Page 22
LAARS Heating Systems
Figure 2. Combustion Air and Vent through Roof
Category l and lll
84”
2”
Min. (Typ)
Multiple Vents
Window
2” Min. (Typ)
Multiple Air Intakes
Above expected snow line
213
36”
90
12”
OUTLET
INLET
12”
Terminals must be placed such that they are a Minimum of 12” above the
expected snow line. Local codes may have more specific requirements and
must be consulted. Refer to the NFPA 54 National Fuel Gas Code and your
local codes for all required clearances for venting.
Figure 3. Minimum Venting Distance for Single and Multiple Units.
Category lll only
Table 9.
Outdoor Terminals
Exhaust Vent
Inlet Air
Laars part number
Laars part number
1250
1500
1750
2000
2500
CA016700
CA0169000
CA016800
CA017000
Outdoor Terminals
Size
WARNING
The outdoor vent terminal gets hot. This unit must be
installed in such a way as to reduce the risk of burns
from contact with the vent terminal.
must be equipped with the inlet air and exhaust terminal
kits listed in Table 9. Additional instructions are supplied
with the terminal kits.
WARNING
If installing outdoors in a location that may
experience freezing temperatures, provisions must
be made to protect the unit from freeze damage.
Manufacturer does not warranty damage caused by
freezing temperatures. The unit must not operate if
the outdoor temperature drops below 5F (-15C)
2.E
Outdoor Installation
This unit can only be installed outdoors in areas that will
never experience freezing temperatures. Precautions
must be taken to prevent water in the heat exchanger and
condensate inside and outside of the boiler from freezing.
Damage due to freezing water or condensate is not
covered by the warranty. For units installed outdoors the
minimum outdoor operating temperature is 5F (-15C)
For proper operation in outdoor installations, the boiler
Содержание LAARS OmniTherm ONH1250