background image

Ussc

ASSEMBLY INSTRUCTIONS

Combustion Air Intake

This appliance requires a source of combustion air. If you home is of tight construction or has nega-
tive pressure problems, you will need an outside source of air.

You have two options. You may cut a rectangular hole in the fl oor of your home and the fl oor protector, or 
purchase a standard 4” Dryer Vent kit from your local hardware supply store and install it on the rear of the 
pedestal.

If your choice is to cut a rectangular hole in the fl oor and fl ooring protector, refer to the below illustrations for 
assistance. You must place a rodent screen between the fl oor protector and the fl oor to prevent passage of 
any unwanted vermin into your home.

If using a Dryer venting kit, the outlet cover must be of a design that DOES NOT close by means of 
a fl ap or trap door. 

You must purchase a style that allows a continuous in-fl ow of air and that has a rodent 

screen. You will also need a Combustion Air Adapter to attach to the pedestal of the appliance. This adapter 
can be purchased from your dealer.

If your home is not of tight construction, you can just simply remove the 4” round knockout in the rear of the 
pedestal.

 “Combustion Air thru Unit Base” installation:

First, decide the location of the appliance. Then, cut a 2” x 6” rectangular opening in the fl oor protector 
within the appliance base’s perimeter. Using the fl ooring protector as a template, position it in place 
and mark onto the fl oor of your home where to make your next cut. Make the cut in your home’s fl oor 
slightly larger than the 2” x 6” to accommodate any misalignment. Attach a piece of screen over the 
hole to prevent any unwanted vermin entering your home. Complete your appliance install.

 “Dryer Venting Kit” installation:

Begin by installing the 4” adapter to the rear of the appliance using the screws provided. If not already, 
remove the round knock-out from the pedestal. Follow the manufacturer’s installation instructions for 
attaching the dryer vent kit to the home. Then attach it to the adapter on the appliance.

“Combustion Air thru Unit Base” Installation

“Dryer Venting Kit” Installation

FLOOR PROTECTOR

Home’s Floor

Rodent Screen

Non-Combustible Floor

Make a 2” x 6” (51mm x 152mm) 
cutout through both the floor 
protector and home’s flooring 
within the perimeter of the 
appliance’s base.

Содержание SW4100

Страница 1: ...ual before you install or useyournewroomheater Failuretofollowinstruc tions may result in property damage bodily injury or even death Improper Installation Could Void Your Warranty SAFETY TESTED TO UL...

Страница 2: ...CALS OR FLUIDS TO IGNITE THE FIRE DO NOT LEAVE THE STOVE UNATTENDED WHEN THE DOOR IS SLIGHTLY OPENED DO NOT BURN GARBAGE FLAMMABLE FLUID SUCH AS GASOLINE NAPHTHA OR MOTOR OIL DO NOT CONNECT TO ANY AIR...

Страница 3: ..._________ Reason for Purchase Alternative Heat Main Heat Source Decoration Cost Other _________________________ What was the determining factor for purchasing your new appliance _______ I have read th...

Страница 4: ...4 Ussc CUT HERE CUT HERE Fold Here Fold Here United States Stove Company P O Box 151 South Pittsburg TN 37380 Fold Here PLACE STAMP HERE...

Страница 5: ...ustible floor protector as specified in this manual All chimney and chimney connector components required for your particular chimney installation Assembly Flue Collar Assembly 1 Mount the flue collar...

Страница 6: ...f your home is not of tight construction you can just simply remove the 4 round knockout in the rear of the pedestal Combustion Air thru Unit Base installation First decide the location of the applian...

Страница 7: ...ATED SHALL BE PROVIDED WHEN REQUIRED POSITIONING THE STOVE It is very important to position the wood stove as close as possible to the chimney and in an area that will favor the most efficient heat di...

Страница 8: ...actor is given with a required thickness T in inches R 1 k x T C factor is given R 1 C Example If the floor protector is 4 brick with a C factor of 1 25 over 1 8 mineral board with a k factor of 0 29...

Страница 9: ...vertical walls and for vertical flue pipe The chimney connector must not pass through an attic or roof space closet or similar concealed space a floor or a ceiling For Canadian installations where pa...

Страница 10: ...per foot with the upper end of the section toward the chimney Any installation with a horizontal run of chimney pipe must conform to NFPA 211 You may contact NFPA National Fire Protection Association...

Страница 11: ...lowing recommendations may be useful for the installation of your chimney 1 DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE 2 It must rise above the roof at least 3 0 9m from the...

Страница 12: ...same manufacturer and install the ceiling support package or wall pass through and T section package firestops where needed insulation shield roof flashing chimney cap etc Maintain proper clearance t...

Страница 13: ...ssociation NFPA by having it inspected by a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the stove is installed...

Страница 14: ...him ney connector and a minimum 24 gage ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152 4 mm separation area containin...

Страница 15: ...cur whether or not there is combustion present 2 Existing fuel fired equipment in the house such as fireplaces or other heating appliances smell do not operate properly suffer smoke roll out when open...

Страница 16: ...f drying This point cannot be over stressed the vast majority of the problems related to the operation of a wood stove is caused by the fact that the wood used was too damp or has dried in poor condit...

Страница 17: ...chamber When you have achieved a good bed of hot embers we recommend the following burn procedures HEATING Controlled combustion is the most efficient technique for wood heating because it enables yo...

Страница 18: ...ture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote mak...

Страница 19: ...rd properly installed GLASS Inspect and clean the glass regularly in order to detect any cracks If you spot one turn the stove off imme diately Do not abuse the glass door by striking or slamming shut...

Страница 20: ...20 Ussc REPAIR PARTS 7 8 9 5 6 4 1 3 2 Feed Door Assembly 26 22 23 25 24 35 36 34 33 37 38 33 32 31 2 5 6 9 10 8 7 18 17 27 29 28 21 19 20 11 12 13 14 15 16 1 4 30 3...

Страница 21: ...5 16 18 x 3 4 Bolt 1 16 83338 5 16 18 Lock Nut 1 17 69660 Assembly Door_Large Rectangle 1 18 891135 Handle Spring LG Nickel 1 19 892020 Plate Hearth 1 20 891929 Rod Damper 1 21 891331 Spring Handle Br...

Страница 22: ...22 Ussc NOTES...

Страница 23: ...Ussc 23 NOTES...

Страница 24: ...NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMA TION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESCRIPTION 3 THE MODEL NU...

Отзывы: