background image

B

Selection of asymmetrical Switching Time Delay.

Rapidly changing reactive loads can cause excessive wear on contactors ( eg Arc Welders, Crushers or 
Strip Mills). In this case it is useful to use assymetrical switching of  FAST IN/SLOW OUT.  The ratio is set 
using the + - buttons. If we have

"1"

(Factory setting) we have equal times for switch in and switch out , as 

selected in pos. 2. By selecting any number between 1…..99  we can vary the switch out time up to 99 times
the switch in time.  i.e. if we set to "10" (display 

Y_10

) and have selected a switch time of 5 secs., in Pos 

2, we switch in after 5 secs of lagging kvar demand, but only switch out after the leading kvar has exceeded
the threshold for 5 x 20 secs + Lock out time (see Pos C). If it is required that the switch out time is
quicker than the switch in time (reversal of the above situation) this can be achieved but must be ordered 
when the relay is built.

C

Selection of  Lock Out Time at each Change of Switching Direction

This position allows adjustment of the lock out time on load reversal and on initial energising. If we set to 

L_30

we have 30 secs lock out time, in addition to the time selected in Pos. 2. This will operate each time 

we have load reversal, thus helping to reduce contactor wear. The lock out time is adjustable from 1…254 
sec.; 

Factory setting = 30 secs ( "L_30")

D

Selection of C.T.Ratio .

This is only applicable for CXM relays. Please see the section of these instructions 

“CXM Multi-Meter version” 

On the CX relay the display will be non-operative in this position and will show 

"_

not

"

E

Selection of V.T. Ratio

This is only applicable on CXM relays. Please see the section of these instructions 

CXM Multi-Meter version

On the CX relay the display will be non-operative and will show "_not"

F    Selection of Switching Program.

The switching programs are selected using the + -  buttons:

"Auto" -

Fully automatic self selection of capacitor steps in order to achieve the required power factor with 

no pre-determined switching sequence. Relay voltage measurement L2-L3

"1 1 1 1"

:  Sequential switching in/out with fully automatic recognition of each capacitor size. 

This program could be selected for 

tuned filter banks

where it is essential that each tuned step is

switched sequentially.

"Eaut"

: identical to 

"Auto"

, but for 

single phase operation, with relay measurement voltage taken from 

L1-N

"E111"

: identical to 

"1111"

,  but for 

single phase operation with relay measurement voltage taken L1-

Factory Setting  

"Auto"

Commissioning

Apply the supply, measurement and control voltages. Connect the current transformer, and remove any 
short circuit link. Make sure the Current Transformer is positioned so as to measure the total current of the 
system including the capacitor bank current. On a 3 phase system the measured voltage L2-L3 must always
be taken from the two phases on which the CT is not mounted, i.e. if the CT is on L1, voltage supply 
must be from L2-L3.If a change must be made on site it is preferable to change the voltage connections 
rather than the CT so as to avoid the risk of an open circuit CT.

If the supply is single phase, the appropriate setting must be selected on "F" of the function switch with 
measured voltage connections (L2-L3) changed to single phase. 
Indication "I—O"  :  No current or less than 10mA is flowing in the CT circuit.
If capacitor steps are energised, they will be automatically disconnected after 5 minutes. If the relay 
is in manual mode, (Pos.4) the steps will stay in circuit.
Indication "U—0" measuring voltage is below 50 V or not connected.
The relay will start to control if the measured voltage (L2-L3) is at 50 volts or above, and the reactive 
component of the measured current is 10mA or above.
If the measured voltage falls below 50V, energized steps will be switched off after a 2 sec time delay in 
both automatic and manual mode.

2    Factory Settings of Function Switch

Power factor target = 1                                                                            C.T. Ratio = 100
Step switch time = 60 secs                                                                      V.T. Ratio =  1
Step limit switch = Max of controller                                                          Switch Mode = Auto
Changes can be made using the function switch, but remember any changes 

will only be stored in the 

memory when the function switch is put in pos. 3 

after the change has been made. 

4

Содержание CX

Страница 1: ...T FOR CORRECT MEASUREMENTS Page 7 WIRING DIAGRAM Page 8 Fan Control DIP switch see p6 Function Switch LED Indication Calling for Capacitor steps in LED Indication Calling for Capacitor steps out LED Indication Calling for Capacitor steps in LED Indication Calling for Capacitor steps out Scroll Buttons CXM With Multi Meter CX BPC Boddingtons P wer Controls UNIT 1 ZONE D CHELMSFORD ROAD INDUSTRIAL E...

Страница 2: ...he removable front plastic nameplate For the CX relay there are two push buttons located either side of the function switch For the CXM multi meter version the keys are on the front of the relay They also allow you to roll through the different measured values of U I P Q S F COSPHI If option L fan control is fitted there will be 2 additional DIP switches S1 S2 located behind the name plate to sele...

Страница 3: ...cedure and alarm AL appears in the display The L and F values for each step can be scrolled through with or button and this is a good check to do on regular capacitor bank maintenance The stored values can be re set by pushing buttons and together for longer than 20 sec The regulator will store each step from the moment of re set Automatic mode remains active whilst these checks are made The CXM r...

Страница 4: ...equence Relay voltage measurement L2 L3 1 1 1 1 Sequential switching in out with fully automatic recognition of each capacitor size This program could be selected for tuned filter banks where it is essential that each tuned step is switched sequentially Eaut identical to Auto but for single phase operation with relay measurement voltage taken from L1 N E111 identical to 1111 but for single phase o...

Страница 5: ...achieve the target power factor 12 With the CX or CXM relay it is not necessary to preset any C k value threshold level when to start to switch a step in out The relay selects the most suitable capacitor size to meet the target power factor Consequently capacitor kvar sizes may be mixed Each time they are switched the reactive output unit of value for each step will be recorded in the CX or CXM re...

Страница 6: ...n site the data output from the CX relay can be fed into our Data Logger available as follows DS 21 0 256 MB Approx 2500 events recorded DS 22 _ 0 512 MB Approx 5000 events recorded DS 23 _ 1 024 MB Approx 10000 events recorded The Data Logger can then be taken to the PC for downloading using a WORD programme Optional Features Option L This option has 2 functions 1 Fan Control It is very important...

Страница 7: ...1 4000 e g 800A 5A 160 Factory setting 100 Holding the for longer than 2 secs enables rapid roll through E v t ratio using key or in the range of 1 0 350 0 e g 20 kV 0 1kV 200 Factory setting 1 0 Holding the for longer than 2 secs enables rapid roll through Relay type CXM indicates following energy data selectable by using key or C Power Factor U Measuring voltage I Current in selected phase P Tot...

Страница 8: ...40 VAC 8 415V 10 Normal Voltage Connection is L2 L3 415V 10 unless otrhewrwise specified on the order L1 N connection ONLY used when relay is specified for single phase supply in which case the connections L2 L3 are not made 415V 10 Normal Voltage Connection is L2 L3 415V 10 unless otrhewrwise specified on the order L1 N connection ONLY used when relay is specified for single phase supply in which...

Отзывы: