background image

 

 

28

 

Installation (Combustion Air Supply) continued-

 

 
All Air From Inside the Building:

 The confined space must be provided with 

two permanent openings communicating directly with an additional room(s) of 
sufficient volume so that the combined volume of all spaces meets the criteria 
for an unconfined space. The total input of all gas utilization equipment installed 
in the combined space must be considered in making this determination. Each 
opening must have a minimum free area of 1 square inch per 1000 BTU 

(6.5 

cm

2

/0.29 kw)

 per hour of the total input rating of all gas utilization equipment in 

the confined space, but not less than 100 square inches (645 cm

2

). One 

opening must be within 12 inches 

(31 cm)

 of the top and one within 12 inches 

(31 cm)

 of the bottom of the enclosure. 

 

All Air From Outdoors

: The confined space must be provided with two 

permanent openings, one commencing within 12 inches 

(31 cm)

 of the top and 

one commencing within 12 inches 

(31 cm)

 from the bottom of the enclosure. 

The openings must communicate directly, or by ducts, with the outdoors or 
spaces (crawl or attic) that freely communicate with the outdoors. 
 
1.  When directly communicating with the outdoors, each opening must have a 

minimum free area of 1 square inch per 4000 BTU 

(6.5 cm

2

/1.2 kw)

 per 

hour of total input rating of all equipment in the enclosure. 

2.  When communicating with the outdoors through vertical ducts, each 

opening must have a minimum free area of 1 square inch per 4000 BTU 

(6.5 cm

2

/1.2 kw)

 per hour of total input rating of all equipment in the 

enclosure. 

3.  When communicating with the outdoors through horizontal ducts, each 

opening must have a minimum free area of 1 square inch per 2000 BTU 

(6.5 cm

2

/0.6 kw)

 per hour of total input rating of all equipment in the 

enclosure. 

4.  When ducts are used, they must be of the same cross-sectional area as 

the free area of the openings to which they connect. The minimum 
dimension of rectangular air ducts must be not less than 3 inches 

(7.5 cm).

 

 

Specially Engineered Installations

 

The requirements noted under CONFINED SPACES above must not 
necessarily govern when special engineering, approved by the authority having 
jurisdiction, provides an adequate supply of air for combustion, ventilation, and 
dilution of flue gases. 

Содержание URG2PV50T6N

Страница 1: ...one Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas...

Страница 2: ...n the event of improper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the flammable vapors outsid...

Страница 3: ...2 L 60 Gal 227 1 L 19 Vent Pipe Preparation and Joining 25 Combustion Air Supply 27 Water Connections 29 Gas Connections 32 Electrical Connections 33 Wiring Diagram 34 GENERAL OPERATION 35 Lighting an...

Страница 4: ...r You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water See t...

Страница 5: ...dential garages must be installed and located or protected to avoid physical damage For other installations refer to local codes In the absence of local codes the water heater must be installed in com...

Страница 6: ...h little or no odor to reveal their presence NOTE DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR WI...

Страница 7: ...uate drain The piping must be at least 3 4 inch 1 9 cm in diameter and pitched for proper drainage It is recommended that a minimum clearance of four 4 inches 10 2 cm be provided on the side of the wa...

Страница 8: ...earances to combustibles for this water heater are zero 0 inch 0 cm from the sides and rear five 5 inches 12 7 cm from the front of the jacket zero 0 inch 0 cm from the vent connector and fifteen 15 i...

Страница 9: ...t 2 13 m M Clearance under a veranda porch deck or balcony 12 inches 30 cm b 1 In accordance with the current CAN CGA B149 Installation Codes 2 In accordance with the current ANSI Z223 1 Latest editio...

Страница 10: ...low noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the water heater s efficiency The acceptance of the venting system is dependent upon ful...

Страница 11: ...lue gas venting rated Class II 65 C Approved Primers and Cements For installations in the US only PVC and CPVC Primer ASTM F656 PVC Cement ASTM D 2564 CPVC Cement ASTM F493 ABS Primer and Cement ASTM...

Страница 12: ...supplied exhaust adapter with drain outlet mounts directly to the blower outlet and is secured with two hose clamps one to the blower and the other to the vent pipe Tubing is provided to drain any acc...

Страница 13: ...NT CONNECTOR LENGTHS FOR 3 7 6 cm DIAMETER VENT PIPE Terminating of Elbows Maximum straight Length ft m Minimum straight Length ft m 48 65 gal Through the Wall 1 55 16 8 2 6 Through the Wall 2 50 15 2...

Страница 14: ...tor is going to pass through the wall Use the proper cement to secure the 90 vent terminal provided with the water heater to the vent connector The distance between the edges of the 90 vent terminal a...

Страница 15: ...15 Venting Part I continued 4 V E N T IN S T AL L A TIO N 3 V E N T IN S T AL L A TIO N Figure 3...

Страница 16: ...local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code latest edition Figure 4 NOTE For installations requiring both horizontal and vertical runs th...

Страница 17: ...height greater than or equal to 12 30 5 cm above the ground or anticipated snow level the installation must be modified as shown below see Figure 5 Refer to Table 3 for maximum venting lengths using...

