Page 74
LAARS Heating Systems
8.D.8
External
The External Configuration Screen applies to the 0-10VDC (4-20mA) analog input BMS signal, and allows adjustment
of the following parameters:
To navigate to the External Configuration Screen, touch the External Icon on the Configuration Screen.
• Control Mode –
ONH & ONV models are on/off units, therefore, firing rate is always 100%. This parameter provides the
ability to either disable external control or configure the unit for Boiler Set Point or Firing Rate control mode.
•
Max Set Point –
When the Control Mode is set to Boiler Set Point, this is the maximum value that corresponds to
the Demand Max value.
•
Min Set Point –
When the Control Mode is set to Boiler Set Point, this is the minimum value that corresponds to the
Demand Min value.
• Demand Max –
This is the maximum value that corresponds to the control mode selected. With Firing Rate control
mode selected, this is the maximum rate at which the boiler/heater will run. The unit of this parameter is %, so if the
value of this parameter is 10000, or 100.00%, this equates to 10.0VDC or 20mA.
ONH & ONV models are on/off units,
therefore, firing rate is always 100%.
• Demand Min –
This is the minimum value that corresponds to the control mode selected. With Firing Rate control
mode selected, this is the minimum rate at which the boiler/heater will run. The unit of this parameter is %, so if the value
of this parameter is 2000, or 20.00%, this equates to 2.0VDC or 4.8mA.
ONH & ONV models are on/off units, therefore,
firing rate is always 100%.
• Demand On –
This is the threshold (VDC/mA) at which the input signal will initiate the selected control mode behavior. The
unit of this parameter is %, so if the value of this parameter is 1500, or 15.00%, this equates to 1.5VDC or 4.6mA.
•
Demand Off –
This is the threshold (VDC/mA) at which the input signal will deactivate the selected control mode behavior.
The unit of this parameter is %, so if the value of this parameter is 1000, or 10.00%, this equates to 1.0VDC or 4.4mA.
•
Input Type –
This parameter allows the user to select between voltage (0-10VDC) or current (4-20mA) input. Jumpers will
need to be configured accordingly.