Series 70

Servo NXT - EtherNet/IP

Installation, Operation and Maintenance Manual

4.2 Power Connections 
4.2.1 Input Power 

Due to the power requirements of large electric 
actuators, the Servo NXT EIP has a dedicated 
power input separate from the EtherNet/IP 
network cabling. This power input energizes not 
only the Servo NXT EIP, but also the actuator 
motor used to position the valve. 

Power provided to the Servo NXT EIP should be 
within 10% of the voltage listed for the actuator. 
For example, a 24VAC actuator should have 
power provided that has a voltage within 21.6 
and 26.4VAC after voltage drops of the cabling. 
Additionally, the power supply should be capable 
of sourcing 5A per actuator, since the actuator is 
capable of drawing large currents on startup. 

Note: 

24VAC actuators should have a dedicated 

100VA transformer for each actuator

4.2.2 Heater (optional)

The S70 has the option of having a cartridge 
heater installed at the factory. These 2 terminals 
provide a connection point for this heater, 
providing fused power to the heater from the 
input power terminals.

4.2.3 Motor

The S70 actuator is driven by either a split 
capacitor induction motor (120VAC or 230VAC 
operation) or a brushed DC motor (24VAC or 
24VDC operation). The Servo NXT EIP provides 
power to the motor to operate the actuator 
and position the valve based on the command 
position provided by the scanner. 

4.3 Factory Connections

One large terminal strip is provided on the 
Servo NXT EIP for connections switches and 
potentiometer internal to the actuator. These 
connections are generally made at the factory 
and should not require adjustment in the field. 

4.3.1 Limit Switches

The switches attached to this terminal strip have 
been set at the factory to be engaged when 
the limits of travel have been reached, in other 
words, when the fully open and fully close 
positions have been reached. These switches 
prevent the Servo NXT EIP from operating the 
actuator to a point where the gearing could 
bind up and become damaged. These switches 
are engaged by a cam shaft coupled to the 

output gear of the actuator, and the cams on 
the cam shaft should be adjusted to ensure the 
limit switches are engaged before any other 
mechanical limits are reached. 

The Servo NXT EIP provides a logic level voltage 
at the Open (LO) and Close (LC) terminals of 
this connection. Once one of the travel limit 
switches is engaged, the switch at the applicable 
connection will engage and pull this pin to 0V, 
signaling the Servo NXT EIP to end operation.

For proper operation, both travel limit switches 
should not be engaged at the same time. This 
would prevent the Servo NXT EIP from operating 
the actuator, and results in a limit switch fault.

4.3.2 Torque Switches (optional)

If the torque present on the output of the 
actuator goes outside the rated torque listed 
for the unit, then the actuator gearing could be 
damaged. These switches detect the presence of 
high torque on the output gear, and if activated, 
put the Servo NXT EIP into a fault state. This 
fault state prevents further operation until the 
torque is reduced. 

The Servo NXT provides a logic level voltage at 
the Open (TO) and Close (TC) terminals of this 
connection. If the actuator torque increases 
above the rated torque, the switch at the 
applicable connection will pull this pin to 0V, 
signaling the Servo NXT to enter a torque switch 
fault.

4.3.3 Handwheel Switch

The S70 actuator comes with an external 
handwheel that can be pulled out to allow 
for the valve to be positioned manually. If the 
handwheel is pulled out or engaged, then a 
switch is activated in the actuator, putting the 
Servo NXT EIP into a fault state. This fault state is 
active until the handwheel is pushed back in or 
disengaged. 

The Servo NXT EIP provides a logic level voltage 
at the HW terminal of this connection. If the 
handwheel is engaged (pulled out), this pin will 
get pulled to 0V, signaling the Servo NXT EIP and 
resulting in a handwheel fault.

Содержание Series 70

Страница 1: ...ETHERNET IP Installation Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY BRAY COM Network Status Mac ID 125K 250K Baud Rate Reprogram Open Close Controller Status Autocal Begin Autocali...

Страница 2: ...FOR MORE INFORMATION ON THIS PRODUCT AND OTHER BRAY PRODUCTS PLEASE VISIT OUR WEBSITE www bray com...

Страница 3: ...4 2 Power Connections 6 4 2 1 Input Power 6 4 2 2 Heater optional 6 4 2 3 Motor 6 4 3 Factory Connections 6 4 3 1 Limit Switches 6 4 3 2 Torque Switches optional 6 4 3 3 Handwheel Switch 6 4 3 4 Contr...

Страница 4: ...tch 10 4 5 5 Enter Switch 10 5 0 EtherNet IP Interface 10 5 1 EtherNet IP Conformance 10 5 2 Scanner Configuration 10 5 3 Address Assignment 10 5 4 Establish Connection 11 5 4 1 Input Assembly Data 12...

Страница 5: ...0 Servo NXT EtherNet IP to establish and maintain the desired process setpoint 2 1 Definition of Terms Servo NXT EIP Bray EtherNet IP based controller primarily intended for use in the Series 70 elect...

Страница 6: ...This mode of operation prevents remote operation of the Servo NXT EIP Once exiting Manual Mode the unit will return to Remote Mode 3 1 4 Autocalibration Mode The Servo NXT EIP uses an automated calibr...

Страница 7: ...Bray logo Red Fault LEDs Limit Switch fault Handwheel fault Torque fault Feedback fault White Autocalibration LED White Manual Mode LED User switches Autocalibration switch Manual Mode switch Up arro...

Страница 8: ...These switches prevent the Servo NXT EIP from operating the actuator to a point where the gearing could bind up and become damaged These switches are engaged by a cam shaft coupled to the output gear...

Страница 9: ...4 3 4 Control Box optional Connections for the local control station if present The local control station allows for local operation of the actuator putting the Servo NXT EIP into Local Mode and over...

Страница 10: ...wner connection shall transition to steady green when any subsequent Exclusive Owner connection is established Devices that support multiple Exclusive Owner connections shall retain the O T connection...

Страница 11: ...and the other switch has a wire disconnected then this fault will also occur 4 4 7 2 Handwheel Fault This red LED is on if a handwheel fault is active This occurs if the handwheel is detected to be in...

Страница 12: ...gnificantly more detail on the concerns and requirements for successfully establishing and managing a functional EtherNet IP network This list is not exhaustive and there are many more references avai...

Страница 13: ...ges should be configured based on the Connection Manager attributes defined in the EDS file The EDS file provides limits for implicit messaging to ensure the device maintains reliable generation of da...

Страница 14: ...edback position positive values only 0 20 Stroke Time REAL 32 Time in seconds the last full stroke took to complete positive values only 0 24 Motor Operating Time REAL 32 Time in hours that the motor...

Страница 15: ...ating in the open direction 6 Autocalibration Running BOOL 1 Set high when actuator is running through the calibration routine 7 PST Running BOOL 1 Set high when actuator is running through the partia...

Страница 16: ...e actuator attempts to operate a load outside the operational torque limits 3 Motor Stall Fault BOOL 1 Dynamic Fault Set high in the event of motor stall no motor movement detected 5 Autocalibration F...

Страница 17: ...BOOL 1 Toggle Bit Change bit state to operate the actuator to PST offset position to test device operability 2 4 Partial Stroke Test Stop BOOL 1 Toggle Bit Change bit state to cancel an ongoing partia...

Страница 18: ...t Open Speed REAL 32 Percent of max speed the motor should run at in the open direction Range 10 100 Default 100 0 16 Open Speed Start Position REAL 32 Position where open speed limiting should begin...

Страница 19: ...L 1 When high inverts input feedback position range Default Low 1 Enable Actuator Speed Limiting BOOL 1 Set high to enable speed limiting for the range specified Default Low 2 Enable Torque Limiting B...

Страница 20: ...and set it to use the address set in memory 4 Establish that explicit messages can be exchanged with the Servo NXT EIP through the network scanner a Data received should align with the information co...

Страница 21: ...PC ABS Blend Mounting Screw Material Nylon Terminals Wire Gauge 26 16 AWG 0 13 1 31 mm2 Torque Limit 3 5 in lbs 15 6 N Voltage Limit 200 V Current Limit 5 A Switch Force 0 79 lbf 3 5 N Temperature Rat...

Страница 22: ...skestra e 25 47877 Willich Germany Tel 49 2154 8875 0 ENERGY Mining Oil Gas Power FGD Nuclear Power INDUSTRIAL Chemical Pulp Paper Textile Marine WATER Water Wastewater Ultra Pure Water Desalination I...

Отзывы: