background image

8

S19-324D1

 Installation

6/11/2020 

Bradley • 

215-1848 Rev. G: ECO 20-05-028

Servicing of Lights

S19-324D1 LED Arrays (Type 4X)

A

De-power the control box by 
observing standard lock-out tag-out 
practices.

B

Unscrew the light needing 
replacement from the pendant 
mount. Refer to light manufacturer's 
instructions for servicing. Replace 
with appropriate LED array color light 
fixture.

C

Once light is replaced, re-attach 
repaired light to pendant mount.

D

Check that the signaling station is 
functioning properly once the power 
is restored by activating the fixture 
attached to the signaling station.

Troubleshooting

Problem

Cause

Solution

The signal light and horn (if 

applicable) does not operate 

when water flows.

No power to the signal station.

Check that the circuit breaker or fuse is supplying power to the 

signal station

Component failure.

Check the two 3 Amp 24VDC fuses on the print circuit board in 

the signal station enclosure.

No input power.

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure.

Water flowing in wrong 

direction for flow switch body.

Verify that the direction of the water flow corresponds to the arrow 

on the flow switch body.

Insufficient water flow.

Check that water flow is sufficient (2.4 gallons per minute is 

required).

Installation error.

Check all electrical connections, including power supply at the 

quick-connect cable, from the signal station to the flow switch.

Horn sounds and signal light 

does not light.

Component failure.

Check light connections and filament in the light.

Area light does not operate.

No power to the signal station.

Check that the circuit breaker or fuse is supplying power to the 

signal station

Component failure.

Check the two 3 Amp 24VDC fuses on the print circuit board in the 

signal station enclosure.

No input power.

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure.

Component failure.

Check light connections and filament in the light.

Beacon light does not 

operate. (This light should 

turn off when the signal light 

turns on and back on when 

the signal light turns off.)

Fixture in use.

Make sure that the flow switch contacts are open (horn and/or 

signal light are not ON).

Power disconnected in error.

Check that the circuit breaker or fuse is supplying power to the 

signal station.

Component failure.

Check the 3 Amp 24VDC fuses on the print circuit board in the 

signal station enclosure.

No input power.

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure.

Component failure.

Check light connections and filament in the light.

Содержание S19-324D1

Страница 1: ...n Proof Emergency Signaling System Table of Contents Pre Installation Information 2 3 Assembly of Components 4 Install the Flow Switch and Mount Signaling Assembly 5 Connect Signaling Assembly to Flow...

Страница 2: ...eginning installation and after installation is complete Test the unit for leaks and adequate water flow Main water supply should be ON at all times unless system is being serviced Provisions shall be...

Страница 3: ...require a minimum of 30 PSI 0 21MPa flowing pressure Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing fluid supply is present and any sediment buil...

Страница 4: ...Sensor Body Brass Adapter and Tee 2 7 8 73mm 1 5 8 41mm NEMA 4X Junction Box and Cover Electrical Quick Disconnect Male 3 13 16 97mm 5 5 16 135mm Red Blue Black Remote Sensing 13 1 8 334mm System is...

Страница 5: ...m may be mounted directly to the drench shower piping using the supplied U bolts and nuts The signaling system can also be bolted to a flat surface such as a wall hardware for this type of installatio...

Страница 6: ...clockwise and sealing the control box The cable may be cut to any length required A Wire the flow switch to the control box with one of the provided cables and conduit hubs supplied per the wiring sch...

Страница 7: ...ill automatically reset the silence feature The signaling system is designed to work properly even if both the eyewash and drench shower are used simultaneously The signaling system will continue to o...

Страница 8: ...that water flow is sufficient 2 4 gallons per minute is required Installation error Check all electrical connections including power supply at the quick connect cable from the signal station to the fl...

Страница 9: ...9 324D1 Bradley 215 1848 Rev G ECO 20 05 028 6 11 2020 S19 324D1 Service Parts 30 32 31 32 33 34 37 34 38 76 84 62 34 33 34 20 38 77 63 61 41 43 32 33 34 39 36 34 37 34 36 33 34 2 1 60 64 65 38 84 36...

Страница 10: ...Surface Mount 60 140 1157 1 Plate PM Pipe Mount 60 S70 176 1 Mounting Plate Heat Trace Item Part No Qty Description 61 160 514 5 Screw 3 8 16 x 1 0 BTNCA 62 161 157 5 Nut 3 8 16 Hex Jam 63 140 1158 1...

Отзывы: