IMPORTANT INFORMATION
When the CV mode is selected, the parameters that can be set to AC voltage and
DC offset voltage.
when the CC mode is selected, the parameters can be set to AC current and DC
offset current.
5.6.3
DC (-DC option)
In source and sink mode, ESA can also be designed as a DC output, allowing DC voltage and
current to be generated. The output frequency range is extended to DC~100Hz. The DC voltage
range is 420V (standard), and the accuracy is 0.2% FS.
Test steps:
Click "Sequence Mode" to enter panel, select the DC output mode (DC) on the right side(Figure
5-13②
), the user can select different operating modes (CV/CC/CP) according to the test
requirements, and set the DC voltage/ Current. When the parameter setting is completed, click
"Apply"→"Power On"→"Output On", the power supply is on and outputs DC
voltage/current/Power.
IMPORTANT INFORMATION
In the DC output mode, only need to set the voltage/current of a certain phase,
and it will be the output DC voltage/current. If -1P option is added, the three-
phase parameters (L1, L2, L3) need to be set at the same time. For example, in ESA
30-300-46, the standard output DC current is 23A/phase, if -1P option is added
(add single phase output), after changing the corresponding wiring, the maximum
output DC current will be 69A.
(when related to wiring issues, please combine 2.2.2 and 2.2.3)