4 Installation
4.1
Unpacking and inspection
1. Unpack the UPS and check that there is no damage caused during transport. If any parts
are damaged or missing, do not start the appliance and inform the carrier and report it to
the service center.
2. Check the attachment (please refer to the Appendix 1 table).
4.2
Note
Please place the UPS in a clean environment and avoid vibration, dust, moisture, flammable
and corrosive gases and liquids.
The ambient temperature must be in a range between 0 ° C ~ 40 ° C. If the ambient
temperature exceeds 40 ° C, the nominal power decreases by 12% as the ambient
temperature increases.
The maximum working temperature cannot be higher than 50 ° C.
The UPS must be placed in a sufficiently ventilated place.
4.3
Mounting the brackets for the Tower-mounted installation
The plastic brackets must be mounted as shown in illustration 5 and 6
As for the mounting of the brackets for the different UPS models, it is necessary to know that the
1KVA unit needs a space of 1 unit, so it is sufficient to follow the illustrations 5 and 6. For the other
models the space between the brackets it is 2 units and for a correct assembly the other
illustrations in this paragraph must also be considered.
Illustration 4: mounting brackets-1
Illustration 5: mounting brackets-2