can  be  assigned  to  either  alarm  >  or  <  condition,  by  a  corresponding 
parameter selection in this step: 
0 = < setpoint 
1 = > setpoint 

Starter condition of alarms 

A control  signal to the Starter input  (see diagram) throws  the alarm 
output to a programmable condition for  an adjustable period of time. 
This may be required for the starting period of a machine, specifically 
if monitored for low speed alarm. 
Parameter 0 sets output to > setpoint during starter phase, 
parameter 1 sets output to < setpoint during starter phase, 

Step P04.04 

Alarm output during starter phase 

Starter time elapse 

The starter time elapse is adjusted in program step P04.05 with range 
000...999 sec.                       

Step P04.05 

starter time period 

Relay output SP1 assigned to setpoint SP1 or to reverse alarm SP2 

The  relay  SP1  can  be  assigned  either  to  the  setpoint  SP1  or  to  the 
reverse alarm SP2. If assigned to SP2, relay SP1 has identical function 
as relay SP2.  
Assignment is adjusted in step P04.06: 
Parameter 0 = relay SP1 assigned to setpoint SP1 
Parameter 1 = relay SP1 assigned to reverse alarm SP2 

Step P04.06 

assignment of relay output SP2  

Program Range P05 

Not relevant 

Initial parameters 

The unit comes programmed to initial parameters, as  listed on page 4. 
In course  of the installation however, the specific adjustment to the 
application conditions is indispensable. 

initial parameters 

Содержание D124.1S2

Страница 1: ...ion Monitor Series D124 1S2 with analog output and setpoint alarm Instructions and Operation Manual valid for serial nos exceeding 211600 Contents page Specifications 2 Instructions for Use Short form...

Страница 2: ...U1M 20 40Vac dc version U2 85 265Vac dc version U2M 85 265Vac dc Consumption 5 W resp 5 VA Signal input matching speed direction sensors series A5S3 to other sources response level on off 7 volts 4 vo...

Страница 3: ...rmal operation the Analog Output and the Setpoints follow the input signal with the in step P00 03 programmed time The Display update rate additionally depends on step P02 01 After a sudden interrupt...

Страница 4: ...ondition 0 forw 1 rev 1 reverse 03 8 minimum no of reverse pulses to release reverse alarm 05 04 8 time period for reset of reverse pulse counter xxx seconds 010 sec 05 8 forced direction at zero spee...

Страница 5: ...relay control leads The ground terminal PE is internally separated from common zero but tied by a 100 k resistor to it EMI The unit complies with all relevant regulations as determined by the Policy...

Страница 6: ...it will become valid touched instead leaves the parameter at its previous value Leave the programming phase by again touching The display returns to process readings Programmable Parameters Group P00...

Страница 7: ...ined in a separate pro gram step P02 01 Step P00 03 minimum measuring time Group P01 xx Measurement Configuration Input Scaling Scaling defines the relation between the input signal frequency in terms...

Страница 8: ...d in step P00 03 the display may have its own up dating programmable in steps of 0 1 seconds up to 9 9 sec Set the parameter to the desired time sequence A recommended value is 0 3 sec Step P02 00 num...

Страница 9: ...r the display of the speed Step P04 00 setpoint SP1 Alarm Hysteresis The hysteresis is the margin between condition excess and no excess defined by its bandwidth and its position in reference to the s...

Страница 10: ...hase Starter time elapse The starter time elapse is adjusted in program step P04 05 with range 000 999 sec Step P04 05 starter time period Relay output SP1 assigned to setpoint SP1 or to reverse alarm...

Страница 11: ...l Display and keys reference control inputs high level 10 24volts vs ref or contact closure vs sensor supply Input section and sensor supply Sensor supply 100 k A2 A1 A3 1 2 38 screen not connected to...

Страница 12: ...ion of 4 1999 Operating temperature range for version M extended to 20 C to 65 C Supply voltage for version U1M 20 40Vac dc 6 2009 for serial nos exceeding 211500 Voltage output is obsolete Plug in te...

Отзывы: