealers worldwide who provide quality service You can also find the nearest Authorized Service Dealer in our dealer locator map on the Internet at BRIGGSandSTRATTON COM Table of Contents Safe Operation Checklist 5 Operator Safety 6 Equipment Description 6 Important Safety Information 6 Assembly 8 Unpack Generator 8 Install Wheel Kit 8 Add Engine Oi...

Страница 5: ...Oil and Fuel Engine oil filled to proper level See Add Engine Oil Fuel tank filled at or below red indicator See Add Fuel Inspect fuel lines tank cap and fittings each time before using generator DO NOT use if fuel leak or damage is found Electrical When connecting to a buildings electrical system install listed transfer equipment See Connecting to a Building s Electrical System Electrical cords a...

Страница 6: ...nce is felt and then pull rapidly to avoid kickback NEVER start or stop engine with electrical devices plugged in and turned on WARNING Generator voltage could cause electrical shock or burn resulting in death or serious injury Use approved transfer equipment to prevent backfeed by isolating generator from electric utility workers When using generator for backup power notify utility company DO NOT...

Страница 7: ...uipment marine applications or enclosure DO NOT tip engine or equipment at angle which causes fuel to spill DO NOT stop engine by moving choke control to Choke position WHEN TRANSPORTING MOVING OR REPAIRING EQUIPMENT Transport move repair with fuel tank EMPTY or with fuel shutoff valve OFF DO NOT tip engine or equipment at angle which causes fuel to spill Disconnect spark plug wire WHEN STORING FU...

Страница 8: ...ters 2 500 feet with the high altitude kit is not recommended Attach Negative Battery Cable 030620 Only Figure 3 Your unit is equipped with electric start capability but can be started manually If you choose not to use the electric start feature you do not need to connect the negative battery cable The sealed battery on the generator is pre installed except for the negative black battery cable To ...

Страница 9: ...s a buildup of CO the alarm will alert the occupants by flashing visual indicator light and alarm Smoke alarms cannot detect CO gas Operate this product ONLY outside far away from windows doors and vents to reduce the risk of carbon monoxide gas from accumulating and potentially being drawn towards occupied spaces DO NOT run this product inside homes garages basements crawlspaces sheds or other pa...

Страница 10: ...uel tank causing a fire resulting in death or serious injury Portable generator must be at least 1 5m 5 feet from any structure overhang trees windows doors any wall opening shrubs or vegetation over 30 5 cm 12 inches in height DO NOT place portable generator under a deck or other type of structure that may confine airflow Smoke alarm s MUST be installed and maintained indoors according to the man...

Страница 11: ...uld cut current off quickly enough so that a person in normal health should not suffer any serious electrical injury Test RCBO Test your RCBO every month as follows 1 While generator is running push Test T button The circuit breaker should trip handle will move to approximate center position which will disconnect power to outlets NOTICE If circuit breaker does not trip DO NOT use generator Call a ...

Страница 12: ...tion I 3 Move choke lever 4 R to choke position 4A For electric starting model 030620 only turn and hold key in start switch 4 A to start position until generator starts To prolong the life of starter components DO NOT hold key in start position for more than 5 seconds and pause for at least 1 minute between starting attempts If engine starts proceed to step 6 If engine fails to start proceed to s...

Страница 13: ...Weather Shelter 1 Using non combustible material with a fire rating of at least one hour build a shelter that will enclose three sides and the top of the generator Make sure muffler side of generator is exposed NOTICE Contact your local building material supplier for non combustible materials with a fire rating of at least one hour NOTICE Be sure shelter can easily be repositioned for change in wi...

Страница 14: ...ferably the largest load you have 3 Permit the generator output to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again permit the generator to stabilize 6 Repeat steps 4 and 5 for each additional load NEVER add more loads than the generator capacity Take special care to consider surge loads in generator capacity as described above Wattag...

Страница 15: ...dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings Cleaning Daily or before use look around and underneath the generator for signs of oil or fuel leaks Clean accumulated debris from inside and outside the generator Keep the linkage spring and other engine controls clean Keep the area around and behind the muffler free from any combu...

Страница 16: ...s 1 Make sure unit is on a level surface 2 Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug 3 Clean area around oil drain plug 4 J The oil drain plug is located at base of engine opposite carburetor 4 Remove oil drain plug and drain oil completely into a suitable container 5 Reinstall oil drain plug and tighten securely Remove oil fill cap di...

Страница 17: ...trol in the engine has not been treated with a fuel stabilizer it must be drained into an approved container Run the engine until it stops from lack of fuel The use of a fuel stabilizer in the storage container is recommended to maintain freshness Change Engine Oil While engine is still warm drain oil from crankcase Refill with recommended grade See Changing Engine Oil Other Storage Tips 1 Do Not ...

Страница 18: ...y 3 See Don t Overload Generator in Operation section 4 Contact authorized service facility 5 Clean or replace fuel filter Engine will not start shuts down when running or starts and runs rough 1 On off switch set to off position 0 2 Fuel Valve is in off 0 position 3 Low oil level 4 Dirty air cleaner 5 Clogged or dirty fuel filter 6 Out of fuel 7 Stale fuel 8 Spark plug wire not connected to spark...

Страница 19: ...period specified below it will repair or replace free of charge any part that is defective in material or workmanship or both Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser This warranty is effective for and is subject to the time periods and conditions stated below For warranty service find the nearest Authorized Service Dealer...

Страница 20: ...N o t f o r R e p r o d u c t i o n BRIGGS STRATTON POWER PRODUCTS GROUP LLC MILWAUKEE WISCONSIN U S A ...

Отзывы: