7
1.3 Technical Specifications
GENERAL SPECIFICATIONS
100
120
150
160
200
Output kVA
100
120
150
160
200
Output kW
80
96
120
128
160
Output Power factor
0,8
Parallel Operation
Up to 2 UPS or 1 Redundant
Hot Stand-by Operation
2 UPS (1 Redundant)
Battery charging
temperature compensation
Optional
INPUT
Number of phase
3 phase
Input voltage
220/380 Vac or 230/ 400 Vac 3 phase,N
Voltage tolerance
+15%, -15%
By-pass voltage
220/380 Vac or 230/ 400 Vac 3 phase, N
Input frequency
50 Hz.
±
5%
RFI Level
EN 50091
OUTPUT
Number of phase
3 phase
Nominal Output voltage
220/380 Vac or 230/ 400 Vac 3 phase,N
Voltage regulation tolerance
±
1%
Nominal Output frequency
50 Hz
Output frequency tolerance (line syncron)
±
1%
Output frequency tolerance (free running)
±
0,2%
Efficiency 100% Load
90%
Load Crest Factor
3:1
Total Harmonic Distortion (THD)
<3%
Overload
125% load 10 min.150% load 1 min.
BATTERY
Number of
30
Run time
Optional
Float charge voltage
405 Vdc
End of charge voltage
300 Vdc
INTERFACE
Communication
RS232 (standart) RS485 (optional)
Up to 5 remote monitoring panel
Remote control
Dry contact Line failure, battery low, bypass,
EPO, battery trip in/out
SNMP capability
Optional SNMP adapter
Modem connection
Available
OTHER
Maximum temperature
0-40
°
C
Audible noise
<70 dBA
Dimensions (HxWxD) (mm)
1650x1870x810
1730x1935x870
Содержание T-3100P
Страница 2: ......
Страница 25: ...21 Figure 3 2 Parallel UPS connection ...