APPENDIX A
ITALIANO
Table 2: Extended configuration parameters (to set temperatures to Fahrenheit degrees see appendix A page
57
).
DFLT
PAR.
DESCRIPTION
SET VALUES
17
C01
Changeover
lower threshold (°C)
0
..
24
30
C02
Changeover
upper threshold (°C)
26
..
48
2
.
0
C03
Heating proportional band
(°C)
0
.
8
..
8
.
0
2
.
0
C04
Cooling proportional band
(°C)
0
.
8
..
8
.
0
0
C05
Heating integrating
time (minutes)
0
..
60
0
C06
Cooling integrating
time (minutes)
0
..
60
20
C07
Heating valve minimum
power (%)
0
..
50
0
C08
Cooling valve minimum
power (%)
0
..
50
3
C09
Fan motor speeds number
1
..
3
0
C10
Fan speed “ “
button limitation
0
..
15
33
C11
Minimum fan power (%)
1
..
100
66
C12
Medium fan power (%)
1
..
100
100
C13
Maximum fan power (%)
1
..
100
50
C14
Minimum fan power with
electric heater ON
0
..
100
0
.
0
C15
Fan signal lower limit
(V)
0
..
10
.
0
10
.
0 C16
Fan signal upper limit (V)
0
..
10
.
0
1
C17
Terminal 3 input function
0
..
22
3
C18
Terminal 4 input function
0
..
22
9
C19
Terminal 16 input function
0
..
23
0
C20
On/Off “ “
button limitation
0
..
7
1
.
5
C21
∆ integration set point (°C)
0
.
0
..
20
.
0
0
C22
Default display
0
Room
Temperature
1
Set point
Temperature
0
C23
Terminal 8 output function
0
..
16
Tab. 4
Tab. 3
Tab. 4
Tab. 4
Tab. 5
Tab. 6