UNI EN ISO 9001-2015 n° 9115.BRMO
USER MANUAL
“Aquarius Plus”
File name
Date
Page
Code
PUT9I001 PUT9I1K5
DF19009A
05/04/19
31
di
32
PUT9I002
PUT9I003
MD03006C
- All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
performance
Line mode
Full load≥86%
Full load≥88%
Battery mode
Full load≥84%
ECO
Full load≥94%
Output Voltage Distortion
≤3% (100% linear load)
≤5% (100% non-linear load)
Battery
Battery voltage
24VDC
24VDC
48VDC
48VDC
72VDC
72VDC
Battery number
2
4
6
Tipo batterie
12V/7AH airtight lead (for standard UPS only)
Autonomy
Full load 4 minutes. For standard UPS only.
Charge current (A)
1
4
1
4
1
4
10 Environmental conditions
Template
1KVA-3KVA
Temperature
0℃
~
40℃
Humidity
0-95% without condensation
Altitude
1500 m
Storage temperature
-25℃ - 55℃
11 Mechanical specifications Rack mounting 19”
Model
Dimension W*D*H (mm)
Net / Gross Weight (kg)
1KVAS
440*430*86,5
15,7
1KVAH
2KVAS
440*572*86,5
26,3
2KVAH
3KVAS
440*736*86,5
33
3KVAH
12 Communication ports
12.1
RS232
On the UPS there is a RS232 DB9 connector. To connect the unit to a PC it is necessary to have a
standard serial cable. The following table shows how to wire the serial cable: