Fan Stage(s) Test ON or OFF 

This test turns on all fan stages and commands all dampers 
to open. Press 

SELECT

 to test or 

NEXT

 to advance to the next test.

Operation

6

The Expandable Zone Panel has LED’s and a built-in display 
to tell the installer and the system owner the current operating 
mode of the panel. Refer to the figure below and the following 
descriptions of the panel LED’s for operation information.

Damper Control Test PO or PC 

This test powers all dampers open or closed. Press 

SELECT

 to test 

or 

NEXT

 to advance to return to first test.

 LED 

COLOR 

INDICATION

  Panel Status LED

  

  Panel Power 

Green 

Flashing Green When Normal

  Equipment LED’s

  

   Rh 

Red 

24 VAC at equipment Rh Terminal

   Rc 

Red 

24 VAC at equipment Rc Terminal

   Y1 

Yellow 

First Stage Compressor Call Active

   Y2 

Yellow 

Second Stage Compressor Call Active

   G 

Green 

First Stage Fan Call Active

   G2 

Green 

Second Stage Fan Call Active

   W1/E/AX1 

White 

W1 or E or AX1 Call Active

   W2/AX2 

White 

W2 or AX2 Call Active

   O/B/W3 

Green 

Reversing Valve Active or W3

   L 

Yellow 

Input from Equipment Check is Active

14

(continued)

Содержание 140404

Страница 1: ...he entire panel before applying transformer power This panel is designed for professional installation and is to be installed and configured as described in this manual Any other use is not recommende...

Страница 2: ...lectronic self resetting current limiting for panel power and damper zones Configuration Conventional and Heat Pump equipment up to 4 Heating Stages and 2 Cooling Stages Maximum Zones 4 Zones Main Pan...

Страница 3: ...aster installations Figure 2 3 EM HEAT R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 1 PO COMM PC DAMPER ZONE 1 R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 2 DAMPER ZONE 2 PO COMM...

Страница 4: ...op of wiring terminal and gently pull out wire s EM HEAT R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 1 PO COMM PC DAMPER ZONE 1 R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 2 DAMP...

Страница 5: ...PUT 2nd Stage Compressor G 1 OUTPUT 1st Stage Fan Control G2 1 OUTPUT 2nd Stage Fan Control W1 E AX1 1 OUTPUT W1 1st Stage Conventional Heat E Emergency Heat AX1 1st Stage Auxiliary Heat W2 AX2 1 OUTP...

Страница 6: ...ne Panel 2 Wire Damper PO C PC PO COM PC Zone Panel 3 Wire Damper Thermostat Wiring 3 2 Install the system thermostats using the instructions provided by the manufacturer Connect the thermostats to th...

Страница 7: ...eat Call G Fan Call C 24 VAC Transformer Common Note 1 3 HEAT 2 COOL With Auxiliary Heat R 24 VAC Power O B Changeover Valve Note 2 L Optional System Fault Monitor AX1 Auxiliary Heat Relay 3rd Stage H...

Страница 8: ...panel as shown For a single stage heating and cooling system the 2nd and 3rd stage connections are not used For a system using a dual transformer remove jumper Rc to Rh see Figure 3 page 4 Make sure...

Страница 9: ...Power Heating Transformer Rc Connected to Rh with Jumper O B Changeover Valve Note 4 L Optional System Fault Monitor W2 Auxiliary Heat Relay 2nd Stage Heating Note 5 Y1 Compressor Call Stage 1 1st St...

Страница 10: ...ms you will need to make configuration changes described in this section To start configuration 1 Press SETUP and hold for 3 seconds 10 2 The panel backlight will turn on and the display will change 3...

Страница 11: ...trol REV VAL O O Select for cool active reversing valve B Select for heat active reversing valve Note 7 6 Auxiliary Stage COMP LOC OFF OFF Select for Compressor runs with Auxiliary Heat Call Compresso...

Страница 12: ...ted 17 Second Stage Fan G2 ZONES 2 2 of Select the number of zones that must call before the zones second stage fan will turn on 18 Priority Zone PRIORTY 1 OFF Select to have opposite calls answered i...

Страница 13: ...municating properly the display will show the zone number and OK If the zone is not communicating properly the display will show Address Invalid or Duplicate Address See Error Conditions section 7 for...

Страница 14: ...PC This test powers all dampers open or closed Press SELECT to test or NEXT to advance to return to first test LED COLOR INDICATION Panel Status LED Panel Power Green Flashing Green When Normal Equip...

Страница 15: ...D s the expandable zone panel has a full function built in backlit display panel that provides information on the current operations of the zone panel When the expandable zone panel is running in norm...

Страница 16: ...o cooling calls will be answered if emergency heat is switched on To select Emergency Heat from the main panel 1 Press and release the EM HEAT button located below the main display 2 The display will...

Страница 17: ...un Delay HI Limit Displayed when the Plenum Temperature is exceeded during equipment heating operation All heating stages will be turned off and the fan will be turned on until the plenum temperature...

Страница 18: ...an expansion panel This message will appear when an expander is powered up and wired to the communication terminals To locate the expander panel with the invalid address view the expander panel status...

Страница 19: ...anel display 4 If new zones do not appear check wiring and ensure expansion zones have power 5 Press HOLD FOR EXIT for 3 seconds to complete adding zones The expansion zones may be wired to either the...

Страница 20: ...es 5 6 Expander Panel Zones 7 8 Expander Panel As Needed Daisy Chain All Zones Located at Main Panel Star Wiring All Zones Located at Main Panel Main Panel Expander Panel Zones 7 8 Expander Panel Zone...

Страница 21: ...Panel Zones 7 8 500 Ft Maximum 21 Main Panel Expander Panel Zones 5 6 Expander Panel As Needed 500 Ft Maximum Expander Panel As Needed Expander Panel As Needed Daisy Chain Zones Located Remote to Mai...

Страница 22: ...opy of this warranty Visit us online www braeburnonline com warranty Phone us 866 268 5599 Write us Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 5YEAR WARRANTY LIMITED Braeburn Systems...

Отзывы: