HERMAL PROCESS EQUIPMENT SPECIALISTS
Additional programmable features of the controller are:-
a)
Two independent temperature sensing circuits
b)
Two independent liquid level sensing circuits
c)
Variable temperature hysteresis
d)
High/low temperature alarm circuit (no volt or 110/250volt output)
e)
Manual energy saving function for overnight/weekend shutdown periods (not timer
operated)
f) No volt or 110/240v output relay to operate heater / pump
Please contact Braude if you require further information.
2.
Warning Notice
We strongly recommend that installation is carried out by a qualified electrician. This controller
is manufactured from top quality non-corrodable materials and should give trouble free service
provided it is installed, operated and maintained properly.
Warning-Mains Voltage
Always disconnect supply before removing cover or attempting connections.
The Tankmaster MP is supplied as standard with
Volt free
relays UNLESS specified at
the time of order.
Should the Tankmaster MP be ordered as a mains output voltage type the grey output
lead (marked with a red warning label and fitted with a protective cap) becomes live once
the mains supply lead is connected to 230/110VAC. Always connect output lead first.
The controller is rated at 5 amps, any heater or pump likely to draw more current should
be connected through a contactor as shown in the wiring diagrams Fig 3 or 4.
Note: Failure to connect the earth may result in a serious safety hazard.
Your Tankmaster controller is sealed to IP65 standard. If the cover is removed ensure
that the gasket is firmly seated in the locating groove before tightening the remaining
screws.
Caution The controller must be isolated from the electrical supply during installation.
3.
Mounting
Remove the clear plastic cover by undoing the 4 plastic screws at the corners. The controller
should be fixed to a suitable surface within reach of the probe leads using suitable screws
through the 4 fixing holes in the corner pillars. The unit should be positioned within easy reach
of the equipment to which it will be connected.