background image

 

15 

Gas Connections 

 

The gas supply lines must meet all requirements of the National Fuel Gas 
Code (ANSI Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural 
Gas Installation Code (Latest Edition) or CAN/CGA B149.2 Propane 
Installation Code (Latest Edition). 
 
The minimum permissible gas supply pressure for the purpose of input 
adjustment is one (1.0) inch 

(0.25 kPa) 

water column above the operating 

manifold pressure. See the rating plate and gas valve for the manifold 
pressure and gas type. The maximum permissible gas supply pressure is 
fourteen (14.0) inches 

(3.5 kPa)

 water column for natural gas and liquefied 

petroleum gases/propane gas. 
 
1.  Connect this water heater only to the type of gas (Natural or Propane gas) 

as shown on the rating plate. Use clean black iron pipe or equivalent 
material approved by local codes and ordinances. (Dirt and scale from the 
pipe can enter the gas valve and cause it to malfunction). The inlet gas 
line must have a minimum length of three (3) inches 

(7.6 cm)

 drip leg 

(sediment trap) 

installed as close to the water heater’s gas valve as 

possible. A ground joint union must be installed as close to the water 
heater as possible in the gas supply line feeding the water heater to 
permit servicing of the water heater. Compounds used on the threaded 
joints of the gas piping must be resistant to the action of liquefied 
petroleum gases/propane gas. DO NOT apply pipe dope to the gas valve 
inlet and make certain that no pipe dope has become lodged in the inlet 
screen of the gas valve. Extreme care must be taken to ensure no pipe 
dope enters the gas valve. Avoid excessive torque when tightening the 
gas supply line to the gas valve. Excessive torque may result in cracking 
of the gas valve housing and could create a gas leak. When tightening 
gas supply line to L.P. control, it is recommended to hold the inlet body of 
the control securely with an adequate wrench. The suggested maximum 
torque is 31.5 ft. lbs

. (4.4 kg-m).

  

 

 
2.  This water heater and its gas connection must be leak tested before 

placing the water heater in operation. Check for gas leaks with a soap and 
water solution and a brush or a commercial leak detector fluid. 

NEVER 

USE A MATCH OR OPEN FLAME FOR TESTING! 

 

WARNING

 

The manufacturer of this water heater will not be liable for any damage 
or injury caused as a result of a cracked gas inlet as a result of 
excessive torque. 

Содержание RG275H10N

Страница 1: ...ne Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas s...

Страница 2: ...t the plumbing professional from whom your water heater was purchased For your records we recommend that you write the model serial number and installation date of your water heater in the maintenance...

Страница 3: ...will nullify the warranty This water heater has been designed and certified for the purpose of heating potable water The installation and use of this water heater for any purpose other than the heatin...

Страница 4: ...alternative anode s may be purchased from the supplier that installed this water heater This will minimize the odor while protecting the tank Additionally the water heater should be flushed with appro...

Страница 5: ...er where the floor is level and is easily accessible to gas and water supply lines DO NOT locate the water heater where water lines could be subjected to freezing temperatures Make sure the cold water...

Страница 6: ...vier than air and will remain at floor level if there is a leak Basements crawl spaces closets and areas below ground level will serve as pockets for accumulation of leaking gas Before lighting smell...

Страница 7: ...er for servicing and maintenance of the combination temperature and pressure relief valve To comply with NSF requirements this water heater is to be a Sealed to the floor with sealant in a smooth and...

Страница 8: ...iance is to be installed in an alcove or closet the entire floor must be covered by the panel increase distances to provide clearance for servicing If the rating plate or the label on the front of the...

Страница 9: ...and in good condition Check to make sure the venting system is properly sized for the water heater If the venting system was previously sized for another gas appliance that has been removed the venti...

Страница 10: ...nd flue tubes with possible damage to the water heater When an exhaust fan is installed in the same room with a water heater sufficient openings for air must be provided in the walls Undersized openin...

Страница 11: ...vided with two permanent openings one commencing within 12 inches 31cm of the top and one commencing within 12 inches 31cm from the bottom of the enclosure The openings must communicate directly or by...

Страница 12: ...sion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this...

Страница 13: ...ressure relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief v...

Страница 14: ...pplier Please consult with a plumbing professional WARNING Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time generally two...

Страница 15: ...d joint union must be installed as close to the water heater as possible in the gas supply line feeding the water heater to permit servicing of the water heater Compounds used on the threaded joints o...

Страница 16: ...test pressures in excess of 1 2 psi 3 5 kPa The water heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply syste...

Страница 17: ...ockwise to the OFF position 3 Shut off the gas supply to the water heater 4 Close the cold water supply shut off valve 5 Open the drain valve on the water heater by turning the knob counter clockwise...

Страница 18: ...18 Lighting and Shutdown Instructions White Rodgers Mechanical Gas Control...

Страница 19: ...19 Lighting and shutdown instructions White Rodgers Electronic Gas Control...

Страница 20: ...20 Lighting and Shutdown Instructions Honeywell Gas Controls...

Страница 21: ...21 THERMOSTAT ADJUSTMENT White Rodgers Mechanical Gas Control THERMOSTAT ADJUSTMENT White Rodgers Electronic Gas Control...

Страница 22: ...22 Thermostat Adjustment continued THERMOSTAT ADJUSTMENT Honeywell V1 Gas Control THERMOSTAT ADJUSTMENT Honeywell V2 Gas Control...

Страница 23: ...ck of the main burner and pilot flames should be made to determine if they are burning properly The main burner flame should light smoothly from the pilot DANGER Hotter water increases the risk of sca...

Страница 24: ...other flammable vapors and liquids 4 Bi annually conduct a visual check of the main and pilot burner flames to determine that they are burning properly See Burner Flame Check section WARNING Water he...

Страница 25: ...t nipple has been installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will influen...

Страница 26: ...d three second pause Thermostat calling for heat no faults Water heater operating normally LED on continuously Set point knob has been recently turned to the OFF position Set point know was recently t...

Страница 27: ...alve if five flash error persists Six flashes and three second pause Water leak detected by accessory module some models Excessive amount of water in drain pan water dam Seven flashes and three second...

Страница 28: ...eaches the setpoint temperature Two flashes and three second pause LED yellow Low thermopile voltage main burner not lit Check thermopile and its connections Check pilot flame Four flashes and three s...

Страница 29: ...calling for heat Water heater operating normally and is in heat cycle Solid ON Not an error Indicates that the control is in shutdown mode Set point knob was recently turned to OFF position Wait until...

Страница 30: ...5 682 666 5 761 379 5 943 984 5 954 492 5 988 117 6 056 542 6 142 216 6 442 178 6 684 821 6 935 280 7 063 132 7 063 133 7 007 748 7 270 087 7 334 419 7 337 517 7 409 925 7 458 341 7 559 293 7 621 238...

Страница 31: ...ight Side 4 Magnesium Anode 16 Hex Screw 8 15 x 3 4 5 Nipple 17 Outer Door 6 Flue Baffle Assembly 18 Combustion Chamber 7 Dip Tube Cold Water Inlet 19 Steel Burner 8 Escutcheon 20 Orifice 9 Temperatur...

Страница 32: ...or boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non p...

Отзывы: