PSI BOX Reference
Mode 7 Overview
Figure 7-1 The Default Mode 7 Configuration.
________________________________________
DEFAULT IEEE DEVICE NUMBER
=AS SET BY DIP SWITCHES
DEFAULT IEEE SECONDARY ADDRESS
=NONE
TIME OUT VALUE
=10 (1 second)
PSI BOX MY LISTEN ADDRESS
=00
PSI BOX MY SECONDARY ADDRESS
=NONE
PSI BOX MY TALK ADDRESS
=00
END OF INPUT TERMINATION (EOS=)
=EOI ASSERTED BY DEVICE
END OF OUTPUT METHOD (END=13)
=EOI SENT WITH <CR>
RS232 PORT ECHO STATE
=OFF. ECHO=OFF
EMERGENCY RESET CHARACTER
=@. DECIMAL 64
INTERFACE CLEAR LINE IFC
=PULSE TRUE>100 micro sec
REMOTE ENABLE LINE REN
=ASSERTED TRUE
ATTENTION LINE ATN
=ASSERTED TRUE C-A-C
Data Pass Through Mode.
_______________________
By default any data, that does not start with the BUS
command sequence, is treated as data to passed straight though
the PSI BOX to the current IEEE device.
At the start of the data stream the PSI BOX sends the
current device LISTEN address. Then the current secondary
address, if any. Then the data received from the RS232 host
computer is sent byte by byte. The EOI will be set true
concurrently with a data byte and will be followed by the UNL
command according to the End Of Sequence method specified
by the EOS= command.
Any data that starts with a <Carriage Return> or <Line
Feed> character will be buffered until it has been checked for
the BUS command sequence. Thus the data sequence:-
<CR> BUFFET
will have the three bytes <CR> BU stored by the PSI BOX until
the F character arrives, as this point the PSI BOX determines
that <CR> BUS has not been received from the host RS232
computer. Therefore the PSI BOX sends <CR>BUF to the
current device on the IEEE bus and the later characters FET are
sent as soon as they have been received.