Installation
10
2/1/07
Bradley Corporation • 215-576 Rev. X; EN 06-915-C
TEMPERATURE
ADJU
S
TMENT
S
TEM
TEMPERATURE
LOCKING
NUT
7
Check operation
8
Completing Installation
CHECK TO MAKE SURE BOTH STOP/CHECK VALVES ARE FULLY
OPEN (SEE PAGE 7).
A
INSTALL THE OPTIONAL SOAP SYSTEM FOLLOWING THE
INSTALLATION INSTRUCTIONS OUTLINED IN MANUAL
PROVIDED WITH THE SOAP SYSTEM.
A
TO INSTALL THE FRONT PANEL, SLIP SLOT IN THE BOTTOM OF
THE FRONT PEDESTAL PANEL OVER THE LIP ON THE LOWER
BRACKET.
A
SECURE THE PANEL TO THE UPPER BRACKET WITH THE
ATTACHED SCREW.
B
PUSH OPERATING PUSH BUTTONS UNTIL AIR IS PURGED FROM
LINES.
C
CHECK THE TEMPERATURE WHEN APPROXIMATELY 1.0 GPM
WATER FLOW IS REACHED AND ADJUST IF NECESSARY (THE
RANGE OF THE VALVE IS 95°F–115°F (35°C–43°C). TO ADJUST
THE TEMPERATURE, FOLLOW THE PROCEDURE BELOW:
• LOOSEN TEMPERATURE LOCKING NUT WITH WRENCH.
• USING A BLADE SCREWDRIVER, TURN THE ADJUSTMENT
STEM COUNTERCLOCKWISE TO INCREASE THE
TEMPERATURE OR CLOCKWISE TO DECREASE THE
TEMPERATURE.
• ONCE DESIRED TEMPERATURE IS REACHED, TIGHTEN NUT TO
PREVENT TEMPERATURE CHANGE.
D
IMPORTANT:
The Vernatherm™ valve is NOT factory-preset. Upon
installation, the valve temperature must be checked and
adjusted to ensure delivery of safe water temperature. Water
in excess of 110°F (43ºC) may cause scalding.
OPTIONAL: Install soap system
TURN ON THE MAIN WATER SUPPLY TO THE QUADRA-FOUNT™
AND CHECK FOR LEAKING.
B