13
Venting (Part I) continued-
sure the vent pipe terminal elbow fitting is at least 1”
(2.5 cm)
away from the
edge of the wall.
TABLE 1 - VENT CONNECTOR LENGTHS
FOR 3”
(7.6 cm)
DIAMETER VENT PIPE
Terminating
# of Elbows
Maximum straight
Length
ft
(m)
Minimum
straight
Length
ft
(m)
48, 65 gal.
Through the Wall
1 55
(16.8)
2
(.6)
Through the Wall
2 50
(15.2)
2
(.6)
Through the Wall
3 45
(13.7)
2
(.6)
Through the Wall
4 40
(12.2)
2
(.6)
Through the Roof
0 60
(18.3)
7
(2.1)
Through the Roof
1 55
(16.8)
7
(2.1)
Through the Roof
2 50
(15.2)
7
(2.1)
Through the Roof
3 45
(13.7)
7
(2.1)
TABLE 2 -VENT CONNECTOR LENGTHS
FOR 4”
(10.2 cm)
DIAMETER VENT PIPE
Terminating
# of 90
Elbows (excl.
vent term.)
Maximum straight
Length
ft
(m)
Min
straight
Length
ft
(m)
48, 65 gal.
Through the Wall
1 175
(53.3)
10
(3.1)
Through the Wall
2 170
(51.8)
10
(3.1)
Through the Wall
3 165
(50.3)
10
(3.1)
Through the Wall
4 160
(48.8)
10
(3.1)
Through the Wall
5 155
(47.2)
10
(3.1)
Through the Roof
0 180
(54.9)
15
(4.6)
Through the Roof
1 175
(53.3)
15
(4.6)
Through the Roof
2 170
(51.8)
15
(4.6)
Through the Roof
3 165
(50.3)
15
(4.6)
Through the Roof
4 160
(48.8)
15
(4.6)
NOTE: When using 4”
(10.2 cm)
vent pipe, use a 4”
(10.1 cm)
to 3”
(7.6
cm)
reducer and exit the building wall with 3”
(7.6 cm)
vent pipe using the