Installation
MF2904/IR
Bradley Corporation
• 215-752 Rev. U; EN 08-023
9/25/08
7
10
Set Temperature
A
Check the temperature when
approximately 1.0 GPM water fl ow
is reached and adjust if necessary
(the range of the valve is 95°F–
115°F (35°C–43°C). To adjust the
temperature:
• Loosen temperature locking nut with
wrench.
• Using a blade screwdriver, turn the
adjustment stem counterclockwise
to increase the temperature
or clockwise to decrease the
temperature.
• Once desired temperature is
reached, tighten nut to prevent
temperature change.
SOLENOID ASSEMBLY
VERNATHERN™ TMV
The Vernatherm™ valve is NOT factory-preset. Upon installation, the valve temperature must be checked and
adjusted to ensure delivery of safe water temperature. Water in excess of 110°F (43ºC) may cause scalding.
A
Check to make sure both stop/check valves
are fully open (see Figure 2).
B
Turn on the main water supply to the Tri-
Fount® and check for leaking.
C
Turn on the electrical power and pass your
hand in front of each sensor until air is
purged from the lines.
9
Check Operation