2.7 Inputs
INPUTS 11
*
CHANGE INPUT. 001
INPUT 01
▲
STATUS 001
EXCLUDED
Status:
(Default:
EXCLUDED
)
F
S
A
EXCLUDED
Inputs are excluded when they are unused.
INSERTED
Inputs are inserted when they are used in the system.
TEST
An input is a test when you want to monitor the behaviour of
an input via the events log without triggering any alarms nor
telephone calls.
Example:
following installation of a system the input continues to revert
to alarm without any apparent reason. By placing it into test mode you
can continue to monitor any alarms (though the events log) without
generating any alarms.
▼
*
▼ ▲
▼ ▲
+ -
TYPE 001
IMMEDIATE
Type:
(Default:
IMMEDIATE
)
F
S
A
The type defines the input’s functional characteristics.
IMMEDIATE
This is a classic intruder-proof input, active when the control
unit is up
and inactive when the control unit is off. If
unbalanced it triggers a general alarm.
Example:
Installing a magnetic radio contact onto a window.
SERVICE
It is active with control unit engaged or disengaged . It is not
registered as an an alarm input, but only to be monitored via
key pad or to activate outputs of calls regardless of control
unit status. It is recorded in the event log.
BLCK PRG.IN.
If closed, it enables the time schedule function, excluding it if
open.
FAULT
It remains enabled with control unit engaged and disengaged.
The Fault Led light up for any malfunctions and breakdown
output is enabled. The system displays the ANOMALY message
followed by the input description.
DELAYED 01
It is active only when the control unit is on. If unbalanced,
it
triggers entrance time 1, during which a valid code must be
entered to disengage the control unit. During this time the
buzzer will sound continuously. If the control unit is not
disengaged the general alarm will be triggered.
Example:
input associated with an input port.
DELAYED 02
As DELAYED 1, but with entrance time 2.
24 HRS
This instantaneous input is active either when the control unit is
on
or off. Unbalancing a 24 hour input triggers a general alarm.
Example:
input associated with external siren tamper.
TECHNIC
This instantaneous input is active either when the control unit
is on
or off. Unbalancing a technical input activates the
TECHNICAL ALARM-defined output, sounding a continuous
buzz (for the duration of the technical alarm) and the switching
on of the alarm LED-light on the keypads.
Example:
an input associated with a fire or gas detection sensor.
PATH
Instantaneous input with control unit on. It performs
like a
delayed input if a control unit DELAYED input triggers the
entrance time. And performs like an instantaneous input in all
other situations.
Example:
input associated with an infrared detector placed in front of a
delayed-type input. If users open the door, this triggers the entrance time
and the detector also performs in the same way; whereas if an intruder
break in through a window, the sensor performs instantaneously.
+ -
▼ ▲