Страница 18: ...ALLATIONS Terminating Reduce 4 to 3 Reduce 10 1 cm to 7 6 cm of Elbows Max straight Length ft m Min straight Length ft m 48 65 gal 2 90 Elbows with 1 90 Elbow 1 160 48 8 10 3 1 2 90 Elbows with 1 90 E...

Страница 19: ...e venting distances allowed with 3 7 6 cm diameter vent pipe When venting with 3 7 6 cm vent pipe use a 3 7 6 cm to 2 5 1 cm reducer to exit through the building wall with 2 5 1 cm vent pipe Use the 2...

Страница 20: ...l 5 95 29 0 10 3 1 Through the Roof 0 120 36 6 15 4 6 Through the Roof 1 115 35 15 4 6 Through the Roof 2 110 33 5 15 4 6 Through the Roof 3 105 32 0 15 4 6 Through the Roof 4 100 30 5 15 4 6 NOTE Whe...

Страница 21: ...he 45 vent terminal and the exterior wall see Figure 7 must be at least 1 in 2 5 cm Use the proper cement and assembly procedures to secure the vent connector joints between the terminal and the blowe...

Страница 22: ...the necessary holes through the roof and ceiling and install the vent connector as shown in Figure 8 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1...

Страница 23: ...shown below see Figure 9 Refer to Table 7 for maximum venting lengths using 2 5 1 cm vent pipe or Table 8 for maximum lengths using 3 7 6 cm vent pipe 2 VENT INSTALLATION 3 VENT INSTALLATION Figure 9...

Страница 24: ...LLATIONS Terminating Reduce 3 to 2 Reduce 7 6 cm to 5 1 cm of Elbows Maximum Length ft m Minimum Length ft m 2 90 Elbows with Vent Terminal 1 100 30 5 10 3 1 2 90 Elbows with Vent Terminal 2 95 29 0 1...

Страница 25: ...applicator tools to ensure proper preparation and joining of pipe and fittings a Cutting Tools i A square cut must be achieved with a miter box saw or pipe cutter to ensure a proper mating with the f...

Страница 26: ...at around the end of the pipe 4 Joining a Joints should be made immediately after cement is applied b After fully inserting pipe into fitting socket hold joint together for about 15 to 20 seconds c Re...

Страница 27: ...le weather stripping heavily insulated caulked vapor barrier etc additional air may need to be provided using the methods described under CONFINED SPACES All Air From Outdoors or Specially Engineered...

Страница 28: ...ly or by ducts with the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each opening must have a minimum free area of 1 squa...

Страница 29: ...on DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this s...

Страница 30: ...relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief valve Ve...

Страница 31: ...scalds Water temperature over 125 F Feel water before bathing or before setting temperature are available showering Temperature limiting valves Review this instruction manual at water heater scalded A...

Страница 32: ...to the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive...

Страница 33: ...water heater and use the flexible cord provided Do not plug the line cord into a receptacle that can have its power supply interrupted by a switch that is used to turn on and off lights If wiring in...

Страница 34: ...34 Wiring Diagram Figure 10...

Страница 35: ...ter heater 3 Close the cold water supply shut off valve 4 Open the drain valve on the water heater by turning the stem counter clockwise The drain valve has threads on the end that will allow the conn...

Страница 36: ...36 Lighting and Shutdown instructions...

Страница 37: ...tleship Grey faceplate is approximately 180 F maximum set point Figure 11 DANGER Hotter water increases the risk of scald injury Scalding may occur within five 5 seconds at a temperature setting of 14...

Страница 38: ...adjustable air shutter See Figure 12 At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning properly The main burner flame should lig...

Страница 39: ...ames to determine that they are burning properly See Burner Flame Check section on page 38 If sooting or other burner anomalies are evident shut down the water heater by turning off the gas per the in...

Страница 40: ...omponents which are not exact duplicates of Thoroughly inspect and replace as needed burner inner door gasket and or sight window gasket any time burner inner door is removed or disturbed Replace wate...

Страница 41: ...installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will influence the time inter...

Страница 42: ...117 6 056 542 6 142 216 6 442 178 6 684 821 6 935 280 7 063 132 7 063 133 7 007 748 7 270 087 7 334 419 7 337 517 7 409 925 7 458 341 7 559 293 7 621 238 7 634 976 7 650 859 7 665 210 7 665 211 7 699...

Страница 43: ...use Pressure switch not working closed position 1 Pressure switch tubing kinked or blocked 2 Blocked pressure tap on switch 3 Faulty pressure switch Three flashes three second pause Pressure switch or...

Страница 44: ...ired false pilot flame sensed System auto resets Pilot valve stuck in open position Seven flashes three second pause Flammable vapor sensor fault detected see warning label 1 Flammable vapor present 2...

Страница 45: ...moving combustion air through the combustion system 5 The pressure switch closes 6 The control senses the closed pressure switch and starts the ignition process by providing a spark at the pilot elect...

Страница 46: ...tch 14 Pilot Assembly 4 Flue Baffle 15 Main Burner Orifice 5 Honeywell Gas Control Valve 16 Gas Feedline 6 Drain Valve 17 Flammable Vapors Sensor 7 Fiberglass Insulation not shown 18 Sensor Harness 8...

Страница 47: ...sed for boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a...

Страница 48: ...48 NOTES...

Отзывы: