Trouble Shooting Guide continued-
PROBLEM CAUSE
SOLUTION
Insufficient hot
water
Aquastat setting
too low
Adjust aquastat to higher
setting. See Section VII
Undersized boiler
with no priority to
domestic hot water
Rewire for priority
Peak use of hot
water is greater
than tank storage
capacity
Determine peak usage
and compare to tank
capacity
Faulty tank
aquastat
Replace aquastat
Boiler cycles
more than 5
times per day
in summer
Excessive demand
Reduce demand or
consider larger tank
Faulty aquastat
Replace aquastat
Boiler high limit
set too low
Increase boiler high limit
setting