WET LOCATION EMERGENCY LIGHTING UNIT
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS: When using electrical equipment, always adhere to basic safety
precautions including the following:
1. Do not mount near gas or electric heaters.
2. Equipment should be mounted securely in locations and at heights where it will not be readily
subjected to tampering by unauthorized personnel.
3. The use of accessory equipment and replacement parts not recommended by the
MANUFACTURER may cause an unsafe condition.
4. Do not use this equipment for other than its intended purpose.
5. The AC voltage rating of this equipment is specified on the product label. Do not connect equipment
to any other voltage.
6. When this equipment is furnished with halogen type lamps, these additional safeguards apply:
• CAUTION: Wedge-based incandescent lamps are used in this equipment. To avoid shattering, do not operate lamps in excess of rated
voltage. Protect lamps from abrasion and scratches and against liquids when lamp is operating. Dispose of lamps properly.
• The lamps in this unit operate at a high temperature. Do not store or place flammable materials near the lamps.
7. In unheated areas where the temperature may drop below 32ºF for prolonged periods, the battery capacity and total output rating of the
equipment will be redced. Ensure that the equipment will operate in conformance with the applicable National Electric Code and NFPA
Life Safety code requirements. Contact our distributor for further technical assistance.
SAVE THESE INSTRUCTIONS!
INSTALLATION INSTRUCTIONS
1. Mount the equipment securely in place using the provided mounting plates. If accessory mounting devices are being utilized in this
installation, follow any instructions provided with those devides to ensure a safe installation.
2. Extend 24-hour AC supply of rated voltage to the equipment, which is furnished with a dual voltage 120V/277V field selectable input
(see Figure 1 on page 2). Connect unit to utility power using an approved seal tight connector or NEMA4X connector. The unit should
be DRILLED for the connector in the proper location as it relates to the location of the entry point of the power feed coming into the
unit. There are various places inside the unit that are suitable for this incoming power location. For 120V supply, connect the line wire
to the black lead for 277V supply, connect the line wire to the orange lead. Connect neutal wire to the white lead. Connect the ground
wire in accordance with local codes. A green ground lead is provided.
DO NOT
energize circuit at this time.
CAUTION:
Insulate the unused black or orange wire. Failure to insulate the unused wire will cause an unsafe condition.
3. Connect the battery using the RED and BLUE connectors from the circuit board. The equipment is supplied with one battery lead (Red
+ Positive) connected. If the battery is supplied with terminals, connect the blue battery lead to the negative terminal. If the battery is
supplied with leads, connect the two blue leads together with the supplied wire nut.
4. Energize the AC supply. The
CHARGE
indicator will illuminate.
5. Replace the cover.
6. Adjust and focus the lighting heads as required.
FLEXIBLE CONDUIT ONLY!