9

03/24999571

Technical datas

The power supplies and electrical control equipment are to be operatetd exclusively with the components authorised by 

the manufacturer.

Electrical properties

Rated operating voltage:    

 

24 V DC

Alarm indicator:   

 

 

LED red

Operating current at 30 V, quiescent:  

max. 120 μA

Operating current at 30 V, alarm:    

min. 19 to max. 22.5 mA

Permissible voltage range:  

 

18 to 30 V DC

Signal transmission: 

 

 

current rise

Remote indicator, short circuit proof:  

max. 5 mA

Mechanical properties

Dimensions: 

 

 

 

see pages 7

Weight:   

 

 

 

125 g

Installation and ambient conditions

Monitored area¹:   

 

 

max. 150 m²

Mounting height¹:  

 

 

max. 16 m

Permissible air speeds: 

 

 

max. 20 m/s

Ambient temperature: 

 

 

-25 °C to +60 °C

Ambient conditions for moisture (constant, 

without condensation) at ≤ 34 °C:   

10 - 95 %, relative humidity

Ambient conditions for moisture (constant, 

without condensation) at > 34 °C:   

max. 35 g/m³, min. 10 %, relative humidity

Authorisations and certifications

Standards: 

 

 

 

EN 54-7

Degree of protection IEC 529:  

 

IP 44

Approval VdS:    

 

 

G 207123

Approval CPD:   

 

 

0786-CPD-20330

Material

Housing:  

 

 

 

ABS/PC

Colour:    

 

 

 

electro white

Trouble-free and safe operation is only warranted when used in conjunction with appropriate manufacturers control unit. 

Request a technical conformity declaration when using drives from other manufacturers.

 

 

 

¹ Values dependent on the ceiling design (height, inclination) according to project guidelines that are specific to each 

country.