BPC CX Скачать руководство пользователя страница 3

5

Selection of Step Limitation

This position limits the number of steps in circuit. e.g. if you have a CX12, twelve step controller, but only 
have nine steps connected, adjust this setting to 9. 

Do not set to more than the number of steps on the 

relay as the defective step alarm will be triggered.

6

Automatic display of failed Capacitors

Indication of either failed capacitor steps or unengaged outputs. Indication  "Cd 05" 

(Capacitor Defect No.5)

alternating with 

"Cd 09"

indicates, that steps 5 and 9 are failing. "Alarm" (AL_ _) will be shown in the 

display. Once the fault on the failed steps has been rectified, the alarm signal is cleared by pressing 
b and – for longer than 20 sec. 

"Cd 0"

will show in the display to indicate the alarm is cancelled 

and there are no defective capacitors. (see also (Pos. 9 below) 

7  Counter for the number of times each capacitor step contactor has switched.

The number of switching operations for each contactor are shown in the display, e.g. "OC_ 4" for capacitor 
step No.4 for 2 sec., then "248". This indicates, that contactor no. 4 has completed 248 switching operations.
Other contactors can be selected by using the +/- buttons. The micro-processor stores the data for 
every 10 contactor switching operations. The stored data of all steps can be cancelled by depressing the +/-
buttons together for more than 20 sec. Automatic control is active all the time!

8  Indication of Step kvar

This is a very useful way of keeping a check on capacitor step kvar outputs over a period of time.
The value indicated on display is 

a unit of value proportional

to the step size, but is not the actual kvar. 

This display will show for example, 

"CC 10"

for the 10th step, followed by 2 numbers e.g. 

"L 74" and "F

84".
"F"

stands for the first sensed capacitor size during commissioning and "L" for the last measured value 

after, let´s say several months or years. In this way a check can be kept on the change in kvar output of 
each step, if any. If the selected defective threshold level in pos. 

0

, is exceeded  due to a failed capacitor or 

blown fuses, the CX or CXM  eliminates this step from the control procedure and alarm 

"AL", 

appears in 

the display. The 

"L"

and  

"F"

values for each step can be scrolled through with + or – button, and this is a 

good check to do on regular capacitor bank maintenance. The stored values can be re-set by pushing  
b and – together for longer than 20 sec. The regulator will store each step from the moment of 
re-set. Automatic mode remains active whilst these checks are made. 
The CXM regulators fitted with multi-meter option 

"M"

(Indication of energy data) displays the measured

capacitor sizes in real kvar provided the correct CT ratio factor has been inserted (see page 5) 

9  Selecting and cancelling the alarm you require

Four alarm types are available and these are selected by scrolling through using the + - buttons, when the 
function switch is in position 9.

"A__0"

All alarm indications cancelled. No alarm will appear in the display.

"A__1"

Alarms will be shown , but will cancel themselves once the position has rectified itself.

"A__2"

Any alarm recorded will remain in the display until the fault is rectified and the alarm is manually

cancelled by pr -  together for at least 20 secs.

"A_3"

The alarm stored on the display is cancelled by pressing the  + -  buttons together for at least  5 

secs.
This will re-set alarms for : 

Low PF for at least 75 times step switching time,  – display indication "AL_"
Over Temperature if "L" option is fitted – display indication "HA" (Heating Alarm)
If both alarms are operating – i.e. Low PF and High Temp, the display will show "AH"

Once the alarm is cancelled the display will show "ArES"( alarm reset) 

NB: if the Defective capacitor Step alarm has operated -  with "AL_" in the display, this can only be 

cancelled by going to Pos.6  on the function switch and pr - together for at least 20 secs,.

A

Selection of a 2nd Power Factor Target, or an alarm 

Some tariffs allow a lower power factor at certain times. For example at night in order to compensate for a 
leading pf on the system caused by the Capacitance of buried cable networks in cities. This position of the 
function switch allows you to select  a second target PF, and this second target PF will be triggered by 
applying voltage between 150-240V 50/60Hz  on NT1/NT2 – see wiring diagram. If option "L"  is fitted, the 
lower PF will automatically come into operation if the ambient temperature rises above 57º C.

3

Содержание CX

Страница 1: ...T FOR CORRECT MEASUREMENTS Page 7 WIRING DIAGRAM Page 8 Fan Control DIP switch see p6 Function Switch LED Indication Calling for Capacitor steps in LED Indication Calling for Capacitor steps out LED Indication Calling for Capacitor steps in LED Indication Calling for Capacitor steps out Scroll Buttons CXM With Multi Meter CX BPC Boddingtons P wer Controls UNIT 1 ZONE D CHELMSFORD ROAD INDUSTRIAL E...

Страница 2: ...he removable front plastic nameplate For the CX relay there are two push buttons located either side of the function switch For the CXM multi meter version the keys are on the front of the relay They also allow you to roll through the different measured values of U I P Q S F COSPHI If option L fan control is fitted there will be 2 additional DIP switches S1 S2 located behind the name plate to sele...

Страница 3: ...cedure and alarm AL appears in the display The L and F values for each step can be scrolled through with or button and this is a good check to do on regular capacitor bank maintenance The stored values can be re set by pushing buttons and together for longer than 20 sec The regulator will store each step from the moment of re set Automatic mode remains active whilst these checks are made The CXM r...

Страница 4: ...equence Relay voltage measurement L2 L3 1 1 1 1 Sequential switching in out with fully automatic recognition of each capacitor size This program could be selected for tuned filter banks where it is essential that each tuned step is switched sequentially Eaut identical to Auto but for single phase operation with relay measurement voltage taken from L1 N E111 identical to 1111 but for single phase o...

Страница 5: ...achieve the target power factor 12 With the CX or CXM relay it is not necessary to preset any C k value threshold level when to start to switch a step in out The relay selects the most suitable capacitor size to meet the target power factor Consequently capacitor kvar sizes may be mixed Each time they are switched the reactive output unit of value for each step will be recorded in the CX or CXM re...

Страница 6: ...n site the data output from the CX relay can be fed into our Data Logger available as follows DS 21 0 256 MB Approx 2500 events recorded DS 22 _ 0 512 MB Approx 5000 events recorded DS 23 _ 1 024 MB Approx 10000 events recorded The Data Logger can then be taken to the PC for downloading using a WORD programme Optional Features Option L This option has 2 functions 1 Fan Control It is very important...

Страница 7: ...1 4000 e g 800A 5A 160 Factory setting 100 Holding the for longer than 2 secs enables rapid roll through E v t ratio using key or in the range of 1 0 350 0 e g 20 kV 0 1kV 200 Factory setting 1 0 Holding the for longer than 2 secs enables rapid roll through Relay type CXM indicates following energy data selectable by using key or C Power Factor U Measuring voltage I Current in selected phase P Tot...

Страница 8: ...40 VAC 8 415V 10 Normal Voltage Connection is L2 L3 415V 10 unless otrhewrwise specified on the order L1 N connection ONLY used when relay is specified for single phase supply in which case the connections L2 L3 are not made 415V 10 Normal Voltage Connection is L2 L3 415V 10 unless otrhewrwise specified on the order L1 N connection ONLY used when relay is specified for single phase supply in which...

Отзывы: