24
Start-Up
Use number No. 1 or No. 2 fuel oil only.
Do not attempt to start the burner if excess oil has accumulated.
Do not use gasoline, crankcase draining or any oil containing gasoline.
This equipment must be adjusted and started only by a qualified service agency – an individual or
agency, licensed and experienced with all codes and ordinances, and who is responsible for the
installation and adjustment of the equipment.
1.
Check that all safety devices are in place.
2.
Check that thermostats are correctly connected and set.
3.
Check that the inside of the furnace is free of any fuel residue or foreign materials and that the
refractory chamber has not been damaged.
4.
Check oil burner nozzle to ensure that the right size and type is installed and tight in the adapter.
See preliminary settings for proper nozzle size and type.
5.
Check electrode settings, as they may have been jarred out of position during transportation. See
oil burner instructions for nozzle and electrode setting
6.
Check air setting to ensure that it matches the preliminary air settings as found in Table 9, Table
10, or Table 11.
7. Check that the Burner mounting bolts are tight.
8.
Lubricate burner motor and circulator motor if required.
9.
Open all oil lines valves.
10.
Set room thermostat to call for heat.
11.
Turn service switch on. Burner should start. On one pipe fuel system only you may have to bleed
the oil system. To bleed attach a clear plastic tube to the oil pump bleed port and allow oil to run
until all the air is out of the oil suction line feeding the oil burner. If air is still evident in the bleed
line you must check the oil lines, all fittings, filters and any other connections for tightness. See
burner and fuel pump manufacturers recommendations for proper bleeding of the fuel system.
CAUTION: DO NOT RUN THE PUMP DRY FOR MORE THAN FIVE MINUTES, AS
IRREPAIRABLE DAMAGE MAY RESULT.
12.
Turn “OFF” burner and install pressure gauge and vacuum gauge into the proper ports on the
pump. See the burner manufacturer’s manual for location of ports.
13.
Start burner again and check oil pressure. Adjust if necessary. See oil burner manufacturers’
instructions for pump adjustment.
Start-up Equipment
THE FOLLOWING PROPER COMBUSTION INSTRUMENTS ARE REQUIRED TO
DETERMINE PROPER AIR ADJUSTMENTS AND DRAFT WHEN SETTING UP OR
SERVICING THE OIL BURNER. DO NOT ATTEMPT TO START UP OR SERVICE THE
FURNACE WITHOUT THE PROPER COMBUSTION INSTRUMENTS.
1.
Carbon-dioxide (C0
2
) or Oxygen (0
2
) Analyzer
2.
Draft gauge. Scale should read from +.10" W.C. to -.25" W.C.
3.
Oil Pressure Gauge 0-200 PSI
4.
Stack Thermometer
5.
Plenum Thermometer
6.
Smoke Test Gun
7.
Vacuum Gauge 0-30 in. of Hg